Date Text
2006-08-09 00:00:00******DENIED******
  
 PLEASE SEE LAST REVIEW COMMENTS THAT
 DON'T APPEAR TO HAVE BEEN ADDRESSED.
 PLEASE SEE SOME ADDITIONAL COMMENTS.
  
 1) IN ADDITION TO APPLICABLE BUILDING
 CODES, NFPA 101, 2003 EDITION SHALL BE
 REFERENCED. THE APPLICABLE EDITION IS
 NOT INDICATED ON THE PLANS.
  
 2) MEANS OF EGRESS ILLUSTRATES BUSINESS
 ONLY, HOWEVER BUILDING MEETS
 REQUIREMENTS FOR MULTIPLE OCCUPANCY.
  
 3) WORK TO COMPLY WITH NFPA 101, SEC.
 6.1.14 MULTIPLE OCCUPANCIES AND ALL
 OTHER APPLICABLE CODES.
  
 4) PLANS SHOW BUILDING TO BE FULLY FIRE
 SPRINKLERED BUT NOT MONITORED. FIRE
 SPRINKLER SYSTEM SHALL BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE. FIRE
 SPRINKLER SYSTEMS SHALL BE SUPERVISED.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER/FIRE ALARM
 SYSTEMS.
  
 6) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 7) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED. LOCATIONS TO BE SHOWN ON
 DRAWINGS.
  
 8) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
 9) ONE STAIRWELL ON SHT A1.1 APPEARS TO
 BE OPEN TO THE COMMON AREA. ARE
 STAIRWELLS RATED ENCLOSURES?
  
 10) SHT A1.0 INDICATES THAT STAIRWELLS
 ARE 2 HR RATED. THAT BEING THE CASE, ALL
 ASSOCIATED DOORS SHALL HAVE 1 1/2 HR
 RATING.
  
 11 OK
  
 12) PLEASE SHOW LOCATIONS OF REQUIRED
 HARDWIRED SMOKE DETECTORS THAT SHALL BE
 A MINIMUM OF 3' FROM HVAC DIFFUSERS.
  
 13) PLEASE SHOW SMOKE DETECTOR ON LEGEND
 TO CLARIFY WHAT IS SHOWN ON DRAWINGS.
  
 14) SMOKE DETECTORS SHALL OPERATE SO
 THAT ACTIVATION OF ONE WILL OPERATE ALL
 DETECTORS WITHIN DWELLING UNIT, SUITE OF
 ROOMS OR SIMILAR AREA. NFPA SEC.
 9.6.2.10.3.
  
 15) PLANS INDICATE A FIRE SPRINKLER
 SYSTEM. A LAYOUT OF THE SYSTEM IS
 REQUIRED PRIOR TO SEPARATE SUBMITAL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722
  
  
  
  
  