| 2006-02-07 00:00:00 | ----------------DENIED----------------- |
| | 1)DUCT SMOKE DETECTORS INSTALLED WITH |
| | RTUS 1 & 2 SHALL BE IN SUPPLY DUCT |
| | RATHER THAN RETURN PER 2004 FBC,M SEC |
| | 606.2.1 |
| | |
| | 2)GRILL TYPES AND CFM RANGES DO NOT |
| | MATCH THOSE SHOWN ON AIR DEVICE SCHEDULE |
| | |
| | 3)PAGE M3 UPPER FLOOR PLAN INDICATES A |
| | CARRIER PACKAGE TERMINAL UNIT.THIS |
| | EQUIPMENT IS NOT SHOWN ON EQUIPMENT |
| | SCHEDULE. |
| | |
| | 4)PAGE M3 GROUND FLOOR PLAN - BRANCH |
| | DUCT FEEDING HALL 100 APPEARS TO BE |
| | PENETRATING A RATED PARTITION.A FIRE |
| | DAMPER IS NEEDED AT THIS LOCATION.THE |
| | BRANCH DUCT ALSO HAS NO SIZE INDICATED |
| | ON PLAN. |
| | |
| | 5)PROVIDE ROOF PLAN SHOWING EF #S AND |
| | LOCATIONS.EXHAUST FAN SCHEDULE |
| | INDICATES ALL FANS ARE ON ROOF, BUT |
| | ELECTRICAL PLAN SHOWS NO PROVISION FOR |
| | POWER TO FANS ON ROOF. |
| | |
| | 6)PAGE M3 DUCT PLAN SHOWS 8X8 EXHAUST |
| | DUCT UP TO EF 1 ON ROOF, TWO LOCATIONS. |
| | DUCT IS ROUTED IN A RATED SHAFT.HOW |
| | AND AT WHAT LOCATION WILL EXHAUST DUCT |
| | EXIT THE RATED SHAFT SINCE IT IS LOCATED |
| | DIRECTLY BELOW RTUS? |
| | |
| | 7)PLEASE SHOW FRESH AIR CALCULATIONS PER |
| | 2004 FBC,M SEC 403.3 |
| | |
| | 8)EQUIPMENT REQUIRING SERVICE ON ROOFS |
| | HIGHER THAN 16' REQUIRE PERMENANT ACCESS |
| | PER 2004 FBC,M SEC 306.5 |
| | |