| 2006-02-07 00:00:00 | ********* UNSAT ************ |
| | |
| | |
| | ** PLEASE KNOW, PLANS HAVE ONLY BEEN |
| | SUBMITTED FOR "PLAN REVIEW" ONLY NAD |
| | HAVE NOT BEEN SUBMITTED FOR PERMIT. |
| | |
| | 1)NOTE: PLEASE SEE THAT ALL DESIGNS AND |
| | CODES ARE REFERENCED TO THE CURRENT |
| | CODES ADOPTED BY THE STATE OF FLORIDA. |
| | PLEASE KNOW, WE ARE CURRENTLY UNDE THE |
| | 2004 FLORIDA BLDG CODE. |
| | 2002 NFPA-70, 2002 NFPA-72,2003 NFPA-101 |
| | PLEASE ADJUST. |
| | PLEASE ALSO SEE NOTES BELOW AS ELCTRICAL |
| | CODE IS BEING REFERENCED FROM THE 1996 |
| | NFPA-70 (NEC). |
| | |
| | 2)NOTE: PLEASE SEE MISSING INFORMATION |
| | AND LICENSE INFORMATION REQUIRED ON |
| | TITLE BLOCKS FOR THE ARCHITECTUAL FIRM, |
| | ENGINEER AND FIRM? ETC. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.002, 61G1-16.004 AND FLORIDA |
| | STATUES, 481.219, 471.023 . |
| | PLEASE KNOW: THIS IS REQUIRED OF ALL |
| | TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 3)NOTE: PLEASE ALSO PROVIDE A SIGNED, |
| | DATED AND SEALED LETTER FOR THE ENGINEER |
| | AS SHOWN ON PLANS AFFIRMING THE LEGAL |
| | SIGNATURE ON SAID PLANS. PLANS APPEAR TO |
| | INDICATE INITIAL(S)? |
| | THIS LETTER IS TO BE CORRECTLY |
| | NOTORIZED, AND WILL BE PLACED IN OUR |
| | SIGNATURE FILE FOR FUTUREREFERENCE. |
| | |
| | 4)NOTE: PLEASE INDICATE THE ROOF TOP |
| | RECEPTS AS GFI OR GFI PROTECTED AS |
| | REQUIRED PER 210.8B2 |
| | |
| | 5)NOTE: PLEASE SEE NO COMMON AREAS SHALL |
| | BE FED FROM CIRCUIT DERVIED FROM APTS OR |
| | OFFICE UNITS. PLEASE SEE CIRCUITING OF |
| | HALL RECEPTS ARE SHOWN TO ONE UNIT. |
| | PLEASE SEE 210.25 |
| | |
| | 6)NOTE: PLEASE SHOW ALL KITCHEN |
| | COUNTERSPACE RECEPTS AS GFI/ GFI |
| | PROTECTED AS REQUIRED PER 210.8A6 |
| | |
| | 7)NOTE: PLEASE SEE IF OFFICE UNITS WHICH |
| | WILL ALSO BE REQUIRED TO HAVE GFI |
| | RECEPTS, EITHER BASE ON POSSIBLE USE |
| | CHANGE TO DWELLING UNITS, OR AS REQUIRED |
| | PER 210.8B3 |
| | |
| | 8)NOTE: PLEASE SEE A MIN OF TWO SMALL |
| | APPLIANCE CIRCUITS ARE REQUIED PER |
| | 210.52B1. |
| | |
| | 9)NOTE: PLEASE SEE 210.52B1, 210.11C1, |
| | 220.16A WHICH REQUIRES EACH TO BE |
| | FIGURED AT A MIN OF 1500 VA. |
| | |
| | 10)NOTE: PLEASE SEE 210.52B1 WHICH |
| | REQUIRE STHE ONE OR MORE SMALL APPLIANCE |
| | CIRCUITS TO FEED DINING ROOM(S) AND THE |
| | LIKE AREAS. PLEASE SEE CIRCUITING |
| | FEEDING DINING RM AREA MAY NOT FEED |
| | LIVING RMS OR ANY OTHER AREAS. |
| | |
| | 11)NOTE: PLEASE SEE 210.11C2, 220.16B |
| | WHICH REQUIRES A MIN LAUNDRY /WASHER |
| | CIRCUIT TO BE 1500VA . |
| | |
| | 12)NOTE: PLEASE SEE 220.18, 240.4, |
| | 310.16, DRYER SAHLL BE FIGURED AT A MIN |
| | OF 5KW, 30A, #10 AWG. |
| | PLEASE ADJUST AS THESE ARE SHOWN ON A |
| | 2-POLE 20A BRKR? |
| | |
| | 13)NOTE: PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUITS AS REQUIRD |
| | UNDER THE 2002 NEC 210.12B |
| | PLEASE KNOW, ALL, ELECTRICAL |
| | DEVICES/OUTLETS SUCH AS LTS, SD'S |
| | RECEPTS, FANS ETC SHALL BE AFCI |
| | PROTECTED. |
| | ** PLEASE KNOW, AREAS NOW SHOWN AS |
| | "OFFICES" ARE UNITS WHICH SEEM TO SHOW |
| | POSSIBLE CHANGE IN-USE OR OCCUPANCY. IF |
| | THESE AREAS ARE ADAPTABLE FOR |
| | RESIDENTIAL USE, THEN AFCI PROTECTION |
| | WILL BE REQUIRED FOR THESE ROOMS. |
| | |
| | 14)NOTE: PLEASE SEE NFPA-70 11.5.1.1 |
| | WHICH REQUIRES THE USE OF SMOKE |
| | DETECTORS INSIDE AND OUTSIDE ALL |
| | SLEEPING RMS OR ADAPTABLE SLEEPINS |
| | ROOMS.** PLEASE SEE PREVIOUS NOTES WITH |
| | RESPECT TO THE CIRCUITING OF BEDRMS. |
| | |
| | 15)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. PLEASE SEE CIRCUTING |
| | MISSING. |
| | 215.5 |
| | |
| | 16)NOTE: PLEASE SEE MANY AREA WHERE |
| | THERE ARE HAND-DRAWN CHANGES MADE TO |
| | PLANS WHICH ARE SIGNED AND SEALED |
| | DOCUMENTS. PLEASE KNOW, THIS IS NOT |
| | PERMITTED UDNER FS 471.025. |
| | |
| | 17)NOTE: PLEASE SEE THAT PANEL SCHEDULES |
| | INDICATE ALL CONDUCTORSIZES, PER |
| | 240.4,310.16. |
| | |
| | 18)NOTE: PELASE SEE RECEPTS FOR LV TYPE |
| | PLUG-IN TRANSFORMERS ARE NOT PERMITTED |
| | IN CLOTHES CLOSETS AND LOCATIONS IN |
| | CLOSE PROXIMITY OF EASILY IGNITIBLE |
| | MATERIALS. |
| | PLEASE SEE 110.26,240.24, ETC |
| | AS THESE TYPE UNITS CREATE HIGH TEMPS |
| | AND HAVE CAUSED FIRES IN THIS |
| | JURISDICTION, THESE WILL NOT BE |
| | PERMITTED IN THESE CLOSETS DUE TO THE |
| | LIFE SAFETY AND PROPERTY HAZARD IT |
| | CREATES. |
| | |
| | 19)NOTE: PLEASE SEE 700.12EWHICH |
| | REQUIRESD THE BRANCH CIRCUIT FEEDING THE |
| | UNIT EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | PLEASE ADJUST CIRCUITING AS SHOWN. |
| | |
| | 20)NOTE: PLEASE PROVIDE THE |
| | PHOTOMETRICAS FOR EXITING STAIR AREAS AS |
| | NFPA-101 7.8.1.3 REQUIES A MIN OF 10FT |
| | CANDLES (108 LUX) FOR THE ALL AREAS OF |
| | WALKING SURFACE IN STAIRS UNDER NORMAL |
| | POWER AND IS PERMITTED TO BE LOWERED TO |
| | A MIN OF 1FT CANDLE (10.8 LUX) UNDER |
| | EMERGENCY CONDITIONS, 7.9.2.2 |
| | |
| | 21)NOTE: PLEASE CORRELATE THE FIXTURE |
| | LEGEND WITH PLANS. |
| | PLEASE ALSO CORRELATE THE FIXTURE |
| | SCHEDULE WITH PLANS AS SOME FIXTURES ARE |
| | LABELED ON PLANS , YET NOT ON SCHEDULE. |
| | E-1). |
| | |
| | 22)NOTE: PLEASE SEE UNIT "F" AS |
| | DISCONNECT FOR WH SEEMS TO BE LABELED AS |
| | "RTU". |
| | |
| | 23)NOTE: PLEASE SEE 250.6, 250.24, NO |
| | "EQUIPMENT GROUNDING CONDUCTORS" SHALL |
| | BE INSTALLED BEFORE THEFIRST MEANS OF |
| | DISCONNETC. PLEASE SEE THESE ARE SHOWN |
| | FROM FPL, TO GUTTER, TO METER ETC. |
| | |
| | 24)NOTE: PLEASE SEE NOTE #3 ON E-7 WHICH |
| | REFERENCES THE 1996 NEC. |
| | PLEASE ADJUST. |
| | |
| | 25)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | DETAIL SHALL BE SHOWN IN LEIU OF CODE |
| | REFERENCE. |
| | PLEASE SEE FBC 1040.2.1, TECHNICAL CODES |
| | SHALLL NOT BE REFERENCE IN LEIU OF |
| | TERCHNICAL INFORMATION REQUIRED ON |
| | PLANS. |
| | PLEASE SEE 250.50, FOR MIN CONNECTIONS |
| | TO BE MADE. |
| | |
| | 26)NOTE: PLEASE SUBMITLOAD |
| | CALCULATIONS FOR ALL AREAS, PANELS, |
| | BLDG. PLEASE SEE THESE ARE SHOWN A MIXED |
| | USE. PLEASE ADJSUT ACCORDINGLY. |
| | PLEASE ALSO INDICATE OF CONTINUOUS LOADS |
| | AT 125%. 215.3,230.42, |
| | 220.10,220.11,220.13 ETC |
| | |
| | 27)NOTE: PLEASE BE SURE TO SEE THE 2004 |
| | FBC CHAPTER 13 WITH RESPECT TO THE |
| | ENERGY CODE AND DESIGNS. PLEASE KNOW |
| | THIS IS A COMMERCIAL BLGD WITH A CHANGE |
| | OF OCCUPANCY WHICH WILL REQUIRE ENERGY |
| | CODE UPGRADES. |
| | |
| | ** PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER REVIEWER(S) WHICH |
| | MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO REMOVED ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED |
| | SHEETS SEPARATED FROM NEW SETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2006-02-06 00:00:00 | IN ELEC FOR REVIEW , REVIEW IN PROGRESS. |
| | NOTES TO FOLLOW. |