Plan Review Notes
Plan Review Notes For Permit 05121124
Permit Number 05121124
Review Stop E
Sequence Number 4
Notes
Date Text
2006-10-15 19:25:27********* UNSAT3RDREVIEW ***********
  
 ** PLEASE SEE MANY ITEMS FROMTHE TWO PREVIOUS REVIEWS
 WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE SEE NEW
 COMMENTS DUE TO
 INFORMATION SHOWN ON PLANS WHICH WAS
 DIFFERENT FROM PREVIOUS REVIEW OR HAS CHANGED IN
 DESIGN
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW WITH NEW
 NOTES ADDED TO THE END OF THE PREVIOUS
 NOTES.
  
 ** IMPORTANT**
 THERE IS A BALANCED OWED OF $460, WHICH WILL BE
 REQUIRED TO BE PAID BEFORE ANY PERMIT CAN BE ISSUED.
 PLEASE ALSO BE AWARE THE NEXT RESUB WILL ALSO HAVE FEES
 DUE.
  
  
 ** IMPORTANT**
 THE OCCUPANCY OF UNITS ON SECOND FLOOR GREATLY AFFECTS
 MANY COMMENTS FOR CODE COMPLIANCE , WHETHER OR NOT THEY
 ARE RESIDENTIAL OR COMMERCIAL OFFICES.
  
  
 1)NOTE: OK.
  
 2)NOTE: OK.
  
 3)NOTE: OK SIGNED PLANS.
  
 4)NOTE: OK.
  
 5)NOTE:NO, PLEASE SEE THE NOTE WITH RESPECT THE
 EXHAUST FANS IN OTHER NOTES. OTHER "HOUSE" CIRCUITS
 WERE CORRECTED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2
 NO, PLEASE SEE COMMON AREA
 ELECTRICAL STILL BEING SHOWN CIRCUITED
 TO ONE OF THE RESIDENTTIAL UNITS.
 THIS IS NOT PERMITTED.
  
 ** PREVIOUS REVIEW NOTEREVIEW #1**
 PLEASE SEE NO COMMON AREAS SHALL
 BE FED FROM CIRCUIT DERVIED FROM APTS OR
 OFFICE UNITS. PLEASE SEE CIRCUITING OF
 HALL RECEPTS ARE SHOWN TO ONE UNIT.
 PLEASE SEE 210.25
  
 6)NOTE:OK.
  
 7)NOTE: OK.
  
 8)NOTE:NO, PLEASE SEE TWO ACESSIBLE SMALL APPLIANCE
 CIRCUITS ARE REQUIRED ALONG KITCHEN COUNTER SPACE. ONE
 MAY NOT BE LOCATED BEHIOND THE FRIG, ALOTHOUGH MAY BE
 ON ONE OR MORE OF THE SM APPL CIRCUITS. PLEASE SEE
 MINIMUM LOAD WHICHSHALL BE FIGNURED FOR EACH OF THE
 SMALL APPLIANCE CIRCUITS. DINING RMS AND AREASOF THE
 LIKE.
 PLEASE SEE 210.52B1, 210.11C1, 220.16. PLEASE SEE MIN
 VA FOR EACH CIRCUIT. PLEASE SEE OTHER COMMENTS WITH
 RESPECT TO LOAD CALCULATIONS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, STIL SHOWS ONLY ONE.
  
 **PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE A
 MIN OF TWO SMALL
 APPLIANCE CIRCUITS ARE REQUIRED PER
 210.52B1.
  
 9)NOTE: OK.
  
 10)NOTE: OK.
  
 11)NOTE: OK.
  
 12)NOTE: OK.
  
 13)NOTE:NO, PLEASE LOOK AT ALL CIRCUITING AS NOW
 SHOWN. PLEASE SEE ARC FAULT IS BEING SHOWN ON
 DISHWASHER AND MANY OTHER ITEMS NOT REQUIRED?? IT IS
 UNCLEAR OF THE INTENT. THE ORIGINAL AND PREVIOUS
 COMMENTS HAD TO DO WITH THE "OUTLETS" IN SLEEPING ROOMS
 OR ROOMS WILL BE CONSIDERED SUCH.
 IT IS UNCLEAR AT THIS TIME AND RESPONSE LETTER ONLY
 MENTIONS THEY ARE REFLECTED.?
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SEE THERE ARE
 CIRCUITS NOW SHOWN WITH ARC FAULT
 PROTECTION WHICH ARE NOT REQUIRED AND
 SOME WHICH DO SHOW ARC FAULT PROTECTION
 AND SOME THAT DO NOT??
 PLEASE SEE ALL "OUTLETS".
  
 ** PREVIOUS REVIEW NOTE REVIEW#1 **
 PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS AS REQUIRD
 UNDER THE 2002 NEC 210.12B
 PLEASE KNOW, ALL, ELECTRICAL
 DEVICES/OUTLETS SUCH AS LTS, SD'S
 RECEPTS, FANS ETC SHALL BE AFCI
 PROTECTED.
 ** PLEASE KNOW, AREAS NOW SHOWN AS
 "OFFICES" ARE UNITS WHICH SEEM TO SHOW
 POSSIBLE CHANGE IN-USE OR OCCUPANCY. IF
 THESE AREAS ARE ADAPTABLE FOR
 RESIDENTIAL USE, THEN AFCI PROTECTION
 WILL BE REQUIRED FOR THESE ROOMS.
  
 14)NOTE:NO, PLEASE SEE CIRCUITING NOTES FOR EXHAIST
 FANS. THE CIRCUITING FOR SA'S ARE OK, IT OTHER
 CIRCUITING IS CORRECTED AND AFCI PROTECTION IS
 INDICATED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2 **
 OK, HOWEVER 2ND PART OF THIS
 NOTE WAS NOT DONE.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE NFPA-70 11.5.1.1
 WHICH REQUIRES THE USE OF SMOKE
 DETECTORS INSIDE AND OUTSIDE ALL
 SLEEPING RMS OR ADAPTABLE SLEEPING
 ROOMS.** PLEASE SEE PREVIOUS NOTES WITH
 RESPECT TO THE CIRCUITING OF BEDRMS.
  
 15)NOTE: NO, PLEASE SEE THERE ARE STILL MANY ITEMS ON
 PLANS WHICH DO NOT CONTAIN CIRCUITING.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2 **
 NO, PLEASE SEE SOME CIRCUITS
 ARE NOT COMEPLETE AT THIS TIME IN
 DWELLING UNITS AND HOUSE AREAS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE. PLEASE SEE CIRCUTING
 MISSING.
 215.5
  
 16)NOTE: OK.
  
 17)NOTE: OK.
  
  
 18)NOTE: OK.
  
 19)NOTE: OK.
  
 20)NOTE: NO/OK. PLEASE SEE A DETAIL WAS SUBMITTED
 HOWEVER DOES NOT SHOW ALL EGRESS PATHS FOR MIN LIGHTING
 LEVELS UNDER NORMAL AND EMERGENCY. PLEASE ALSO SEE A
 FIXTURE TYPE IS NOW BEING NOTED AT A HID METAL HALIDE
 FOR ONE OF THE EM FIXTURES?? PLEASE SEE THIS DOES NOT
 INDICATE ANY QUARTZ/RE-STRIKE. IF AND WHEN POWER IS
 INTERUPTED IN AN EMERGENCY, THESE FIXTURES WILL NOT
 COME ON PROVIDINGTHE MIN LIGHTING LEVELS WITHIN THE
 TIME REQUIRED BEIGN HID FIXTURES. PLEASE EXPLAIN
 FIXTURE TYPE, AADJUST FIXTURE TYPE ETC?
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SEE A NOTE WAS ADDED
 TO PLANS IN LEIU OF THE DETAIL NEEDED
 AND REQUIRED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE PROVIDE THE PHOTO-METRICS FOR
 EXITING STAIR AREAS AS NFPA-101 7.8.1.3
 REQUIRES A MIN OF 10FT CANDLES (108 LUX)
 FOR THE ALL AREAS OF WALKING SURFACE IN
 STAIRS UNDER NORMAL POWER AND IS
 PERMITTED TO BE LOWERED TO A MIN OF 1FT
 CANDLE (10.8 LUX) UNDER EMERGENCY
 CONDITIONS, 7.9.2.2
  
 21)NOTE: OK, HOWEVER PLEASE STILL PLEASE SEE NOTE WITH
 RESPECT TO FBC CHAPTER 13 WHICH MAY AFFECT FIXTURES.
  
 22)NOTE: OK.
  
 23)NOTE:NO, SAME NOTE.PLEASE ALSO SEE NEW NOTES FOR
 THE REVISED RISER NOW SUBMITTED FOR FIRST REVIEW.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SEE "EQUIPMENT
 GROUNDING CONDUCTORS" ARE STILL BEING
 SHOWN BEFORE THE FIRST MEANS OF
 DISCONNECT. PLEASE SEE NEW NOTESAS
 LOCATION WILL CHANGE.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE 250.6, 250.24, NO
 "EQUIPMENT GROUNDING CONDUCTORS" SHALL
 BE INSTALLED BEFORE THEFIRST MEANS OF DISCONNECT.
 PLEASE SEE THESE ARE SHOWN
 FROM FPL, TO GUTTER, TO METER ETC.
  
 24)NOTE:OK.
  
 25)NOTE: OK.
  
 26)NOTE: NO, PLEASE SEE PREVIOUS NOTES. CALCULATIONS
 SUBMITTED AND SHOWN DO NOT CORRELATE WITH SOME PANEL
 SCHEDULES. PLEASE ALSO SEE SOME AS THEY SO NOT MEET NEC
 CODE COMPLIANCE. PLEASE SEE OCCUPANCY WILL AFFECT THIS.
 PLEASE SEE RESIDENTIALUNITS ALSO. ETC
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SUBMIT COMPLETE
 CALCULATIONS FOR EACH PANEL FOR USE AS
 SHOWN ON PLANS.
 PLEASE ALSO SHOW LOADS FOR SERVICE, NONE
 WERE SUBMITTED.
  
 **PREVIOUS REVIEW NOTES REVIEW #1 **
 PLEASE SUBMITLOAD CALCULATIONS FOR
 ALL AREAS, PANELS, BLDG. PLEASE SEE
 THESE ARE SHOWN A MIXED
 USE. PLEASE ADJUST ACCORDINGLY.
 PLEASE ALSO INDICATE OF CONTINUOUS LOADS
 AT 125%. 215.3,230.42,
 220.10,220.11,220.13 ETC
  
 27)NOTE:NO, PLEASE SEE 2004 FBC CHAPTER 13. PLEASE
 SEE OCCUPANCY WILL HAVE AN AFFECT ON THIS. PLEASE SEEE
 ONLY SOME OF THE FOLLOWING SECTIONS WHICH ARE BEING
 BROKEN DOWN. PLEASE KNOW, ALL OF THE CHAPTER WAS GIVEN
 ON PREVIOUS REVIEW AS NOTHING WAS SUBMITTED OR SHOWN.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2& .1.3. PLEASE SEE
 MANY ITEMS MISSING.
 PLEASE SEE 13-415.2.ABC.1,TABLES 415.2.C.1, 415.2.B.1
 PLEASE SEE THE ENERGY CALCULATIONS WERE NOT THE ONLY
 ITEM NEEDED.
 PLEASE SEE ALL SEPARATE SPACES ETC
 PLEASE PROVIDE THE MAX TIMES PERMITTED ON OVER RIDE
 DEVICES ETC. ( OS TYPE 30MINS MAX, TIMER TYPE 4HRS
 MAX)
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, THIS WAS NOT ADDRESSED AND
 NO DESIGNS, CALCS, CONTROLS ETC WERE
 SUBMITTED FOR REVIEW. PLEASE SEE MIN
 CALCULATIONS REQUIRED.
 ALSO NO ENERGY CALCULATIONS WERE
 SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE BE SURE TO SEE THE 2004
 FBC CHAPTER 13 WITH RESPECT TO THE
 ENERGY CODE AND DESIGNS. PLEASE KNOW
 THIS IS A COMMERCIAL BLDG WITH A CHANGE
 OF OCCUPANCY WHICH WILL REQUIRE ENERGY
 CODE UPGRADES.
  
 **** NEW NOTES 2ND REVIEW****
  
 28) NOTE: OK, HOWEVER SEE NEW NOTE FROM 3RD REVIEW.
  
 29) NOTE:NO/OK, PLEASE SEE A COMPLETELY NEW RISER
 DIAGRAM HAS BEEN SUBMITTED, HOWEVER LABELING OF ALL
 EQUIPMENT AS PERVIOUSLY NOTED STILL NEEDS TO BE
 ADDRESSED FOR EACH MAIN /PANEL ECT.
 PLEASE ALSO SEE NEW COMMENTS DUE REVISED RISER FOR NEW
 3RD REVIEW NOTES.
  
 ** PREVIOUS REVIEW NOTES REVIEW #2**
 PLEASE SEE RISER WHICH
 INDICATES MORE THAN SEVEN MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED.
 230.2,230.70.
 PLEASE KNOW A SEPARATE TYPE OF METER
 BANK SERVICE MAY BE DONE WITH A MAIN
 ETC.
 PLEASE ALSO SEE MANY OF THE TENANT
 METERS, MAINS ETC ARE LABLED AS "HOUSE" EQUIPMENT??
 PLEASE SEE PANEL "HP" SHOULD BE THE ONLY
 PANEL, METER AND MAIN LABLED AS "HOUSE".
 408.4
 30) NOTE: PLEASE SEE CLOSET LT IN UNIT
 "C" WHICH DOES NOT MEET 410.8
  
 30) NOTE:NO, SAME, PLEASE SEE REPSONSE LTR MENTIONS
 THIS WAS ADDRESSED, HOWEVER SEE PLANS ARE STILL SHOWING
 MULTIPLE CIRCUITS FOR THE SAME EXHAUST FANS AND IF SOME
 OF THESE ARE SUPPOSE TO BE ON "HOUSE PANEL " AS
 REPSONSE LETTER MENTIONS, THEN PLEASE SEE PLANS AS
 THESE ARE STILL SHOWN TO UNIT PANELS FOR TENANTS WHICH
 IS NOT PERMITTED. SEE NOTES ABOVE WITH RESPECT TO
 "HOUSE EQUIPMENT' WHICH IS NOT PERMITTED ON TENANT
 PANELS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 PLEASE SEE SOME UNITS SHOW AND
 LABEL "TWO" EXHAUST FAN CIRCUITS??
 PLEASE ALSO SEE ARC FAULT CIRCUITING.
 PLEASE SEE MANY OF THESE DO NOT
 CORRELATE WITH CIRCUITING SHOWN ON PLANS
 AND DEVICES. SOME ARE NOT AS LABELED.
 FBC 106.1.2 ADMIN SECT.
  
 31) NOTE: OK, RELOCATED PANELS.
  
 32) NOTE: OK, HOWEVER SEE NOTES FOR CONTROL OF LTS. IF
 THIS DOES BECOME A ROOM WHICH REQUIRES A PUMP OR
 CONTROLLER SOME ELECTRICAL ITEMS WILL BE REQUIRED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 PLEASE SEE PLANS MENTIONS
 "SPRINKLER ROOM" ? WHAT IS THIS AND IS
 THERE LIGHTING FOR SERVICE OF EQUIPMENT
 ETC?
 LS 101 7.8
  
 33) NOTE:NO, PLEASE SEE A NOTICE WAS GIVEN WITH
 RESPECT TO REPEAT COMMENTS. PLEASE KNOW AS PLANS WERE
 SUBMITTED THE FIRST TWO TIMES AS "PLAN REVIEW ONLY" THE
 FEE WILL NOT APPLY FOR THIS REVIEW, HOWEVER PLEASE BE
 AWARE IF "ANY " OF THE SAME CODE COMPLIANT COMMENTS
 COME BACK WHICH ARE REPEAT FOR THENEXT REVIEW A FEE
 WILL BE ASSESSES AS REQUIRED PER FLORIDA STATUE GIVEN.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2 **
 PLEASE SEE COPY OF FS
 553.80(2)B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE AS MANY OF
 THESE COMMENTS ARE THE SAME AS THE
 PREVIOUS REVIEW. THIS IS ONLY BEING
 GIVEN AS A NOTICE AT THIS TIME.
  
  
 **** NEW NOTES FOR 3RD REVIEW *****
  
 34) NOTE: PLEASE SEE 210.52C1-5 FOR SPACING OF GFI
 RECEPTS ALONG KTICHEN COUNTER SPACE. PLEASE SEE AS
 SHOWN AND IF THE OCCUPANCY IS GOING TO BE RESIDENTIAL,
 THEN THE SPACING AS SHOWN IN SOME UNITS DO NOT MEET
 CODE GIVEN.
  
 35) NOTE: PLEASE PROVIDE ALL AIC RATINGS FOR ALL NEW
 SERVICE EQUIPMENT AS SHOWN. ALL MAINS PANELS ETC SHALL
 MEET 110.9 AND PLEASE SEE 240.12 FOR SELECTIVE
 COORDINATION.
  
 36) NOTE: PLEASE SEE AS RISER CONTAINS A NEW MAIN,
 PLEASE NOW INDICATE A "FLOATING NEUTRAL" FORALL
 METERS ON THE SECONDARY SIDE OF THE NEW MAIN. 250.6,
 250.24B
 PLEASE ALSO SEE NOTE ON RISER SHEETS WHICH BODNIGN W/
 EMT TO MEET 250.66. PLEASE SEE ALL NEUTRALS AND
 EQUIPMENT GROUNDS ARE REQUIRED TO BE SEPARATE AFTER THE
 FIRST MEANS OF DISCONNECT.
  
 37) NOTE: PLEASE SEE PLANS NOW MENTIONS AS FA SYSTEM TO
 BE INSTALLED, YET NO INFORMATION WAS SUBMITTED FOR
 THIS.? PLEASE CLARIFY THE SMOKE DEVICES ON PLANS.
 PLEASE SEE NFPA-72 DEFINITIONS FOR SA (SMOKE ALARMS)
 AND SD (SMOKE DETECTORS). PLEASE ADJUST ACCORDINGLY ID
 UTILIZING A SYSTEM AS PART OF THE BUILDING. NFPA-72
 11.5, 11.8 ETC
  
 38) NOTE: PLEASE SEE A PREVIOUS NOTE MENTIONED
 QUALIFICATIONS FOR LIMITS ON PLAN DESIGN. PLEASE SEE FS
 471.003, 471.025, 481.221. PLEASE KNOW, DUE TO THE
 REPEAT COMMENTS FOR CODE COMPLIANCE REPEATED , ONE SET
 OF EACH ELECTRICAL SET OF PLANS SUBMITTED ARE BEING
 RETAINED FOR POSSIBLE REVIEW AND SUBMISSION TO THE
 FLORIDA BOARD OF ARCHITECTS AND LEGAL COUNSEL TO THE
 BOARD.
 PLEASE ADDRESS ALL COMMENTS. TO DATE, NO ONE HAS
 CONTACTED THIS OFFICE IF THERE WERE ANY COMMENTSOR
 QUESTIONS ON SAID REVIEW COMMENTS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved