Notes
Date Text
2006-07-06 00:00:00**
 ********* UNSAT2ND REVIEW ***********
  
 ** PLEASE SEE MANY ITEMS FROM PREVIOUS
 REVIEW AND SOME NEW ITEMS DUE TO
 INFORMATION SHOWN ON PLANS WHICH WAS
 DIFFERENT FROM PREVIOUS REVIEW.
  
 ** PLEASE KNOW, PLANS HAVE NOW BEEN
 SUBMITTED FOR PERMIT.
 PLEASE SEE THE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW WITH NEW
 NOTES ADDED TO THE END OF THE PREVIOUS
 NOTES.
  
 ** IMPORTANT**
 PLEASE SEE AS REQUESTED ON PREVIOUS
 REVIEW, PLEASE SUBMIT ONE SET OF THE
 OLD/VOIDED SETS FOR REFERENCE. THIS WAS
 NOT DONE.
  
 1)NOTE:NO, PLEASE SEE COVER SHEETS
 ONLY MENTIONS THE CODES AND NOT THE
 YEARS OF EDITIONS.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE THAT ALL DESIGNS AND
 CODES ARE REFERENCED TO THE CURRENT
 CODES ADOPTED BY THE STATE OF FLORIDA.
 PLEASE KNOW, WE ARE CURRENTLY UNDER THE
 2004 FLORIDA BLDG CODE.
 2002 NFPA-70, 2002 NFPA-72,2003 NFPA-101
 PLEASE ADJUST.
 PLEASE ALSO SEE NOTES BELOW AS
 ELECTRICAL CODE IS BEING REFERENCED FROM
 THE 1996
 NFPA-70 (NEC).
  
 2)NOTE: OK, AS TITLE BLOCKS HAVE BEEN
 REVISED AND ENGINEERING FIRM AND
 ENGINEER IS NO LONGER DOING THE PROJECT.
 HOWEVER PLEASE SEE NEW NOTES.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING INFORMATION
 AND LICENSE INFORMATION REQUIRED ON
 TITLE BLOCKS FOR THE ARCHITECTUAL FIRM,
 ENGINEER AND FIRM? ETC.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002,
 61G1-16.004 AND FLORIDA
 STATUES, 481.219, 471.023 .
 PLEASE KNOW: THIS IS REQUIRED OF ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 3)NOTE: NO, PLEASE SEE IT SEEMS THE
 ENGINEER AS SHOWN ON PREVIOUS PLANS HAS
 BEEN REMOVED AND THE PLANS ARE NOW DONE
 BY AN ARCHITECT. PLEASE SEE NEW COMMENTS PERTAINING TO
 THE PLANS AND PLEASE SEE
 THAT THE PREVIOUS NOTE STILL APPLIES TO
 THE ARCGITECT OF RECORD. PLEASE SEE
 PLANS ARE CLEARLY "SIGNED" WITH
 "INITIALS". IF THIS IS THE "LEGAL
 SIGNATURE" OF SAID ARCHITECT, PLEASE
 PROVIDE A SIGNED,DATED AND SEALED
 NOTORIZED LETTER FOR LEGAL SIGNATURE
 VERIFICATION. THIS WILL BE PLACED IN OUR
 SIGNATURE FILE FOR FUTURE REFERENCE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE ALSO PROVIDE A SIGNED, DATED AND
 SEALED LETTER FOR THE ENGINEER AS SHOWN
 ON PLANS AFFIRMING THE LEGAL SIGNATURE
 ON SAID PLANS. PLANS APEAR TO INDICATE INITIAL(S)? THIS
 LETTER IS TO BE CORRECTLY
 NOTORIZED, AND WILL BE PLACED IN OUR
 SIGNATURE FILE FOR FUTUREREFERENCE.
  
 4)NOTE: NO, PLEASE SEE LOWER POWER PLANS
 INDICATE ROOF TOP GFI'S AND THE TWO ARE
 FED FROM FIRST FLR TENANT PANELS. THESE
 SHOULD BE FED FROM HOUSE PANEL.
  
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE ROOF TOP
 RECEPTS AS GFI OR GFI PROTECTED AS
 REQUIRED PER 210.8B2
  
 5)NOTE: NO, PLEASE SEE COMMON AREA
 ELECTRICAL STILL BEING SHOWN CIRCUITED
 TO ONE OF THE RESIDENTTIAL UNITS.
 THIS IS NOT PERMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NO COMMON AREAS SHALL
 BE FED FROM CIRCUIT DERVIED FROM APTS OR
 OFFICE UNITS. PLEASE SEE CIRCUITING OF
 HALL RECEPTS ARE SHOWN TO ONE UNIT.
 PLEASE SEE 210.25
  
 6)NOTE:NO, PLEASE SEE CODE CHANGED IN
 1993 TO REQUIRED "ALL" NOT ONLY RECEPTS
 LOCATED WITHIN 6' OF SINK.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SHOW ALL KITCHEN
 COUNTERSPACE RECEPTS AS GFI/ GFI
 PROTECTED AS REQUIRED PER 210.8A6
  
 7)NOTE: NO, SAME NOTE: PLEASE SEE
 KITCHENS IN OTHER THAN DWELLING UNITS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE IF OFFICE UNITS WHICH
 WILL ALSO BE REQUIRED TO HAVE GFI
 RECEPTS,IN EITHER CASE ON POSSIBLE USE
 CHANGE TO DWELLING UNITS, OR AS REQUIRED
 PER 210.8B3
  
 8)NOTE: NO, STIL SHOWS ONLY ONE.
  
 **PREVIOUS REVIEW NOTE ** PLEASE SEE A
 MIN OF TWO SMALL
 APPLIANCE CIRCUITS ARE REQUIED PER
 210.52B1.
  
 9)NOTE: OK.
  
 10)NOTE: OK.
  
 11)NOTE: OK.
  
 12)NOTE: OK.
  
 13)NOTE: NO, PLEASE SEE THERE ARE
 CIRCUITS NOW SHOWN WITH ARC FAULT
 PROTECTION WHICH ARE NOT REQUIRED AND
 SOME WHICH DO SHOW ARC FAULT PROTECTION
 AND SOME THAT DO NOT??
 PLEASE SEE ALL "OUTLETS".
  
 ** PREVIOUS REVIEW NOTES **
 PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS AS REQUIRD
 UNDER THE 2002 NEC 210.12B
 PLEASE KNOW, ALL, ELECTRICAL
 DEVICES/OUTLETS SUCH AS LTS, SD'S
 RECEPTS, FANS ETC SHALL BE AFCI
 PROTECTED.
 ** PLEASE KNOW, AREAS NOW SHOWN AS
 "OFFICES" ARE UNITS WHICH SEEM TO SHOW
 POSSIBLE CHANGE IN-USE OR OCCUPANCY. IF
 THESE AREAS ARE ADAPTABLE FOR
 RESIDENTIAL USE, THEN AFCI PROTECTION
 WILL BE REQUIRED FOR THESE ROOMS.
  
 14)NOTE: OK, HOWEVER 2ND PART OF THIS
 NOTE WAS NOT DONE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-70 11.5.1.1
 WHICH REQUIRES THE USE OF SMOKE
 DETECTORS INSIDE AND OUTSIDE ALL
 SLEEPING RMS OR ADAPTABLE SLEEPING
 ROOMS.** PLEASE SEE PREVIOUS NOTES WITH
 RESPECT TO THE CIRCUITING OF BEDRMS.
  
 15)NOTE:NO, PLEASE SEE SOME CIRCUITS
 ARE NOT COMEPLETE AT THIS TIME IN
 DWELLING UNITS AND HOUSE AREAS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE. PLEASE SEE CIRCUTING
 MISSING.
 215.5
  
 16)NOTE: OK.
  
 17)NOTE: OK.
  
  
 18)NOTE: ? NO, PLEASE SEE A NOTE WAS
 ADDED TO PLANS FOR "NO PLUG-IN TYPE "
 TRANSFORMERS TO BE PLACED IN CLOSETS
 ETC, HOWEVER PLEASE CLARIFY THE USE OF
 THE RECEPTS STILL BEING SHOWN IN THESE
 AREAS.
  
 ** PREVIOUS REVIEW NOTE**
 PELASE SEE RECEPTS FOR LV TYPE
 PLUG-IN TRANSFORMERS ARE NOT PERMITTED
 IN CLOTHES CLOSETS AND LOCATIONS IN
 CLOSE PROXIMITY OF EASILY IGNITIBLE
 MATERIALS.
 PLEASE SEE 110.26,240.24, ETC
 AS THESE TYPE UNITS CREATE HIGH TEMPS
 AND HAVE CAUSED FIRES IN THIS
 JURISDICTION, THESE WILL NOT BE
 PERMITTED IN THESE CLOSETS DUE TO THE
 LIFE SAFETY AND PROPERTY HAZARD IT
 CREATES.
  
 19)NOTE: NO, PLEASE SEE LOWER COMM
 UNITS, PLEASE SEE UPPER UNITS CONTAIN LT
 FIXTURE WHICH ARE ALSO PART OF THE
 NORMAL LIGHTING.
 LOWER FLR DOES NOT MEET THE EXCEPTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 700.12EWHICH
 REQUIRESD THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE ADJUST CIRCUITING AS SHOWN.
  
 20)NOTE: NO, PLEASE SEE A NOTE WAS ADDED
 TO PLANS IN LEIU OF THE DETAIL NEEDED
 AND REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE THE PHOTO-METRICS FOR
 EXITING STAIR AREAS AS NFPA-101 7.8.1.3
 REQUIES A MIN OF 10FT CANDLES (108 LUX)
 FOR THE ALL AREAS OF WALKING SURFACE IN
 STAIRS UNDER NORMAL POWER AND IS
 PERMITTED TO BE LOWERED TO A MIN OF 1FT
 CANDLE (10.8 LUX) UNDER EMERGENCY
 CONDITIONS, 7.9.2.2
  
 21)NOTE: NO, PLEASE SEE SOME FIXTURES
 ARE STILL SHOWN AS BLANK. ALL FIXTURES
 SHALL BE SHOWN AT THIS TIME. THESE CAN
 ALWAYS BE REVISED AT A LATER DATE.
  
 **IMPORTANT,PLEASE SEE NEW COMMENTS
 BEFORE FINAL FIXTURES ARE CHOSEN DUE TO
 THE ENERGY CODE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE THE FIXTURE LEGEND
 WITH PLANS.
 PLEASE ALSO CORRELATE THE FIXTURE
 SCHEDULE WITH PLANS AS SOME FIXTURES ARE
 LABELED ON PLANS , YET NOT ON SCHEDULE.
 E-1).
  
 22)NOTE: OK.
  
 23)NOTE:NO, PLEASE SEE "EQUIPMENT
 GROUNDING CONDUCTORS" ARE STIL BEING
 SHOWN BEFORE THE FIRST MEANS OF
 DISCONNECT. PLEASE SEE NEW NOTESAS
 LOCATION WILL CHANGE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 250.6, 250.24, NO
 "EQUIPMENT GROUNDING CONDUCTORS" SHALL
 BE INSTALLED BEFORE THEFIRST MEANS OF DISCONNETC.
 PLEASE SEE THESE ARE SHOWN
 FROM FPL, TO GUTTER, TO METER ETC.
  
 24)NOTE:OK.
  
 25)NOTE: OK.
  
 26)NOTE: NO, PLEASE SUBMIT COMPLETE
 CALCULATIONS FOR EACH PANEL FOR USE AS
 SHOWN ON PLANS.
 PLEASE ALSO SHOW LOADS FOR SERVICE, NONE
 WERE SUBMITTED.
  
 **PREVIOUS REVIEW NOTES **
 PLEASE SUBMITLOAD CALCULATIONS FOR
 ALL AREAS, PANELS, BLDG. PLEASE SEE
 THESE ARE SHOWN A MIXED
 USE. PLEASE ADJSUT ACCORDINGLY.
 PLEASE ALSO INDICATE OF CONTINUOUS LOADS
 AT 125%. 215.3,230.42,
 220.10,220.11,220.13 ETC
  
 27)NOTE: NO, THIS WAS NOT ADDRESSED AND
 NO DESIGNS, CALCS, CONTROLS ETC WERE
 SUBMITTED FOR REVIEW. PLEASE SEE MIN
 CALCULATIONS REQUIRED.
 ALSO NO ENERGY CALCULATIONS WERE
 SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TO SEE THE 2004
 FBC CHAPTER 13 WITH RESPECT TO THE
 ENERGY CODE AND DESIGNS. PLEASE KNOW
 THIS IS A COMMERCIAL BLGD WITH A CHANGE
 OF OCCUPANCY WHICH WILL REQUIRE ENERGY
 CODE UPGRADES.
  
 **** NEW NOTES ****
  
 28) NOTE: PLEASE SEE ORIGINAL PLANS WERE
 DONE BY A PE AND NOW PLANS ARE DONE BY
 ARCHITECT. PLEASE SEE THE SCOPE OF WORK,
 SIZE ETC REQUIRES THE PLANSTO BE DONE BY
 AN PE. FS 471.003(2)H.
  
 29) NOTE: PLEASE SEE RISER WHICH
 INDICATES MORE THAN SEVEN MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED.
 230.2,230.70.
 PLEASE KNOW A SEPARATE TYPE OF METER
 BACNK SERVICE MAY BE DONE WITH A MAIN
 ETC.
 PLEASE ALSO SEE MANY OF THE TENANT
 METERS, MAINS ETC ARE LABLED AS "HOUSE" EQUIPEMNT??
 PLEASE SEE PANEL "HP" SHOULD BE THE ONLY
 PANEL, METER AND MAIN LABLED AS "HOUSE".
 408.4
 30) NOTE: PLEASE SEE CLOSET LT IN UNIT
 "C" WHICH DOES NOT MEET 410.8
  
 30) NOTE: PLEASE SEE SOME UNITS SHOW AND
 LABEL "TWO" EXHAUST FAN CIRCUITS??
 PLEASE ALSO SEE ARC FAULT CIRCUITING.
 PLEASE SEE MANY OF THESE DO NOT
 CORRELATE WIHT CIRCUITING SHOWN ON PLANS
 AND DEVICES. SOME ARE NOT AS LABELED.
 FBC 106.1.2 ADMIN SECT.
  
 31) NOTE: PLEASE SEE ELECTRICAL PANELS
 ARE NOW BEING SHOWN IN CLOSETS WHICH IS
 NOT PERMITTED. PLEASE ALSO SEE ALL MIN
 CLEARENCES ARE ALSO NOT MET.
 PLEASE SEE 110.26,240.24D,408.7 ETC.
  
 32) NOTE: PLEASE SEE PLANS MENTIONS
 "SPRINKLER ROOM" ? WHAT IS THIS AND IS
 THERE LIGHTING FOR SERVICE OF EQUIPMENT
 ETC?
 LS 101 7.8
  
 33) NOTE: PLEASE SEE COPY OF FS
 553.80(2)B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE AS MANY OF
 THESE COMMENTS ARE THE SAME AS THE
 PREVIOUS REVIEW. THIS IS ONLY BEING
 GIVEN AS A NOTICE AT THIS TIME.
  
  
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVED ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED
 SHEETS SEPARATED FROM NEW SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]