Plan Review Notes
Plan Review Notes For Permit 05121124
Permit Number 05121124
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-07 00:00:00********* UNSAT ************
  
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" ONLY NAD
 HAVE NOT BEEN SUBMITTED FOR PERMIT.
  
 1)NOTE: PLEASE SEE THAT ALL DESIGNS AND
 CODES ARE REFERENCED TO THE CURRENT
 CODES ADOPTED BY THE STATE OF FLORIDA.
 PLEASE KNOW, WE ARE CURRENTLY UNDE THE
 2004 FLORIDA BLDG CODE.
 2002 NFPA-70, 2002 NFPA-72,2003 NFPA-101
 PLEASE ADJUST.
 PLEASE ALSO SEE NOTES BELOW AS ELCTRICAL
 CODE IS BEING REFERENCED FROM THE 1996
 NFPA-70 (NEC).
  
 2)NOTE: PLEASE SEE MISSING INFORMATION
 AND LICENSE INFORMATION REQUIRED ON
 TITLE BLOCKS FOR THE ARCHITECTUAL FIRM,
 ENGINEER AND FIRM? ETC.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002, 61G1-16.004 AND FLORIDA
 STATUES, 481.219, 471.023 .
 PLEASE KNOW: THIS IS REQUIRED OF ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 3)NOTE: PLEASE ALSO PROVIDE A SIGNED,
 DATED AND SEALED LETTER FOR THE ENGINEER
 AS SHOWN ON PLANS AFFIRMING THE LEGAL
 SIGNATURE ON SAID PLANS. PLANS APPEAR TO
 INDICATE INITIAL(S)?
 THIS LETTER IS TO BE CORRECTLY
 NOTORIZED, AND WILL BE PLACED IN OUR
 SIGNATURE FILE FOR FUTUREREFERENCE.
  
 4)NOTE: PLEASE INDICATE THE ROOF TOP
 RECEPTS AS GFI OR GFI PROTECTED AS
 REQUIRED PER 210.8B2
  
 5)NOTE: PLEASE SEE NO COMMON AREAS SHALL
 BE FED FROM CIRCUIT DERVIED FROM APTS OR
 OFFICE UNITS. PLEASE SEE CIRCUITING OF
 HALL RECEPTS ARE SHOWN TO ONE UNIT.
 PLEASE SEE 210.25
  
 6)NOTE: PLEASE SHOW ALL KITCHEN
 COUNTERSPACE RECEPTS AS GFI/ GFI
 PROTECTED AS REQUIRED PER 210.8A6
  
 7)NOTE: PLEASE SEE IF OFFICE UNITS WHICH
 WILL ALSO BE REQUIRED TO HAVE GFI
 RECEPTS, EITHER BASE ON POSSIBLE USE
 CHANGE TO DWELLING UNITS, OR AS REQUIRED
 PER 210.8B3
  
 8)NOTE: PLEASE SEE A MIN OF TWO SMALL
 APPLIANCE CIRCUITS ARE REQUIED PER
 210.52B1.
  
 9)NOTE: PLEASE SEE 210.52B1, 210.11C1,
 220.16A WHICH REQUIRES EACH TO BE
 FIGURED AT A MIN OF 1500 VA.
  
 10)NOTE: PLEASE SEE 210.52B1 WHICH
 REQUIRE STHE ONE OR MORE SMALL APPLIANCE
 CIRCUITS TO FEED DINING ROOM(S) AND THE
 LIKE AREAS. PLEASE SEE CIRCUITING
 FEEDING DINING RM AREA MAY NOT FEED
 LIVING RMS OR ANY OTHER AREAS.
  
 11)NOTE: PLEASE SEE 210.11C2, 220.16B
 WHICH REQUIRES A MIN LAUNDRY /WASHER
 CIRCUIT TO BE 1500VA .
  
 12)NOTE: PLEASE SEE 220.18, 240.4,
 310.16, DRYER SAHLL BE FIGURED AT A MIN
 OF 5KW, 30A, #10 AWG.
 PLEASE ADJUST AS THESE ARE SHOWN ON A
 2-POLE 20A BRKR?
  
 13)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS AS REQUIRD
 UNDER THE 2002 NEC 210.12B
 PLEASE KNOW, ALL, ELECTRICAL
 DEVICES/OUTLETS SUCH AS LTS, SD'S
 RECEPTS, FANS ETC SHALL BE AFCI
 PROTECTED.
 ** PLEASE KNOW, AREAS NOW SHOWN AS
 "OFFICES" ARE UNITS WHICH SEEM TO SHOW
 POSSIBLE CHANGE IN-USE OR OCCUPANCY. IF
 THESE AREAS ARE ADAPTABLE FOR
 RESIDENTIAL USE, THEN AFCI PROTECTION
 WILL BE REQUIRED FOR THESE ROOMS.
  
 14)NOTE: PLEASE SEE NFPA-70 11.5.1.1
 WHICH REQUIRES THE USE OF SMOKE
 DETECTORS INSIDE AND OUTSIDE ALL
 SLEEPING RMS OR ADAPTABLE SLEEPINS
 ROOMS.** PLEASE SEE PREVIOUS NOTES WITH
 RESPECT TO THE CIRCUITING OF BEDRMS.
  
 15)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE. PLEASE SEE CIRCUTING
 MISSING.
 215.5
  
 16)NOTE: PLEASE SEE MANY AREA WHERE
 THERE ARE HAND-DRAWN CHANGES MADE TO
 PLANS WHICH ARE SIGNED AND SEALED
 DOCUMENTS. PLEASE KNOW, THIS IS NOT
 PERMITTED UDNER FS 471.025.
  
 17)NOTE: PLEASE SEE THAT PANEL SCHEDULES
 INDICATE ALL CONDUCTORSIZES, PER
 240.4,310.16.
  
 18)NOTE: PELASE SEE RECEPTS FOR LV TYPE
 PLUG-IN TRANSFORMERS ARE NOT PERMITTED
 IN CLOTHES CLOSETS AND LOCATIONS IN
 CLOSE PROXIMITY OF EASILY IGNITIBLE
 MATERIALS.
 PLEASE SEE 110.26,240.24, ETC
 AS THESE TYPE UNITS CREATE HIGH TEMPS
 AND HAVE CAUSED FIRES IN THIS
 JURISDICTION, THESE WILL NOT BE
 PERMITTED IN THESE CLOSETS DUE TO THE
 LIFE SAFETY AND PROPERTY HAZARD IT
 CREATES.
  
 19)NOTE: PLEASE SEE 700.12EWHICH
 REQUIRESD THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE ADJUST CIRCUITING AS SHOWN.
  
 20)NOTE: PLEASE PROVIDE THE
 PHOTOMETRICAS FOR EXITING STAIR AREAS AS
 NFPA-101 7.8.1.3 REQUIES A MIN OF 10FT
 CANDLES (108 LUX) FOR THE ALL AREAS OF
 WALKING SURFACE IN STAIRS UNDER NORMAL
 POWER AND IS PERMITTED TO BE LOWERED TO
 A MIN OF 1FT CANDLE (10.8 LUX) UNDER
 EMERGENCY CONDITIONS, 7.9.2.2
  
 21)NOTE: PLEASE CORRELATE THE FIXTURE
 LEGEND WITH PLANS.
 PLEASE ALSO CORRELATE THE FIXTURE
 SCHEDULE WITH PLANS AS SOME FIXTURES ARE
 LABELED ON PLANS , YET NOT ON SCHEDULE.
 E-1).
  
 22)NOTE: PLEASE SEE UNIT "F" AS
 DISCONNECT FOR WH SEEMS TO BE LABELED AS
 "RTU".
  
 23)NOTE: PLEASE SEE 250.6, 250.24, NO
 "EQUIPMENT GROUNDING CONDUCTORS" SHALL
 BE INSTALLED BEFORE THEFIRST MEANS OF
 DISCONNETC. PLEASE SEE THESE ARE SHOWN
 FROM FPL, TO GUTTER, TO METER ETC.
  
 24)NOTE: PLEASE SEE NOTE #3 ON E-7 WHICH
 REFERENCES THE 1996 NEC.
 PLEASE ADJUST.
  
 25)NOTE: PLEASE SEE GROUNDING ELECTRODE
 DETAIL SHALL BE SHOWN IN LEIU OF CODE
 REFERENCE.
 PLEASE SEE FBC 1040.2.1, TECHNICAL CODES
 SHALLL NOT BE REFERENCE IN LEIU OF
 TERCHNICAL INFORMATION REQUIRED ON
 PLANS.
 PLEASE SEE 250.50, FOR MIN CONNECTIONS
 TO BE MADE.
  
 26)NOTE: PLEASE SUBMITLOAD
 CALCULATIONS FOR ALL AREAS, PANELS,
 BLDG. PLEASE SEE THESE ARE SHOWN A MIXED
 USE. PLEASE ADJSUT ACCORDINGLY.
 PLEASE ALSO INDICATE OF CONTINUOUS LOADS
 AT 125%. 215.3,230.42,
 220.10,220.11,220.13 ETC
  
 27)NOTE: PLEASE BE SURE TO SEE THE 2004
 FBC CHAPTER 13 WITH RESPECT TO THE
 ENERGY CODE AND DESIGNS. PLEASE KNOW
 THIS IS A COMMERCIAL BLGD WITH A CHANGE
 OF OCCUPANCY WHICH WILL REQUIRE ENERGY
 CODE UPGRADES.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVED ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED
 SHEETS SEPARATED FROM NEW SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-02-06 00:00:00IN ELEC FOR REVIEW , REVIEW IN PROGRESS.
 NOTES TO FOLLOW.