| 2006-02-17 00:00:00 | DENIED: |
| | 1.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS PER 2004 FMC 403.3. |
| | |
| | 2.INDICATE OUTSIDE AIR DUCT SIZE, |
| | MATERIAL & LAYOUT. |
| | |
| | 3.PLAN SHEET AC-1 INDICATES FLEX DUCT |
| | THORUGH A RATED WALL WITH A FIRE DAMPER. |
| | PER 2004 FMC 603.5.5, FLEXIBLE AIR DUCTS |
| | & FLEX CONNECTORS SHALL NOT PASS THROUGH |
| | ANY FIRE RESISTANCE RATED ASSEMBLY. |
| | |
| | 4.PLAN SHEET AC-2 HVAC DESIGN |
| | REQUIREMENT CHART INDICATES FIRE DAMPERS |
| | & DUCT SMOKE DETECTORS ARE NOT REQUIRED. |
| | THIS IS INCORRECT.FIRE DAMPERS ARE |
| | REQUIRED THROUGH FIRE RATED PARTITIONS. |
| | PLAN SHEET A-1, FIRST FLOOR ACCORDING TO |
| | THE PARTITION LEGEND THE FOLLOWING AREAS |
| | ARE INDICATED AS FIRE RATED PARTITIONS: |
| | 1) BETWEEN THE ART STUDIO & COMMON AREA |
| | 2) BATHROOM AREAS AND THE COMMON AREA |
| | 3) KITCHEN AREA TO THE CONFERENCE ROOM & |
| | THE CORRIDOR. |
| | |
| | PLEASE NOTE, FIRE DAMPERS ARE NOT |
| | REQUIRED SHOULD PENETRATION MEET ALL THE |
| | REQUIREMENTS OF 2004 FMC 607.5.3 |
| | EXCEPTION #2 ITEMS 2.1 THROUGH 2.6, |
| | PLEASE ANNOTATE ON THE PLAN. |
| | |
| | 5. DUCT SMOKE DETECTORS REQUIRED IN |
| | SYSTEMS THAT HAVE THE DESIGN CAPACITY TO |
| | PRODUCE GREATER THAN 2,000 CFM.SYSTEM |
| | 4 HAS THIS CAPACITY.PLEASE INDICATE |
| | DUCT SMOKE DETECTOR ON THE PLAN IN |
| | ACCORDANCE WITH 2004 FMC 606.2.1. |
| | |
| | 6.PLAN SHEET AC-2 DETAIL FOR THE ROOF |
| | CURB.IS THIS FOR THE CONDENSER UNITS? |
| | PROVIDE DETAIL OF HOW THE UNITS WILL BE |
| | ATTACHED TO THE CURB.TYPICALLY |
| | CONDENSER UNITS ARE MOUNTED ON STANDS IN |
| | ACCORDANCE WITH 2004 FBC TABLE 1509.7. |
| | |