| Date |
Text |
| 2006-10-15 19:25:27 | ********* UNSAT3RDREVIEW *********** |
| | |
| | ** PLEASE SEE MANY ITEMS FROMTHE TWO PREVIOUS REVIEWS |
| | WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE SEE NEW |
| | COMMENTS DUE TO |
| | INFORMATION SHOWN ON PLANS WHICH WAS |
| | DIFFERENT FROM PREVIOUS REVIEW OR HAS CHANGED IN |
| | DESIGN |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW WITH NEW |
| | NOTES ADDED TO THE END OF THE PREVIOUS |
| | NOTES. |
| | |
| | ** IMPORTANT** |
| | THERE IS A BALANCED OWED OF $460, WHICH WILL BE |
| | REQUIRED TO BE PAID BEFORE ANY PERMIT CAN BE ISSUED. |
| | PLEASE ALSO BE AWARE THE NEXT RESUB WILL ALSO HAVE FEES |
| | DUE. |
| | |
| | |
| | ** IMPORTANT** |
| | THE OCCUPANCY OF UNITS ON SECOND FLOOR GREATLY AFFECTS |
| | MANY COMMENTS FOR CODE COMPLIANCE , WHETHER OR NOT THEY |
| | ARE RESIDENTIAL OR COMMERCIAL OFFICES. |
| | |
| | |
| | 1)NOTE: OK. |
| | |
| | 2)NOTE: OK. |
| | |
| | 3)NOTE: OK SIGNED PLANS. |
| | |
| | 4)NOTE: OK. |
| | |
| | 5)NOTE:NO, PLEASE SEE THE NOTE WITH RESPECT THE |
| | EXHAUST FANS IN OTHER NOTES. OTHER "HOUSE" CIRCUITS |
| | WERE CORRECTED. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2 |
| | NO, PLEASE SEE COMMON AREA |
| | ELECTRICAL STILL BEING SHOWN CIRCUITED |
| | TO ONE OF THE RESIDENTTIAL UNITS. |
| | THIS IS NOT PERMITTED. |
| | |
| | ** PREVIOUS REVIEW NOTEREVIEW #1** |
| | PLEASE SEE NO COMMON AREAS SHALL |
| | BE FED FROM CIRCUIT DERVIED FROM APTS OR |
| | OFFICE UNITS. PLEASE SEE CIRCUITING OF |
| | HALL RECEPTS ARE SHOWN TO ONE UNIT. |
| | PLEASE SEE 210.25 |
| | |
| | 6)NOTE:OK. |
| | |
| | 7)NOTE: OK. |
| | |
| | 8)NOTE:NO, PLEASE SEE TWO ACESSIBLE SMALL APPLIANCE |
| | CIRCUITS ARE REQUIRED ALONG KITCHEN COUNTER SPACE. ONE |
| | MAY NOT BE LOCATED BEHIOND THE FRIG, ALOTHOUGH MAY BE |
| | ON ONE OR MORE OF THE SM APPL CIRCUITS. PLEASE SEE |
| | MINIMUM LOAD WHICHSHALL BE FIGNURED FOR EACH OF THE |
| | SMALL APPLIANCE CIRCUITS. DINING RMS AND AREASOF THE |
| | LIKE. |
| | PLEASE SEE 210.52B1, 210.11C1, 220.16. PLEASE SEE MIN |
| | VA FOR EACH CIRCUIT. PLEASE SEE OTHER COMMENTS WITH |
| | RESPECT TO LOAD CALCULATIONS. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2** |
| | NO, STIL SHOWS ONLY ONE. |
| | |
| | **PREVIOUS REVIEW NOTE REVIEW #1 ** |
| | PLEASE SEE A |
| | MIN OF TWO SMALL |
| | APPLIANCE CIRCUITS ARE REQUIRED PER |
| | 210.52B1. |
| | |
| | 9)NOTE: OK. |
| | |
| | 10)NOTE: OK. |
| | |
| | 11)NOTE: OK. |
| | |
| | 12)NOTE: OK. |
| | |
| | 13)NOTE:NO, PLEASE LOOK AT ALL CIRCUITING AS NOW |
| | SHOWN. PLEASE SEE ARC FAULT IS BEING SHOWN ON |
| | DISHWASHER AND MANY OTHER ITEMS NOT REQUIRED?? IT IS |
| | UNCLEAR OF THE INTENT. THE ORIGINAL AND PREVIOUS |
| | COMMENTS HAD TO DO WITH THE "OUTLETS" IN SLEEPING ROOMS |
| | OR ROOMS WILL BE CONSIDERED SUCH. |
| | IT IS UNCLEAR AT THIS TIME AND RESPONSE LETTER ONLY |
| | MENTIONS THEY ARE REFLECTED.? |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2** |
| | NO, PLEASE SEE THERE ARE |
| | CIRCUITS NOW SHOWN WITH ARC FAULT |
| | PROTECTION WHICH ARE NOT REQUIRED AND |
| | SOME WHICH DO SHOW ARC FAULT PROTECTION |
| | AND SOME THAT DO NOT?? |
| | PLEASE SEE ALL "OUTLETS". |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW#1 ** |
| | PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUITS AS REQUIRD |
| | UNDER THE 2002 NEC 210.12B |
| | PLEASE KNOW, ALL, ELECTRICAL |
| | DEVICES/OUTLETS SUCH AS LTS, SD'S |
| | RECEPTS, FANS ETC SHALL BE AFCI |
| | PROTECTED. |
| | ** PLEASE KNOW, AREAS NOW SHOWN AS |
| | "OFFICES" ARE UNITS WHICH SEEM TO SHOW |
| | POSSIBLE CHANGE IN-USE OR OCCUPANCY. IF |
| | THESE AREAS ARE ADAPTABLE FOR |
| | RESIDENTIAL USE, THEN AFCI PROTECTION |
| | WILL BE REQUIRED FOR THESE ROOMS. |
| | |
| | 14)NOTE:NO, PLEASE SEE CIRCUITING NOTES FOR EXHAIST |
| | FANS. THE CIRCUITING FOR SA'S ARE OK, IT OTHER |
| | CIRCUITING IS CORRECTED AND AFCI PROTECTION IS |
| | INDICATED. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2 ** |
| | OK, HOWEVER 2ND PART OF THIS |
| | NOTE WAS NOT DONE. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| | PLEASE SEE NFPA-70 11.5.1.1 |
| | WHICH REQUIRES THE USE OF SMOKE |
| | DETECTORS INSIDE AND OUTSIDE ALL |
| | SLEEPING RMS OR ADAPTABLE SLEEPING |
| | ROOMS.** PLEASE SEE PREVIOUS NOTES WITH |
| | RESPECT TO THE CIRCUITING OF BEDRMS. |
| | |
| | 15)NOTE: NO, PLEASE SEE THERE ARE STILL MANY ITEMS ON |
| | PLANS WHICH DO NOT CONTAIN CIRCUITING. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2 ** |
| | NO, PLEASE SEE SOME CIRCUITS |
| | ARE NOT COMEPLETE AT THIS TIME IN |
| | DWELLING UNITS AND HOUSE AREAS. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| | PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. PLEASE SEE CIRCUTING |
| | MISSING. |
| | 215.5 |
| | |
| | 16)NOTE: OK. |
| | |
| | 17)NOTE: OK. |
| | |
| | |
| | 18)NOTE: OK. |
| | |
| | 19)NOTE: OK. |
| | |
| | 20)NOTE: NO/OK. PLEASE SEE A DETAIL WAS SUBMITTED |
| | HOWEVER DOES NOT SHOW ALL EGRESS PATHS FOR MIN LIGHTING |
| | LEVELS UNDER NORMAL AND EMERGENCY. PLEASE ALSO SEE A |
| | FIXTURE TYPE IS NOW BEING NOTED AT A HID METAL HALIDE |
| | FOR ONE OF THE EM FIXTURES?? PLEASE SEE THIS DOES NOT |
| | INDICATE ANY QUARTZ/RE-STRIKE. IF AND WHEN POWER IS |
| | INTERUPTED IN AN EMERGENCY, THESE FIXTURES WILL NOT |
| | COME ON PROVIDINGTHE MIN LIGHTING LEVELS WITHIN THE |
| | TIME REQUIRED BEIGN HID FIXTURES. PLEASE EXPLAIN |
| | FIXTURE TYPE, AADJUST FIXTURE TYPE ETC? |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2** |
