| 2006-07-17 00:00:00 | DENIED |
| | |
| | |
| | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT |
| | SHALL BE RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSE AND A COPY SUBMITTED TO THIS |
| | OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| | BLANK FORMS ARE AVAILABLE FROM THIS |
| | OFFICE. |
| | NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF |
| | THE DESCRIBED IMPROVEMENT |
| | OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| | 90 DAYS OF RECORDING. |
| | |
| | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 4.SUBMIT TWO COPIES OF ENERGY CALCS |
| | PER 2004 FBC. |
| | |
| | 5.PRODUCT APPROVALS REQUIRED FOR |
| | WINDOWS, EXTERIOR DOORS, STORE FRONT |
| | SYSTEM, LINTELS, ROOFING AND STRAPS AND TIE-DOWNS. |
| | |
| | 6.ALL PRODUCT APPROVALS SUBMITTED WITH |
| | QUALITY ASSURANCE SHALL HAVE THE |
| | FOLLOWING STATE APPROVAL ATTACHED. |
| | |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A STATE PRODUCT APPROVAL |
| | SHEETS THAT LISTS THE PRODUCT IDENTITY |
| | NUMBER FROM THE STATE. IF THE PRODUCT |
| | DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT |
| | AN APPLICATION FOR LOCAL PRODUCT |
| | APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 7.THOSE PRODUCT APPROVALS WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL.WPB |
| | AMENDMENT TO FBC 106.3.3. |
| | |
| | 8.FIRE DOORS AT 2HR WALLS SHALL BE |
| | 1.5HR.FBC 2004 TABLE 715.3 |
| | SHOW RATED WALLS AND THE APPROPRIATE |
| | RATED DOORS. |
| | ALL DOORS SHALL COMPLY WITH THIS |
| | SECTION.DOORS TO COMMON HALLWAY DO NOT |
| | SHOW A RATING. |
| | |
| | 9.A DESIGN PROFESSIONAL OR AN OWNER |
| | MUST ELECT ONE OR A COMBINATION OF |
| | LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | SHOW HOW PLANS WILL COMPLY WITH THE |
| | SECTION(S) SELECTED.2004 FBC EXISTING |
| | BUILDING 301.5 |
| | B. SHOW COMPLIANCE WITH 707.5.1 |
| | |
| | 10.INCLUDE A LIFE SAFTEY PLAN SHOWING |
| | PATH OF TRAVEL AND TRAVEL DISTANCE |
| | COMPLYING WITH 1015.1.MOST REMOTE |
| | POINT. |
| | |
| | 11.SECOND FLOOR STAIRWAY EXIT SHALL |
| | NOT EXIT TO ALLEY WAY.BUT SHALL EXIT |
| | ON TO THE SAME PROPERTY.SUBMIT A SITE |
| | PLAN.WEST STAIRWAY DOES NOT SHOW A |
| | FIRST FLOOR EXIT ON FLOOR PLAN. |
| | |
| | 13.BASED ON FBC TABLE 602 THE NORTH |
| | WALL SHALL HAVE A 1HR. FIRE RATING. |
| | DOORS AND WINDOWS SHALL BE RATED 3/4 HR. |
| | FBC 715.3 AND FBC 715.4.SINCE LARGE |
| | MISSLE IMPACT PROTECTION IS REQUIRED, |
| | LARGE MISSLE IMPACT GLASS MAY HAVE TO BE |
| | USED WITH ROLL UP FIRE SHUTTERS |
| | COMPLYING WITH FBC 715.3.9. |
| | |
| | NEW COMMENT: |
| | A:SHOW PRESSURES FOR DOORS AND |
| | WINDOWS. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. SUBMIT ONE COPY OF |
| | OLD PAGES FOR REFERENCE. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |