2006-02-08 00:00:00******DENIED******
  
 PLAN REVIEW ONLY
  
 1) IN ADDITION TO APPLICABLE BUILDING
 CODES, NFPA 101, 2003 EDITION SHALL BE
 REFERENCED.
  
 2) MEANS OF EGRESS ILLUSTRATES BUSINESS
 ONLY, HOWEVER BUILDING MEETS
 REQUIREMENTS FOR MULTIPLE OCCUPANCY.
  
 3) WORK TO COMPLY WITH NFPA 101, SEC.
 6.1.14 MULTIPLE OCCUPANCIES AND ALL
 OTHER APPLICABLE CODES.
  
 4) PLANS SHOW BUILDING TO BE FULLY FIRE
 SPRINKLERED BUT NOT MONITORED. FIRE
 SPRINKLER SYSTEM SHALL BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER/FIRE ALARM
 SYSTEMS.
  
 6) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 7) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED. LOCATIONS TO BE SHOWN ON
 DRAWINGS.
  
 8) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
 9) ONE STAIRWELL ON SHT A1.1 APPEARS TO
 BE OPEN TO THE COMMON AREA. ARE
 STAIRWELLS RATED ENCLOSURES?
  
 10) SHT A1.0 INDICATES THAT STAIRWELLS
 ARE 2 HR RATED. THAT BEING THE CASE, ALL
 ASSOCIATED DOORS SHALL HAVE 1 1/2 HR
 RATING.
  
 11) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS IN
 TERMS OF CLASS A,B OR C.
  
 12) PLEASE SHOW LOCATIONS OF REQUIRED
 HARDWIRED SMOKE DETECTORS THAT SHALL BE
 A MINIMUM OF 3' FROM HVAC DIFFUSERS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  