Plan Review Notes
Plan Review Notes For Permit 05121124
Permit Number 05121124
Review Stop B
Sequence Number 2
Notes
Date Text
2006-07-17 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 WINDOWS, EXTERIOR DOORS, STORE FRONT
 SYSTEM, LINTELS, ROOFING AND STRAPS AND TIE-DOWNS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.FIRE DOORS AT 2HR WALLS SHALL BE
 1.5HR.FBC 2004 TABLE 715.3
 SHOW RATED WALLS AND THE APPROPRIATE
 RATED DOORS.
 ALL DOORS SHALL COMPLY WITH THIS
 SECTION.DOORS TO COMMON HALLWAY DO NOT
 SHOW A RATING.
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
 B. SHOW COMPLIANCE WITH 707.5.1
  
 10.INCLUDE A LIFE SAFTEY PLAN SHOWING
 PATH OF TRAVEL AND TRAVEL DISTANCE
 COMPLYING WITH 1015.1.MOST REMOTE
 POINT.
  
 11.SECOND FLOOR STAIRWAY EXIT SHALL
 NOT EXIT TO ALLEY WAY.BUT SHALL EXIT
 ON TO THE SAME PROPERTY.SUBMIT A SITE
 PLAN.WEST STAIRWAY DOES NOT SHOW A
 FIRST FLOOR EXIT ON FLOOR PLAN.
  
 13.BASED ON FBC TABLE 602 THE NORTH
 WALL SHALL HAVE A 1HR. FIRE RATING.
 DOORS AND WINDOWS SHALL BE RATED 3/4 HR.
 FBC 715.3 AND FBC 715.4.SINCE LARGE
 MISSLE IMPACT PROTECTION IS REQUIRED,
 LARGE MISSLE IMPACT GLASS MAY HAVE TO BE
 USED WITH ROLL UP FIRE SHUTTERS
 COMPLYING WITH FBC 715.3.9.
  
 NEW COMMENT:
 A:SHOW PRESSURES FOR DOORS AND
 WINDOWS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672