Plan Review Notes
Plan Review Notes For Permit 05121124
Permit Number 05121124
Review Stop M
Sequence Number 1
Notes
Date Text
2006-02-07 00:00:00----------------DENIED-----------------
 1)DUCT SMOKE DETECTORS INSTALLED WITH
 RTUS 1 & 2 SHALL BE IN SUPPLY DUCT
 RATHER THAN RETURN PER 2004 FBC,M SEC
 606.2.1
  
 2)GRILL TYPES AND CFM RANGES DO NOT
 MATCH THOSE SHOWN ON AIR DEVICE SCHEDULE
  
 3)PAGE M3 UPPER FLOOR PLAN INDICATES A
 CARRIER PACKAGE TERMINAL UNIT.THIS
 EQUIPMENT IS NOT SHOWN ON EQUIPMENT
 SCHEDULE.
  
 4)PAGE M3 GROUND FLOOR PLAN - BRANCH
 DUCT FEEDING HALL 100 APPEARS TO BE
 PENETRATING A RATED PARTITION.A FIRE
 DAMPER IS NEEDED AT THIS LOCATION.THE
 BRANCH DUCT ALSO HAS NO SIZE INDICATED
 ON PLAN.
  
 5)PROVIDE ROOF PLAN SHOWING EF #S AND
 LOCATIONS.EXHAUST FAN SCHEDULE
 INDICATES ALL FANS ARE ON ROOF, BUT
 ELECTRICAL PLAN SHOWS NO PROVISION FOR
 POWER TO FANS ON ROOF.
  
 6)PAGE M3 DUCT PLAN SHOWS 8X8 EXHAUST
 DUCT UP TO EF 1 ON ROOF, TWO LOCATIONS.
 DUCT IS ROUTED IN A RATED SHAFT.HOW
 AND AT WHAT LOCATION WILL EXHAUST DUCT
 EXIT THE RATED SHAFT SINCE IT IS LOCATED
 DIRECTLY BELOW RTUS?
  
 7)PLEASE SHOW FRESH AIR CALCULATIONS PER
 2004 FBC,M SEC 403.3
  
 8)EQUIPMENT REQUIRING SERVICE ON ROOFS
 HIGHER THAN 16' REQUIRE PERMENANT ACCESS
 PER 2004 FBC,M SEC 306.5
  