| 2006-08-09 00:00:00 | ******DENIED****** |
| | |
| | PLEASE SEE LAST REVIEW COMMENTS THAT |
| | DON'T APPEAR TO HAVE BEEN ADDRESSED. |
| | PLEASE SEE SOME ADDITIONAL COMMENTS. |
| | |
| | 1) IN ADDITION TO APPLICABLE BUILDING |
| | CODES, NFPA 101, 2003 EDITION SHALL BE |
| | REFERENCED. THE APPLICABLE EDITION IS |
| | NOT INDICATED ON THE PLANS. |
| | |
| | 2) MEANS OF EGRESS ILLUSTRATES BUSINESS |
| | ONLY, HOWEVER BUILDING MEETS |
| | REQUIREMENTS FOR MULTIPLE OCCUPANCY. |
| | |
| | 3) WORK TO COMPLY WITH NFPA 101, SEC. |
| | 6.1.14 MULTIPLE OCCUPANCIES AND ALL |
| | OTHER APPLICABLE CODES. |
| | |
| | 4) PLANS SHOW BUILDING TO BE FULLY FIRE |
| | SPRINKLERED BUT NOT MONITORED. FIRE |
| | SPRINKLER SYSTEM SHALL BE UL CERTIFIED |
| | FOR CENTRAL STATION SERVICE. FIRE |
| | SPRINKLER SYSTEMS SHALL BE SUPERVISED. |
| | |
| | 5) SEPARATE SHOP DRAWINGS AND PERMITS |
| | REQUIRED FOR FIRE SPRINKLER/FIRE ALARM |
| | SYSTEMS. |
| | |
| | 6) CONSTRUCTION, ALTERATION AND |
| | DEMOLITION TO COMPLY WITH NFPA 241. |
| | |
| | 7) 2A-10B,C RATED FIRE EXTINGUISHERS ARE |
| | REQUIRED. LOCATIONS TO BE SHOWN ON |
| | DRAWINGS. |
| | |
| | 8) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENT FOR HANDRAILS AND GUARDS. |
| | |
| | 9) ONE STAIRWELL ON SHT A1.1 APPEARS TO |
| | BE OPEN TO THE COMMON AREA. ARE |
| | STAIRWELLS RATED ENCLOSURES? |
| | |
| | 10) SHT A1.0 INDICATES THAT STAIRWELLS |
| | ARE 2 HR RATED. THAT BEING THE CASE, ALL |
| | ASSOCIATED DOORS SHALL HAVE 1 1/2 HR |
| | RATING. |
| | |
| | 11 OK |
| | |
| | 12) PLEASE SHOW LOCATIONS OF REQUIRED |
| | HARDWIRED SMOKE DETECTORS THAT SHALL BE |
| | A MINIMUM OF 3' FROM HVAC DIFFUSERS. |
| | |
| | 13) PLEASE SHOW SMOKE DETECTOR ON LEGEND |
| | TO CLARIFY WHAT IS SHOWN ON DRAWINGS. |
| | |
| | 14) SMOKE DETECTORS SHALL OPERATE SO |
| | THAT ACTIVATION OF ONE WILL OPERATE ALL |
| | DETECTORS WITHIN DWELLING UNIT, SUITE OF |
| | ROOMS OR SIMILAR AREA. NFPA SEC. |
| | 9.6.2.10.3. |
| | |
| | 15) PLANS INDICATE A FIRE SPRINKLER |
| | SYSTEM. A LAYOUT OF THE SYSTEM IS |
| | REQUIRED PRIOR TO SEPARATE SUBMITAL. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLANS REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |