Plan Review Notes
Plan Review Notes For Permit 05121124
Permit Number 05121124
Review Stop M
Sequence Number 2
Notes
Date Text
2006-08-14 00:00:00DENIED:
 ORIGINAL REVIEW BY RON REGUEIRO DATED
 2/7/06.THE FOLLOWING COMMENTS NEED
 FURTHER CLARIFICATION:
  
 COMMENT 1:DUCT SMOKE DETECTOR SHALL BE
 INSTALLED IN THE SUPPLY AIR DUCT PER
 2004 FMC 606.2.1.PLAN SHEET M-1 THE
 HVAC UNIT SCHEDULE NOTE 6 STILL
 INDICATES THE SMOKE DETECTOR IN THE
 RETURN AIR DUCT.PLEASE REVISE.
  
 COMMENT 2:OK
 COMMENT 3:OK
  
 COMMENT 4:PLAN SHEET M-3 THE GROUND
 FLOOR PLAN INDICATES THE SUPPLY, RETURN
 AND EF-2 DUCTS PENETRATING THE FLOOR
 CEILING ASSEMBLY.PLAN SHEET A7.1 &
 A9.0 INDICATE DUCTS IN A 1HR SHAFT
 ENCLOSURE AND SHALL COMPLY WITH 2004 FMC
 607.5.5.1 OR SHOW COMPLIANCE WITH
 2004 FMC 607.6.1, WHERE DUCTS PENETRATE
 A FIRE-RESISTANCE-RATED FLOOR/CEILING
 THAT CONNECTS MORE THAN 2 STORIES, A
 SHAFT ENCLOSURE IS NOT REQUIRED PROVIDED
 A FIRE DAMPER IS INSTALLED AT THE FLOOR
 PENETRATION.
  
 COMMENT 5:SEE ELECTRICAL COMMENTS.
  
 COMMENT 6:OK
 COMMENT 7:OK
 COMMENT 8:OK
 ***************NEW COMMENTS*************
 COMMENT 9:R/A REQUIRED FROM BEDROOM
 AREA (ROOM #213). SHOW COMPLIANCE WITH
 2004 FMC 601.4.
  
 COMMENT 10: PLEASE CLARIFY SUPPLY,
 RETURN, & EF-1 DUCTS PENETRATING
 FLOOR/CEILING ASSEMBLY.PLAN SHEET A7.1
 & A9.0 INDICATE DUCTS IN 1HR SHAFT.
 FIRE DAMPERS REQUIRED WHERE DUCTS
 PENETRATE THE SHAFT ENCLOSURE (2004 FMC
 607.5.5.1. OR SHOW COMPLIANCE WITH 2004
 FMC 601.4. (SEE COMMENT 4)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].
  