| | NO, PLEASE SEE A NOTE WAS ADDED |
| | TO PLANS IN LEIU OF THE DETAIL NEEDED |
| | AND REQUIRED. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE PROVIDE THE PHOTO-METRICS FOR |
| | EXITING STAIR AREAS AS NFPA-101 7.8.1.3 |
| | REQUIRES A MIN OF 10FT CANDLES (108 LUX) |
| | FOR THE ALL AREAS OF WALKING SURFACE IN |
| | STAIRS UNDER NORMAL POWER AND IS |
| | PERMITTED TO BE LOWERED TO A MIN OF 1FT |
| | CANDLE (10.8 LUX) UNDER EMERGENCY |
| | CONDITIONS, 7.9.2.2 |
| | |
| | 21)NOTE: OK, HOWEVER PLEASE STILL PLEASE SEE NOTE WITH |
| | RESPECT TO FBC CHAPTER 13 WHICH MAY AFFECT FIXTURES. |
| | |
| | 22)NOTE: OK. |
| | |
| | 23)NOTE:NO, SAME NOTE.PLEASE ALSO SEE NEW NOTES FOR |
| | THE REVISED RISER NOW SUBMITTED FOR FIRST REVIEW. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2** |
| | NO, PLEASE SEE "EQUIPMENT |
| | GROUNDING CONDUCTORS" ARE STILL BEING |
| | SHOWN BEFORE THE FIRST MEANS OF |
| | DISCONNECT. PLEASE SEE NEW NOTESAS |
| | LOCATION WILL CHANGE. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| | PLEASE SEE 250.6, 250.24, NO |
| | "EQUIPMENT GROUNDING CONDUCTORS" SHALL |
| | BE INSTALLED BEFORE THEFIRST MEANS OF DISCONNECT. |
| | PLEASE SEE THESE ARE SHOWN |
| | FROM FPL, TO GUTTER, TO METER ETC. |
| | |
| | 24)NOTE:OK. |
| | |
| | 25)NOTE: OK. |
| | |
| | 26)NOTE: NO, PLEASE SEE PREVIOUS NOTES. CALCULATIONS |
| | SUBMITTED AND SHOWN DO NOT CORRELATE WITH SOME PANEL |
| | SCHEDULES. PLEASE ALSO SEE SOME AS THEY SO NOT MEET NEC |
| | CODE COMPLIANCE. PLEASE SEE OCCUPANCY WILL AFFECT THIS. |
| | PLEASE SEE RESIDENTIALUNITS ALSO. ETC |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2** |
| | NO, PLEASE SUBMIT COMPLETE |
| | CALCULATIONS FOR EACH PANEL FOR USE AS |
| | SHOWN ON PLANS. |
| | PLEASE ALSO SHOW LOADS FOR SERVICE, NONE |
| | WERE SUBMITTED. |
| | |
| | **PREVIOUS REVIEW NOTES REVIEW #1 ** |
| | PLEASE SUBMITLOAD CALCULATIONS FOR |
| | ALL AREAS, PANELS, BLDG. PLEASE SEE |
| | THESE ARE SHOWN A MIXED |
| | USE. PLEASE ADJUST ACCORDINGLY. |
| | PLEASE ALSO INDICATE OF CONTINUOUS LOADS |
| | AT 125%. 215.3,230.42, |
| | 220.10,220.11,220.13 ETC |
| | |
| | 27)NOTE:NO, PLEASE SEE 2004 FBC CHAPTER 13. PLEASE |
| | SEE OCCUPANCY WILL HAVE AN AFFECT ON THIS. PLEASE SEEE |
| | ONLY SOME OF THE FOLLOWING SECTIONS WHICH ARE BEING |
| | BROKEN DOWN. PLEASE KNOW, ALL OF THE CHAPTER WAS GIVEN |
| | ON PREVIOUS REVIEW AS NOTHING WAS SUBMITTED OR SHOWN. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2& .1.3. PLEASE SEE |
| | MANY ITEMS MISSING. |
| | PLEASE SEE 13-415.2.ABC.1,TABLES 415.2.C.1, 415.2.B.1 |
| | PLEASE SEE THE ENERGY CALCULATIONS WERE NOT THE ONLY |
| | ITEM NEEDED. |
| | PLEASE SEE ALL SEPARATE SPACES ETC |
| | PLEASE PROVIDE THE MAX TIMES PERMITTED ON OVER RIDE |
| | DEVICES ETC. ( OS TYPE 30MINS MAX, TIMER TYPE 4HRS |
| | MAX) |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2** |
| | NO, THIS WAS NOT ADDRESSED AND |
| | NO DESIGNS, CALCS, CONTROLS ETC WERE |
| | SUBMITTED FOR REVIEW. PLEASE SEE MIN |
| | CALCULATIONS REQUIRED. |
| | ALSO NO ENERGY CALCULATIONS WERE |
| | SUBMITTED. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| | PLEASE BE SURE TO SEE THE 2004 |
| | FBC CHAPTER 13 WITH RESPECT TO THE |
| | ENERGY CODE AND DESIGNS. PLEASE KNOW |
| | THIS IS A COMMERCIAL BLDG WITH A CHANGE |
| | OF OCCUPANCY WHICH WILL REQUIRE ENERGY |
| | CODE UPGRADES. |
| | |
| | **** NEW NOTES 2ND REVIEW**** |
| | |
| | 28) NOTE: OK, HOWEVER SEE NEW NOTE FROM 3RD REVIEW. |
| | |
| | 29) NOTE:NO/OK, PLEASE SEE A COMPLETELY NEW RISER |
| | DIAGRAM HAS BEEN SUBMITTED, HOWEVER LABELING OF ALL |
| | EQUIPMENT AS PERVIOUSLY NOTED STILL NEEDS TO BE |
| | ADDRESSED FOR EACH MAIN /PANEL ECT. |
| | PLEASE ALSO SEE NEW COMMENTS DUE REVISED RISER FOR NEW |
| | 3RD REVIEW NOTES. |
| | |
| | ** PREVIOUS REVIEW NOTES REVIEW #2** |
| | PLEASE SEE RISER WHICH |
| | INDICATES MORE THAN SEVEN MEANS OF |
| | DISCONNECT WHICH IS NOT PERMITTED. |
| | 230.2,230.70. |
| | PLEASE KNOW A SEPARATE TYPE OF METER |
| | BANK SERVICE MAY BE DONE WITH A MAIN |
| | ETC. |
| | PLEASE ALSO SEE MANY OF THE TENANT |
| | METERS, MAINS ETC ARE LABLED AS "HOUSE" EQUIPMENT?? |
| | PLEASE SEE PANEL "HP" SHOULD BE THE ONLY |
| | PANEL, METER AND MAIN LABLED AS "HOUSE". |
| | 408.4 |
| | 30) NOTE: PLEASE SEE CLOSET LT IN UNIT |
| | "C" WHICH DOES NOT MEET 410.8 |
| | |
| | 30) NOTE:NO, SAME, PLEASE SEE REPSONSE LTR MENTIONS |
| | THIS WAS ADDRESSED, HOWEVER SEE PLANS ARE STILL SHOWING |
| | MULTIPLE CIRCUITS FOR THE SAME EXHAUST FANS AND IF SOME |
| | OF THESE ARE SUPPOSE TO BE ON "HOUSE PANEL " AS |
| | REPSONSE LETTER MENTIONS, THEN PLEASE SEE PLANS AS |
| | THESE ARE STILL SHOWN TO UNIT PANELS FOR TENANTS WHICH |
| | IS NOT PERMITTED. SEE NOTES ABOVE WITH RESPECT TO |
| | "HOUSE EQUIPMENT' WHICH IS NOT PERMITTED ON TENANT |
| | PANELS. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2** |
| | PLEASE SEE SOME UNITS SHOW AND |
| | LABEL "TWO" EXHAUST FAN CIRCUITS?? |
| | PLEASE ALSO SEE ARC FAULT CIRCUITING. |
| | PLEASE SEE MANY OF THESE DO NOT |
| | CORRELATE WITH CIRCUITING SHOWN ON PLANS |
| | AND DEVICES. SOME ARE NOT AS LABELED. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 31) NOTE: OK, RELOCATED PANELS. |
| | |
| | 32) NOTE: OK, HOWEVER SEE NOTES FOR CONTROL OF LTS. IF |
| | THIS DOES BECOME A ROOM WHICH REQUIRES A PUMP OR |
| | CONTROLLER SOME ELECTRICAL ITEMS WILL BE REQUIRED. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2** |
| | PLEASE SEE PLANS MENTIONS |
| | "SPRINKLER ROOM" ? WHAT IS THIS AND IS |
| | THERE LIGHTING FOR SERVICE OF EQUIPMENT |
| | ETC? |
| | LS 101 7.8 |
| | |
| | 33) NOTE:NO, PLEASE SEE A NOTICE WAS GIVEN WITH |
| | RESPECT TO REPEAT COMMENTS. PLEASE KNOW AS PLANS WERE |
| | SUBMITTED THE FIRST TWO TIMES AS "PLAN REVIEW ONLY" THE |
| | FEE WILL NOT APPLY FOR THIS REVIEW, HOWEVER PLEASE BE |
| | AWARE IF "ANY " OF THE SAME CODE COMPLIANT COMMENTS |
| | COME BACK WHICH ARE REPEAT FOR THENEXT REVIEW A FEE |
| | WILL BE ASSESSES AS REQUIRED PER FLORIDA STATUE GIVEN. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2 ** |
| | PLEASE SEE COPY OF FS |
| | 553.80(2)B) WITH RESPECT TO REPEAT |
| | COMMENTS FOR CODE COMPLIANCE AS MANY OF |
| | THESE COMMENTS ARE THE SAME AS THE |
| | PREVIOUS REVIEW. THIS IS ONLY BEING |
| | GIVEN AS A NOTICE AT THIS TIME. |
| | |
| | |
| | **** NEW NOTES FOR 3RD REVIEW ***** |
| | |
| | 34) NOTE: PLEASE SEE 210.52C1-5 FOR SPACING OF GFI |
| | RECEPTS ALONG KTICHEN COUNTER SPACE. PLEASE SEE AS |
| | SHOWN AND IF THE OCCUPANCY IS GOING TO BE RESIDENTIAL, |
| | THEN THE SPACING AS SHOWN IN SOME UNITS DO NOT MEET |
| | CODE GIVEN. |
| | |
| | 35) NOTE: PLEASE PROVIDE ALL AIC RATINGS FOR ALL NEW |
| | SERVICE EQUIPMENT AS SHOWN. ALL MAINS PANELS ETC SHALL |
| | MEET 110.9 AND PLEASE SEE 240.12 FOR SELECTIVE |
| | COORDINATION. |
| | |
| | 36) NOTE: PLEASE SEE AS RISER CONTAINS A NEW MAIN, |
| | PLEASE NOW INDICATE A "FLOATING NEUTRAL" FORALL |
| | METERS ON THE SECONDARY SIDE OF THE NEW MAIN. 250.6, |
| | 250.24B |
| | PLEASE ALSO SEE NOTE ON RISER SHEETS WHICH BODNIGN W/ |
| | EMT TO MEET 250.66. PLEASE SEE ALL NEUTRALS AND |
| | EQUIPMENT GROUNDS ARE REQUIRED TO BE SEPARATE AFTER THE |
| | FIRST MEANS OF DISCONNECT. |
| | |
| | 37) NOTE: PLEASE SEE PLANS NOW MENTIONS AS FA SYSTEM TO |
| | BE INSTALLED, YET NO INFORMATION WAS SUBMITTED FOR |
| | THIS.? PLEASE CLARIFY THE SMOKE DEVICES ON PLANS. |
| | PLEASE SEE NFPA-72 DEFINITIONS FOR SA (SMOKE ALARMS) |
| | AND SD (SMOKE DETECTORS). PLEASE ADJUST ACCORDINGLY ID |
| | UTILIZING A SYSTEM AS PART OF THE BUILDING. NFPA-72 |
| | 11.5, 11.8 ETC |
| | |
| | 38) NOTE: PLEASE SEE A PREVIOUS NOTE MENTIONED |
| | QUALIFICATIONS FOR LIMITS ON PLAN DESIGN. PLEASE SEE FS |
| | 471.003, 471.025, 481.221. PLEASE KNOW, DUE TO THE |
| | REPEAT COMMENTS FOR CODE COMPLIANCE REPEATED , ONE SET |
| | OF EACH ELECTRICAL SET OF PLANS SUBMITTED ARE BEING |
| | RETAINED FOR POSSIBLE REVIEW AND SUBMISSION TO THE |
| | FLORIDA BOARD OF ARCHITECTS AND LEGAL COUNSEL TO THE |
| | BOARD. |
| | PLEASE ADDRESS ALL COMMENTS. TO DATE, NO ONE HAS |
| | CONTACTED THIS OFFICE IF THERE WERE ANY COMMENTSOR |
| | QUESTIONS ON SAID REVIEW COMMENTS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |