Plan Review Notes
Plan Review Notes For Permit 05121124
Permit Number 05121124
Review Stop P
Sequence Number 2
Notes
Date Text
2006-08-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1. OK
 2. ENGINEER TAKEN OFF PLANS.
 3. ENGINEER TAKEN OFF PLANS.
  
 4. SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES PER TABLES 1004.1.2 AND
 403.1. SHOW THE SQUARE FOOTAGE OF EACH
 TYPE OF OCCUPANCY FOR MERCANTILE, AND
 BUSINESS. DRINKING FOUNTAINS ARE
 REQUIRED FOR BUSINESS AND MERCANTILE
 OCCUPANCIES. TABLE 403.1.
 ****RESPONSE NOTED ON SHT P-3 INDICATES
 1 SERVICE SINK REQUIRED IN THE
 MERCANTILE AND BUSINESS OCCUPANCIES.
 THIS IS NOT REQUIRED AND SINKS ARE NOT
 SHOWN. CALCULATION TO REFLECT THE FLOOR
 PLAN. - DRINKING FOUNTAINS ARE INDICATED
 AND REQUIRED IN THE BUSINESS OCCUPANCIES
 BUT ARE NOT PROVIDED. SHOW DRINKING
 FOUNTAINS IN THE BUSINESS OCCUPANCIES. -
 WASH MACHINES ARE REQUIRED IN THE
 RESIDENTIAL OCCUPANCIES.
  
 5. SHT A1.1 KITCHEN SINKS IN ROOMS 218 &
 220 SHALL BE ACCESSIBLE. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS.
 ****COMMENT NOT ADDRESSED. NO RESPONSE.
  
 6. SHT A1.2 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 THE SQUARE FOOTAGE OF THE ROOF. INDICATE
 THE SQUARE FOOTAGE DRAINED BY EACH
 PRIMARY ROOF DRAIN. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED
 TO THE CALCULATIONS. SHOW THE LOCATION
 OF ALL SECONDARY DRAINS/OVERFLOW
 SCUPPERS. SUBMIT A DETAIL FOR THE
 CONDUCTOR HEAD SHOWING THE SIZE, HEIGHT
 & WIDTH, AS WELL AS THE DOWNSPOUT
 INDICATING SIZE. SECTIONS 1106 & 1107
 WITH ALL SUBSECTIONS.
 ****COMMENT NOT ADDRESSED, NO RESPONSE.
  
 7. THE TOILET ROOMS IN THE BUSINESS AND
 MERCANTILE OCCUPANCIES SHALL BE
 ACCESSIBLE. PLEASE SHOW THE FOLLOWING:
 FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.4 GRAB BARS
 C. 11-4.16.5 FLUSH CONTROLS
 D. 11-4.16.6 DISPENSERS
 FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 (CLEARANCES NOT SHOWN)
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
 FOR SHOWERS:
 A. 11-4.21.2 SIZE AND CLEARANCES
 B. 11-4.21.3 SEAT
 C. 11-4.21.4 GRAB BARS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.6 SHOWER UNIT
 F. 11-4.21.7 CURBS
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 8. SHT P-4 SANITARY RISER DIAGRAM SHALL
 BE SUBMITTED IN AN ISOMETRIC FORM, AND
 SHALL REFLECT THE PIPING AND FIXTURE
 LAYOUT ON SHEETS P-3 & P-4. SHOW ALL
 PIPE SIZES. THE KITCHEN SINKS AND WASH
 MACHINES SHALL NOT DRAIN THROUGH THE
 HORIZONTAL WET VENTS OF THE BATHROOM
 GROUPS. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE
 WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. SECTIONS
 106.3.5.1.3 & 909.1.
 ****RESPONSE NOTED, BUT SANT. RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLANS
 OF SHEETS P-3 OR P-4. - WASH MACHINE
 DRAINS REQUIRE A STANDPIPE. SECTIONS
 802.4 - RISER SHOWS A 4" STACK"DOWN TO
 BELOW SLAB, BUT NOT CONNECTED TO THE
 BUILDING DRAIN.
  
 9. SUBMIT A WATER RISER DIAGRAM
 ISOMETRIC SHOWING ALL PIPE SIZES,
 VALVES, AND WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9. ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE", (NOT IN THE CEILING).
 SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9,
 (W/M, D/W, AND ICE MAKER IN REF.), SHALL
 BE SHOWN ON THE RISER. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURE IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING. - A FULL OPEN VALVE IS
 REQUIRED AT THE TOP OF EVERY WATER DOWN
 - FEED PIPE. SECTION 606.1(4).
  
 10. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. IF
 EXISTING INDICATE ON THE WATER RISER
 DIAGRAM. SECTION 608.13.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 11. SUBMIT A WATER HEATER DETAIL SHOWING
 THERMAL EXPANSION CONTROL, ALL REQUIRED
 VALVES, PIPING FOR T/P VALVE DISCHARGE
 AND EMERGENCY PAN DRAIN INDICATING
 PIPING MATERIAL AND TERMINATION POINT
 FOR T/P & PAN DRAIN. SECTION 106.1.1.
 12.FLOOR DRAINS ARE NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. IF DRAINING T/P
 AND PAN DRAIN IN HEATER ROOM, A FLOOR
 SINK OR HUB DRAIN WILL BE REQUIRED.
 SECTIONS 802.3 AND 802.3.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NOT ADDRESSED
  
 **************NEW COMMENTS**************
  
 1B. FOR ACCESSIBLE FIXTURES: DOORS SHALL
 NOT SWING INTO THE CLEAR FLOOR SPACE
 REQUIRED FOR ANY FIXTURE. (SHOW ALL
 CLEAR FLOOR SPACES FOR LAVS, W/C'S,
 SHOWERS, KITCHEN SINKS ETC.). SECTION
 11-4.22.2
  
 2B. PEDISTAL LAVS ARE NOT APPROVED FOR
 ACCESSIBLE TOILET AND BATH ROOMS. SEE
 FIG 11-31 FOR REQUIRED CLEARANCES.
  
 3B. SHT A7.1 FINISH SCHEDULE DOES NOT
 INDICATE FLOOR FINISH FOR BATHROOMS 217
 OR 221. INDICATE FLOOR AND BASE FINISH
 TO COMPLY WITH SECTION 1210.1 (BLDG).
  
 4B. SHT A8.2 FINISH SCHEDULE DOES NOT
 REFLECT FINISH SCHEDULE ON SHT A7.1.
 PLEASE CORRELATE SCHEDULES. - WALL
 FINISH, (LATEX PAINT), DOES NOT MEET THE REQUIREMENT TO
 BE NONABSORBENT PER
 SECTION 1210.2.
  
 5B. SHT P-1 PLUMBING NOTES #1. FBC-2004
 NOT VIRGINA CODE COMPLIANCE REQUIRED.
 CHANGE REFERENCE.
  
 REVIEW BY KEN STEVENS