| Date |
Text |
| 2006-08-05 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | |
| | 1. OK |
| | 2. ENGINEER TAKEN OFF PLANS. |
| | 3. ENGINEER TAKEN OFF PLANS. |
| | |
| | 4. SUBMIT CALCULATIONS FOR MINIMUM |
| | FACILITIES PER TABLES 1004.1.2 AND |
| | 403.1. SHOW THE SQUARE FOOTAGE OF EACH |
| | TYPE OF OCCUPANCY FOR MERCANTILE, AND |
| | BUSINESS. DRINKING FOUNTAINS ARE |
| | REQUIRED FOR BUSINESS AND MERCANTILE |
| | OCCUPANCIES. TABLE 403.1. |
| | ****RESPONSE NOTED ON SHT P-3 INDICATES |
| | 1 SERVICE SINK REQUIRED IN THE |
| | MERCANTILE AND BUSINESS OCCUPANCIES. |
| | THIS IS NOT REQUIRED AND SINKS ARE NOT |
| | SHOWN. CALCULATION TO REFLECT THE FLOOR |
| | PLAN. - DRINKING FOUNTAINS ARE INDICATED |
| | AND REQUIRED IN THE BUSINESS OCCUPANCIES |
| | BUT ARE NOT PROVIDED. SHOW DRINKING |
| | FOUNTAINS IN THE BUSINESS OCCUPANCIES. - |
| | WASH MACHINES ARE REQUIRED IN THE |
| | RESIDENTIAL OCCUPANCIES. |
| | |
| | 5. SHT A1.1 KITCHEN SINKS IN ROOMS 218 & |
| | 220 SHALL BE ACCESSIBLE. SUBMIT A DETAIL |
| | SHOWING COMPLIANCE WITH SECTION 11-4.24 |
| | AND ALL SUBSECTIONS. |
| | ****COMMENT NOT ADDRESSED. NO RESPONSE. |
| | |
| | 6. SHT A1.2 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| | THE SQUARE FOOTAGE OF THE ROOF. INDICATE |
| | THE SQUARE FOOTAGE DRAINED BY EACH |
| | PRIMARY ROOF DRAIN. SHOW 1/2 AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS ADDED |
| | TO THE CALCULATIONS. SHOW THE LOCATION |
| | OF ALL SECONDARY DRAINS/OVERFLOW |
| | SCUPPERS. SUBMIT A DETAIL FOR THE |
| | CONDUCTOR HEAD SHOWING THE SIZE, HEIGHT |
| | & WIDTH, AS WELL AS THE DOWNSPOUT |
| | INDICATING SIZE. SECTIONS 1106 & 1107 |
| | WITH ALL SUBSECTIONS. |
| | ****COMMENT NOT ADDRESSED, NO RESPONSE. |
| | |
| | 7. THE TOILET ROOMS IN THE BUSINESS AND |
| | MERCANTILE OCCUPANCIES SHALL BE |
| | ACCESSIBLE. PLEASE SHOW THE FOLLOWING: |
| | FOR W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.4 GRAB BARS |
| | C. 11-4.16.5 FLUSH CONTROLS |
| | D. 11-4.16.6 DISPENSERS |
| | FOR LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | (CLEARANCES NOT SHOWN) |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | D. 11-4.19.5 FAUCETS |
| | E. 11-4.19.6 MIRRORS |
| | FOR SHOWERS: |
| | A. 11-4.21.2 SIZE AND CLEARANCES |
| | B. 11-4.21.3 SEAT |
| | C. 11-4.21.4 GRAB BARS |
| | D. 11-4.21.5 CONTROLS |
| | E. 11-4.21.6 SHOWER UNIT |
| | F. 11-4.21.7 CURBS |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 8. SHT P-4 SANITARY RISER DIAGRAM SHALL |
| | BE SUBMITTED IN AN ISOMETRIC FORM, AND |
| | SHALL REFLECT THE PIPING AND FIXTURE |
| | LAYOUT ON SHEETS P-3 & P-4. SHOW ALL |
| | PIPE SIZES. THE KITCHEN SINKS AND WASH |
| | MACHINES SHALL NOT DRAIN THROUGH THE |
| | HORIZONTAL WET VENTS OF THE BATHROOM |
| | GROUPS. ONLY THE FIXTURES WITHIN THE |
| | BATHROOM GROUPS SHALL CONNECT TO THE |
| | WET-VENTED HORIZONTAL BRANCH DRAIN. ANY |
