| 2006-02-08 00:00:00 | ******DENIED****** |
| | |
| | PLAN REVIEW ONLY |
| | |
| | 1) IN ADDITION TO APPLICABLE BUILDING |
| | CODES, NFPA 101, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 2) MEANS OF EGRESS ILLUSTRATES BUSINESS |
| | ONLY, HOWEVER BUILDING MEETS |
| | REQUIREMENTS FOR MULTIPLE OCCUPANCY. |
| | |
| | 3) WORK TO COMPLY WITH NFPA 101, SEC. |
| | 6.1.14 MULTIPLE OCCUPANCIES AND ALL |
| | OTHER APPLICABLE CODES. |
| | |
| | 4) PLANS SHOW BUILDING TO BE FULLY FIRE |
| | SPRINKLERED BUT NOT MONITORED. FIRE |
| | SPRINKLER SYSTEM SHALL BE UL CERTIFIED |
| | FOR CENTRAL STATION SERVICE. |
| | |
| | 5) SEPARATE SHOP DRAWINGS AND PERMITS |
| | REQUIRED FOR FIRE SPRINKLER/FIRE ALARM |
| | SYSTEMS. |
| | |
| | 6) CONSTRUCTION, ALTERATION AND |
| | DEMOLITION TO COMPLY WITH NFPA 241. |
| | |
| | 7) 2A-10B,C RATED FIRE EXTINGUISHERS ARE |
| | REQUIRED. LOCATIONS TO BE SHOWN ON |
| | DRAWINGS. |
| | |
| | 8) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENT FOR HANDRAILS AND GUARDS. |
| | |
| | 9) ONE STAIRWELL ON SHT A1.1 APPEARS TO |
| | BE OPEN TO THE COMMON AREA. ARE |
| | STAIRWELLS RATED ENCLOSURES? |
| | |
| | 10) SHT A1.0 INDICATES THAT STAIRWELLS |
| | ARE 2 HR RATED. THAT BEING THE CASE, ALL |
| | ASSOCIATED DOORS SHALL HAVE 1 1/2 HR |
| | RATING. |
| | |
| | 11) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILINGS IN |
| | TERMS OF CLASS A,B OR C. |
| | |
| | 12) PLEASE SHOW LOCATIONS OF REQUIRED |
| | HARDWIRED SMOKE DETECTORS THAT SHALL BE |
| | A MINIMUM OF 3' FROM HVAC DIFFUSERS. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLANS REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |