| Date |
Text |
| 2006-01-04 00:00:00 | DENIED: |
| | 1.RETURN AIR FROM BATHROOM AREAS SHALL |
| | NOT BE RECIRCULATED PER 2004 FMC 407.1. |
| | |
| | 2.PLAN SHEET 7 OF 8 INDICATES 150 CFM |
| | OF EXHAUST FROM THE MENS RESTROOM/SHOWER |
| | AREA.PER 2004 FMC TABLE 403.3, A TOTAL |
| | OF 200 CFM IS REQUIRED FROM THE MENS |
| | ROOM. |
| | |
| | 3.PROVIDE MANUFACTURER INFORMATION OR |
| | SPECIFICATIONS FOR THE EXHAUST FAN. |
| | PLANS DOES NOT INDICATE IF THE EXHAUST |
| | FAN IS NEW OR EXISTING. |
| | |
| | 4.PLAN SHEET 7 OF 8 INDICATES SUPPLY |
| | AND RETURN AIR DUCT GOINX DOWN TO THE |
| | 1ST FLOOR IN AN EXISTING OPENING. |
| | PLEASE CLARIFY IF THIS PENETRATION IS |
| | RATED.SHOW COMPLIANCE WITH 2004 FMC |
| | 607.6.1 & 607.8 OR 607.6.3. |
| | |
| | 5.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS IN ACCORDANCE WITH 2004 FMC |
| | TABLE 403.3. |
| | |
| | 6.PLAN SHEET 8 OF 8, DETAIL FOR THE |
| | AHU SHOWS A "SAFE-T-SWITCH" ON THE |
| | AUXILIARY DRAIN LINE.PLEASE INDICATE |
| | IF THE AHU HAS A BOTTOM RETURN.PLEASE |
| | INDICATE IF THE RETURN AIR IS A DUCTED |
| | BOTTOM RETURN OR SHOW COMPLIANCE WITH |
| | 2004 FMC 307.2.3. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |