| 2006-07-06 00:00:00 | ** |
| | ********* UNSAT2ND REVIEW *********** |
| | |
| | ** PLEASE SEE MANY ITEMS FROM PREVIOUS |
| | REVIEW AND SOME NEW ITEMS DUE TO |
| | INFORMATION SHOWN ON PLANS WHICH WAS |
| | DIFFERENT FROM PREVIOUS REVIEW. |
| | |
| | ** PLEASE KNOW, PLANS HAVE NOW BEEN |
| | SUBMITTED FOR PERMIT. |
| | PLEASE SEE THE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW WITH NEW |
| | NOTES ADDED TO THE END OF THE PREVIOUS |
| | NOTES. |
| | |
| | ** IMPORTANT** |
| | PLEASE SEE AS REQUESTED ON PREVIOUS |
| | REVIEW, PLEASE SUBMIT ONE SET OF THE |
| | OLD/VOIDED SETS FOR REFERENCE. THIS WAS |
| | NOT DONE. |
| | |
| | 1)NOTE:NO, PLEASE SEE COVER SHEETS |
| | ONLY MENTIONS THE CODES AND NOT THE |
| | YEARS OF EDITIONS. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE THAT ALL DESIGNS AND |
| | CODES ARE REFERENCED TO THE CURRENT |
| | CODES ADOPTED BY THE STATE OF FLORIDA. |
| | PLEASE KNOW, WE ARE CURRENTLY UNDER THE |
| | 2004 FLORIDA BLDG CODE. |
| | 2002 NFPA-70, 2002 NFPA-72,2003 NFPA-101 |
| | PLEASE ADJUST. |
| | PLEASE ALSO SEE NOTES BELOW AS |
| | ELECTRICAL CODE IS BEING REFERENCED FROM |
| | THE 1996 |
| | NFPA-70 (NEC). |
| | |
| | 2)NOTE: OK, AS TITLE BLOCKS HAVE BEEN |
| | REVISED AND ENGINEERING FIRM AND |
| | ENGINEER IS NO LONGER DOING THE PROJECT. |
| | HOWEVER PLEASE SEE NEW NOTES. |
| | |
| | **PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING INFORMATION |
| | AND LICENSE INFORMATION REQUIRED ON |
| | TITLE BLOCKS FOR THE ARCHITECTUAL FIRM, |
| | ENGINEER AND FIRM? ETC. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002, |
| | 61G1-16.004 AND FLORIDA |
| | STATUES, 481.219, 471.023 . |
| | PLEASE KNOW: THIS IS REQUIRED OF ALL |
| | TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 3)NOTE: NO, PLEASE SEE IT SEEMS THE |
| | ENGINEER AS SHOWN ON PREVIOUS PLANS HAS |
| | BEEN REMOVED AND THE PLANS ARE NOW DONE |
| | BY AN ARCHITECT. PLEASE SEE NEW COMMENTS PERTAINING TO |
| | THE PLANS AND PLEASE SEE |
| | THAT THE PREVIOUS NOTE STILL APPLIES TO |
| | THE ARCGITECT OF RECORD. PLEASE SEE |
| | PLANS ARE CLEARLY "SIGNED" WITH |
| | "INITIALS". IF THIS IS THE "LEGAL |
| | SIGNATURE" OF SAID ARCHITECT, PLEASE |
| | PROVIDE A SIGNED,DATED AND SEALED |
| | NOTORIZED LETTER FOR LEGAL SIGNATURE |
| | VERIFICATION. THIS WILL BE PLACED IN OUR |
| | SIGNATURE FILE FOR FUTURE REFERENCE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE ALSO PROVIDE A SIGNED, DATED AND |
| | SEALED LETTER FOR THE ENGINEER AS SHOWN |
| | ON PLANS AFFIRMING THE LEGAL SIGNATURE |
| | ON SAID PLANS. PLANS APEAR TO INDICATE INITIAL(S)? THIS |
| | LETTER IS TO BE CORRECTLY |
| | NOTORIZED, AND WILL BE PLACED IN OUR |
| | SIGNATURE FILE FOR FUTUREREFERENCE. |
| | |
| | 4)NOTE: NO, PLEASE SEE LOWER POWER PLANS |
| | INDICATE ROOF TOP GFI'S AND THE TWO ARE |
| | FED FROM FIRST FLR TENANT PANELS. THESE |
| | SHOULD BE FED FROM HOUSE PANEL. |
| | |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE THE ROOF TOP |
| | RECEPTS AS GFI OR GFI PROTECTED AS |
| | REQUIRED PER 210.8B2 |
| | |
| | 5)NOTE: NO, PLEASE SEE COMMON AREA |
| | ELECTRICAL STILL BEING SHOWN CIRCUITED |
| | TO ONE OF THE RESIDENTTIAL UNITS. |
| | THIS IS NOT PERMITTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE NO COMMON AREAS SHALL |
| | BE FED FROM CIRCUIT DERVIED FROM APTS OR |
| | OFFICE UNITS. PLEASE SEE CIRCUITING OF |
| | HALL RECEPTS ARE SHOWN TO ONE UNIT. |
| | PLEASE SEE 210.25 |
| | |
| | 6)NOTE:NO, PLEASE SEE CODE CHANGED IN |
| | 1993 TO REQUIRED "ALL" NOT ONLY RECEPTS |
| | LOCATED WITHIN 6' OF SINK. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SHOW ALL KITCHEN |
| | COUNTERSPACE RECEPTS AS GFI/ GFI |
| | PROTECTED AS REQUIRED PER 210.8A6 |
| | |
| | 7)NOTE: NO, SAME NOTE: PLEASE SEE |
| | KITCHENS IN OTHER THAN DWELLING UNITS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE IF OFFICE UNITS WHICH |
| | WILL ALSO BE REQUIRED TO HAVE GFI |
| | RECEPTS,IN EITHER CASE ON POSSIBLE USE |
| | CHANGE TO DWELLING UNITS, OR AS REQUIRED |
| | PER 210.8B3 |
| | |
| | 8)NOTE: NO, STIL SHOWS ONLY ONE. |
| | |
| | **PREVIOUS REVIEW NOTE ** PLEASE SEE A |
| | MIN OF TWO SMALL |
| | APPLIANCE CIRCUITS ARE REQUIED PER |
| | 210.52B1. |
| | |
| | 9)NOTE: OK. |
| | |
| | 10)NOTE: OK. |
| | |
| | 11)NOTE: OK. |
| | |
| | 12)NOTE: OK. |
| | |
| | 13)NOTE: NO, PLEASE SEE THERE ARE |
| | CIRCUITS NOW SHOWN WITH ARC FAULT |
| | PROTECTION WHICH ARE NOT REQUIRED AND |
| | SOME WHICH DO SHOW ARC FAULT PROTECTION |
| | AND SOME THAT DO NOT?? |
| | PLEASE SEE ALL "OUTLETS". |
| | |
| | ** PREVIOUS REVIEW NOTES ** |
| | PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUITS AS REQUIRD |
| | UNDER THE 2002 NEC 210.12B |
| | PLEASE KNOW, ALL, ELECTRICAL |
| | DEVICES/OUTLETS SUCH AS LTS, SD'S |
| | RECEPTS, FANS ETC SHALL BE AFCI |
| | PROTECTED. |
| | ** PLEASE KNOW, AREAS NOW SHOWN AS |
| | "OFFICES" ARE UNITS WHICH SEEM TO SHOW |
| | POSSIBLE CHANGE IN-USE OR OCCUPANCY. IF |
| | THESE AREAS ARE ADAPTABLE FOR |
| | RESIDENTIAL USE, THEN AFCI PROTECTION |
| | WILL BE REQUIRED FOR THESE ROOMS. |
| | |
| | 14)NOTE: OK, HOWEVER 2ND PART OF THIS |
| | NOTE WAS NOT DONE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE NFPA-70 11.5.1.1 |
| | WHICH REQUIRES THE USE OF SMOKE |
| | DETECTORS INSIDE AND OUTSIDE ALL |
| | SLEEPING RMS OR ADAPTABLE SLEEPING |
| | ROOMS.** PLEASE SEE PREVIOUS NOTES WITH |
| | RESPECT TO THE CIRCUITING OF BEDRMS. |
| | |
| | 15)NOTE:NO, PLEASE SEE SOME CIRCUITS |
| | ARE NOT COMEPLETE AT THIS TIME IN |
| | DWELLING UNITS AND HOUSE AREAS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. PLEASE SEE CIRCUTING |
| | MISSING. |
| | 215.5 |
| | |
| | 16)NOTE: OK. |
| | |
| | 17)NOTE: OK. |
| | |
| | |
| | 18)NOTE: ? NO, PLEASE SEE A NOTE WAS |
| | ADDED TO PLANS FOR "NO PLUG-IN TYPE " |
| | TRANSFORMERS TO BE PLACED IN CLOSETS |
| | ETC, HOWEVER PLEASE CLARIFY THE USE OF |
| | THE RECEPTS STILL BEING SHOWN IN THESE |
| | AREAS. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PELASE SEE RECEPTS FOR LV TYPE |
| | PLUG-IN TRANSFORMERS ARE NOT PERMITTED |
| | IN CLOTHES CLOSETS AND LOCATIONS IN |
| | CLOSE PROXIMITY OF EASILY IGNITIBLE |
| | MATERIALS. |
| | PLEASE SEE 110.26,240.24, ETC |
| | AS THESE TYPE UNITS CREATE HIGH TEMPS |
| | AND HAVE CAUSED FIRES IN THIS |
| | JURISDICTION, THESE WILL NOT BE |
| | PERMITTED IN THESE CLOSETS DUE TO THE |
| | LIFE SAFETY AND PROPERTY HAZARD IT |
| | CREATES. |
| | |
| | 19)NOTE: NO, PLEASE SEE LOWER COMM |
| | UNITS, PLEASE SEE UPPER UNITS CONTAIN LT |
| | FIXTURE WHICH ARE ALSO PART OF THE |
| | NORMAL LIGHTING. |
| | LOWER FLR DOES NOT MEET THE EXCEPTION. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 700.12EWHICH |
| | REQUIRESD THE BRANCH CIRCUIT FEEDING THE |
| | UNIT EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | PLEASE ADJUST CIRCUITING AS SHOWN. |
| | |
| | 20)NOTE: NO, PLEASE SEE A NOTE WAS ADDED |
| | TO PLANS IN LEIU OF THE DETAIL NEEDED |
| | AND REQUIRED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE THE PHOTO-METRICS FOR |
| | EXITING STAIR AREAS AS NFPA-101 7.8.1.3 |
| | REQUIES A MIN OF 10FT CANDLES (108 LUX) |
| | FOR THE ALL AREAS OF WALKING SURFACE IN |
| | STAIRS UNDER NORMAL POWER AND IS |
| | PERMITTED TO BE LOWERED TO A MIN OF 1FT |
| | CANDLE (10.8 LUX) UNDER EMERGENCY |
| | CONDITIONS, 7.9.2.2 |
| | |
| | 21)NOTE: NO, PLEASE SEE SOME FIXTURES |
| | ARE STILL SHOWN AS BLANK. ALL FIXTURES |
| | SHALL BE SHOWN AT THIS TIME. THESE CAN |
| | ALWAYS BE REVISED AT A LATER DATE. |
| | |
| | **IMPORTANT,PLEASE SEE NEW COMMENTS |
| | BEFORE FINAL FIXTURES ARE CHOSEN DUE TO |
| | THE ENERGY CODE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CORRELATE THE FIXTURE LEGEND |
| | WITH PLANS. |
| | PLEASE ALSO CORRELATE THE FIXTURE |
| | SCHEDULE WITH PLANS AS SOME FIXTURES ARE |
| | LABELED ON PLANS , YET NOT ON SCHEDULE. |
| | E-1). |
| | |
| | 22)NOTE: OK. |
| | |
| | 23)NOTE:NO, PLEASE SEE "EQUIPMENT |
| | GROUNDING CONDUCTORS" ARE STIL BEING |
| | SHOWN BEFORE THE FIRST MEANS OF |
| | DISCONNECT. PLEASE SEE NEW NOTESAS |
| | LOCATION WILL CHANGE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 250.6, 250.24, NO |
| | "EQUIPMENT GROUNDING CONDUCTORS" SHALL |
| | BE INSTALLED BEFORE THEFIRST MEANS OF DISCONNETC. |
| | PLEASE SEE THESE ARE SHOWN |
| | FROM FPL, TO GUTTER, TO METER ETC. |
| | |
| | 24)NOTE:OK. |
| | |
| | 25)NOTE: OK. |
| | |
| | 26)NOTE: NO, PLEASE SUBMIT COMPLETE |
| | CALCULATIONS FOR EACH PANEL FOR USE AS |
| | SHOWN ON PLANS. |
| | PLEASE ALSO SHOW LOADS FOR SERVICE, NONE |
| | WERE SUBMITTED. |
| | |
| | **PREVIOUS REVIEW NOTES ** |
| | PLEASE SUBMITLOAD CALCULATIONS FOR |
| | ALL AREAS, PANELS, BLDG. PLEASE SEE |
| | THESE ARE SHOWN A MIXED |
| | USE. PLEASE ADJSUT ACCORDINGLY. |
| | PLEASE ALSO INDICATE OF CONTINUOUS LOADS |
| | AT 125%. 215.3,230.42, |
| | 220.10,220.11,220.13 ETC |
| | |
| | 27)NOTE: NO, THIS WAS NOT ADDRESSED AND |
| | NO DESIGNS, CALCS, CONTROLS ETC WERE |
| | SUBMITTED FOR REVIEW. PLEASE SEE MIN |
| | CALCULATIONS REQUIRED. |
| | ALSO NO ENERGY CALCULATIONS WERE |
| | SUBMITTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE BE SURE TO SEE THE 2004 |
| | FBC CHAPTER 13 WITH RESPECT TO THE |
| | ENERGY CODE AND DESIGNS. PLEASE KNOW |
| | THIS IS A COMMERCIAL BLGD WITH A CHANGE |
| | OF OCCUPANCY WHICH WILL REQUIRE ENERGY |
| | CODE UPGRADES. |
| | |
| | **** NEW NOTES **** |
| | |
| | 28) NOTE: PLEASE SEE ORIGINAL PLANS WERE |
| | DONE BY A PE AND NOW PLANS ARE DONE BY |
| | ARCHITECT. PLEASE SEE THE SCOPE OF WORK, |
| | SIZE ETC REQUIRES THE PLANSTO BE DONE BY |
| | AN PE. FS 471.003(2)H. |
| | |
| | 29) NOTE: PLEASE SEE RISER WHICH |
| | INDICATES MORE THAN SEVEN MEANS OF |
| | DISCONNECT WHICH IS NOT PERMITTED. |
| | 230.2,230.70. |
| | PLEASE KNOW A SEPARATE TYPE OF METER |
| | BACNK SERVICE MAY BE DONE WITH A MAIN |
| | ETC. |
| | PLEASE ALSO SEE MANY OF THE TENANT |
| | METERS, MAINS ETC ARE LABLED AS "HOUSE" EQUIPEMNT?? |
| | PLEASE SEE PANEL "HP" SHOULD BE THE ONLY |
| | PANEL, METER AND MAIN LABLED AS "HOUSE". |
| | 408.4 |
| | 30) NOTE: PLEASE SEE CLOSET LT IN UNIT |
| | "C" WHICH DOES NOT MEET 410.8 |
| | |
| | 30) NOTE: PLEASE SEE SOME UNITS SHOW AND |
| | LABEL "TWO" EXHAUST FAN CIRCUITS?? |
| | PLEASE ALSO SEE ARC FAULT CIRCUITING. |
| | PLEASE SEE MANY OF THESE DO NOT |
| | CORRELATE WIHT CIRCUITING SHOWN ON PLANS |
| | AND DEVICES. SOME ARE NOT AS LABELED. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 31) NOTE: PLEASE SEE ELECTRICAL PANELS |
| | ARE NOW BEING SHOWN IN CLOSETS WHICH IS |
| | NOT PERMITTED. PLEASE ALSO SEE ALL MIN |
| | CLEARENCES ARE ALSO NOT MET. |
| | PLEASE SEE 110.26,240.24D,408.7 ETC. |
| | |
| | 32) NOTE: PLEASE SEE PLANS MENTIONS |
| | "SPRINKLER ROOM" ? WHAT IS THIS AND IS |
| | THERE LIGHTING FOR SERVICE OF EQUIPMENT |
| | ETC? |
| | LS 101 7.8 |
| | |
| | 33) NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)B) WITH RESPECT TO REPEAT |
| | COMMENTS FOR CODE COMPLIANCE AS MANY OF |
| | THESE COMMENTS ARE THE SAME AS THE |
| | PREVIOUS REVIEW. THIS IS ONLY BEING |
| | GIVEN AS A NOTICE AT THIS TIME. |
| | |
| | |
| | |
| | ** PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER REVIEWER(S) WHICH |
| | MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO REMOVED ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED |
| | SHEETS SEPARATED FROM NEW SETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2006-07-05 00:00:00 | IN ELEC FOR REVIEW |