| | ADDITIONAL FIXTURES SHALL DISCHARGE |
| | DOWNSTREAM OF THE WET VENT. SECTIONS |
| | 106.3.5.1.3 & 909.1. |
| | ****RESPONSE NOTED, BUT SANT. RISER |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLANS |
| | OF SHEETS P-3 OR P-4. - WASH MACHINE |
| | DRAINS REQUIRE A STANDPIPE. SECTIONS |
| | 802.4 - RISER SHOWS A 4" STACK"DOWN TO |
| | BELOW SLAB, BUT NOT CONNECTED TO THE |
| | BUILDING DRAIN. |
| | |
| | 9. SUBMIT A WATER RISER DIAGRAM |
| | ISOMETRIC SHOWING ALL PIPE SIZES, |
| | VALVES, AND WATER HAMMER ARRESTORS |
| | REQUIRED BY SECTION 604.9. ARRESTORS |
| | SHALL BE LOCATED NEAR THE FIXTURE IN AN |
| | "EFFECTIVE RANGE", (NOT IN THE CEILING). |
| | SECTION 106.3.5.1.3. |
| | ****RESPONSE NOTED, BUT WATER HAMMER |
| | ARRESTORS REQUIRED BY SECTION 604.9, |
| | (W/M, D/W, AND ICE MAKER IN REF.), SHALL |
| | BE SHOWN ON THE RISER. WATER HAMMER |
| | ARRESTORS SHALL BE LOCATED NEAR THE |
| | FIXTURE IN AN "EFFECTIVE RANGE" NOT IN |
| | THE CEILING. - A FULL OPEN VALVE IS |
| | REQUIRED AT THE TOP OF EVERY WATER DOWN |
| | - FEED PIPE. SECTION 606.1(4). |
| | |
| | 10. AN RPZV BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE TO THE BUILDING. IF |
| | EXISTING INDICATE ON THE WATER RISER |
| | DIAGRAM. SECTION 608.13.2. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 11. SUBMIT A WATER HEATER DETAIL SHOWING |
| | THERMAL EXPANSION CONTROL, ALL REQUIRED |
| | VALVES, PIPING FOR T/P VALVE DISCHARGE |
| | AND EMERGENCY PAN DRAIN INDICATING |
| | PIPING MATERIAL AND TERMINATION POINT |
| | FOR T/P & PAN DRAIN. SECTION 106.1.1. |
| | 12.FLOOR DRAINS ARE NOT AN APPROVED |
| | INDIRECT WASTE RECEPTOR. IF DRAINING T/P |
| | AND PAN DRAIN IN HEATER ROOM, A FLOOR |
| | SINK OR HUB DRAIN WILL BE REQUIRED. |
| | SECTIONS 802.3 AND 802.3.2. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | ****NOT ADDRESSED |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. FOR ACCESSIBLE FIXTURES: DOORS SHALL |
| | NOT SWING INTO THE CLEAR FLOOR SPACE |
| | REQUIRED FOR ANY FIXTURE. (SHOW ALL |
| | CLEAR FLOOR SPACES FOR LAVS, W/C'S, |
| | SHOWERS, KITCHEN SINKS ETC.). SECTION |
| | 11-4.22.2 |
| | |
| | 2B. PEDISTAL LAVS ARE NOT APPROVED FOR |
| | ACCESSIBLE TOILET AND BATH ROOMS. SEE |
| | FIG 11-31 FOR REQUIRED CLEARANCES. |
| | |
| | 3B. SHT A7.1 FINISH SCHEDULE DOES NOT |
| | INDICATE FLOOR FINISH FOR BATHROOMS 217 |
| | OR 221. INDICATE FLOOR AND BASE FINISH |
| | TO COMPLY WITH SECTION 1210.1 (BLDG). |
| | |
| | 4B. SHT A8.2 FINISH SCHEDULE DOES NOT |
| | REFLECT FINISH SCHEDULE ON SHT A7.1. |
| | PLEASE CORRELATE SCHEDULES. - WALL |
| | FINISH, (LATEX PAINT), DOES NOT MEET THE REQUIREMENT TO |
| | BE NONABSORBENT PER |
| | SECTION 1210.2. |
| | |
| | 5B. SHT P-1 PLUMBING NOTES #1. FBC-2004 |
| | NOT VIRGINA CODE COMPLIANCE REQUIRED. |
| | CHANGE REFERENCE. |
| | |
| | REVIEW BY KEN STEVENS |