| 2006-02-07 00:00:00 | ************ UNSAT **************** |
| | |
| | *** PLEASE KNOW, PLANS ARE NOT COMPLETE |
| | FOR A COMPLETE REVIEW FOR CODE |
| | COMPLIANCE AT THIS TIME. |
| | PLEASE SEE NOTES BELOW. |
| | |
| | 1)NOTE: PLEASE BE SURE TO COMPLETE ALL |
| | CIRCUITING ON PLANS AND CORRELATE WITH |
| | THE SUBMITTED PANEL SCHEDULES. |
| | PLEASE SEE THERE ARE MANY DEVICES WHICH |
| | DO NOT INDICATE ANY CIRCUITS AND MANY |
| | CIRCUITS WHICH DO NOT CORRELATE WITH THE |
| | SUBMITTED SCHEDULES. |
| | |
| | 2)NOTE: PLEASE BE SURE PLANS REFERENCE |
| | THE CURRENT CODES IN EFFECT AS LISTED. |
| | NFPA-101 2003, NFPA-72 2002, NFPA-70, |
| | 2002. |
| | |
| | 3)NOTE: PLEASE SEE THERE ARE LOCATIONS |
| | ON PLANS WHICH MAKE REFERENCE TO "FOUR |
| | APTS"?? PLEASE DECIDE THE USE, AND |
| | ADJUST PLANS AS NEED. PLEASE SEE OTHER |
| | COMMENTS WITH RESPECT TO FEEDERS/ LOAD CALCULATIONS |
| | ETC. |
| | ** PLEASE KNOW, IF INDEED THERE IS GOING |
| | TO FOUR APT UNITS, PLEASE SEE THE |
| | FOLLOWING COMMENT. |
| | |
| | 4)NOTE: IF 4 APTS? |
| | PLEASE PROVIDE COMPLETE HEIGHT/DEVICE |
| | LOCATIONS AS REQUIRED UNDER FAIR HOUSING |
| | ACT REGULATIONS 24 CFR100.205 |
| | |
| | 5)NOTE:PLEASE SEE NO MAIN OR OCP IS |
| | SHOWN ON RISER FOR SERVICE. 230.70, |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE SEE NO OCP IS SHOWN FOR |
| | MAINS/FEEDS TO EACH PANEL. PLEASE SEE |
| | RISER SHOWS FEEDERS "TYPICAL OF 4"?? |
| | PLEASE INDICATE THE OCP FOR EACH, |
| | 240.4,310.16, 230.70 ETC. |
| | |
| | 7)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR TO EACH PANEL. |
| | 250.110,250.122 ETC. |
| | |
| | 8)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | SYSTEM MENTIONS TO ATTACHED TO FOOTER |
| | STEEL? PLEASE KNOW,IN AN EXISTING |
| | BUILDING, IT IS NOT REQUIRED AND IS NOT RECOMMENDED DUE |
| | TO THE STRUCTUAL |
| | INTEGRITY OF THE EXISTING STEEL/FOOTER. |
| | PLEASE KNOW HOWEVER THIS IS PERMITTED, |
| | AND IF SHOWN ON RISER , IT WILL BE |
| | REQUIRED. |
| | 250.50 |
| | |
| | 9)NOTE: PLEASE SEE 250.66 FOR SIZING OF |
| | GROUNDING ELECTRODE CONDUCTOR AS THIS IS |
| | CURRENTLY SHOWN AS A "6/0"? PLEASE KNOW, |
| | THIS IS NOT A RECOGNIZED AMERICAN WIRE |
| | GAUGE STANDARD. |
| | PLEASE ADJUST AS NEED BASED ON SERVICE |
| | ENTRANCE CONDUCTORS WHICH WILL BE BASED |
| | ON LOAD CALCULATIONS."NOTE: PLEASE SEE |
| | COMMENTS BELOW FOR LOAD CALCS AS SEC'S |
| | MAY CHANGE. |
| | 215.5 |
| | |
| | 10)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | ** PLEASE SEE NOTE #20 ON NOTES WHICH |
| | MENTIONS THE USE OF FUSES, HOWEVER NONE |
| | ARE SHOWN? |
| | |
| | 11)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | PLEASE SEE THIS IS A MIXED USE. |
| | PLEASE SEE THE RESIDENTIAL LOAD |
| | CALCULATIONS ARE BEING USED FOR THE |
| | COMMERICAL SPACE AND ONCE AGAIN THE LOAD CALCULATIONS |
| | MAKE REFERENCE TO THE |
| | INSTALLATION OF"4-APTS" AND DERATING |
| | IS TAKEN FROM TABLE 220.32?? |
| | PLEASE ADJUST ALL LOAD CALCULATIONS AND |
| | SEEOTHER COMMENTS WHICH WILL AFFECT |
| | LOADS AS SHOWN. |
| | |
| | 12)NOTE: PLEASE SHOW ALL PANEL LOCATIONS |
| | FOR VERIFICATION OF CODE COMPLIANCE. |
| | 110.26,240.24 ETC. |
| | |
| | 13)NOTE: PLEASE CORRELATE PANEL |
| | SCHEDULES AND RISER, PANELS SHOWS TWO |
| | PANEL "A"'S? (MISPRINT) |
| | 215.5 |
| | |
| | 14)NOTE: PLEASE CORRELATE ALL LOAD FOR |
| | A/C SYSTEMS, AS MECHANICAL PLANS |
| | INDICATE 10KW UNITS, LOAD CALCUALTIONS |
| | INDICATE BOTH 9KW LOAD AND 5KW LOAD AND |
| | PANEL SCHEDULES INDICATE 5KW HEAT FOR |
| | ALL?? |
| | PLEASE ADJUST LOAD CALCS ETC 215.5 |
| | |
| | 15)NOTE: PLEASE SEE 424.3B WHICH |
| | REQUIRES ALL MIN OCP FOR AHU'S HEAT TO |
| | BE SIZED AT A MIN OF 125%. |
| | PLEASE SEE PANEL SCHEDULES SHOWS 50A, #6 |
| | AWG ON 5KW UNITS. |
| | ** PLEASE KNOW, THERE IS ALSO A MAX OCP. |
| | |
| | 16)NOTE: PLEASE SEE CONDUCTORS SHOWN FOR RANGE/OVENS |
| | WHICH DO NOT SEEM TO |
| | INDICATE THE REQUIRED NEUTRAL CONDUCTOR |
| | PER 250.140 |
| | |
| | 17)NOTE: PLEASE VERIFY ALL CONDUCTORS |
| | LISTED ON PANEL SCHEDULE(S). |
| | PLEASE SEE MANY ARE SHOWING 15A OCP ON |
| | #12 AWG. PLEASE ALSO SEE NOTES WHICH |
| | MENTIONS THE MIN SIZE AWG SHALL BE #12? |
| | PLEAS KNOW, #12 IS PERMITTED ON 15A OCP. |
| | |
| | 18)NOTE: PLEASE SEE AN ELEVATOR IS SHOWN |
| | ON PLANS, HOWEVER THERE IS NO INDICATION |
| | ON ANY PLANS OF THIS EQUIPMENT?? |
| | 215.5 |
| | |
| | 19)NOTE: PLEASE SEE 620.23 WHICH |
| | REQUIRES A DEDICATED BRANCH CIRCUIT FOR |
| | PIT LTS/GFI RECEPT. |
| | |
| | 20)NOTE: PLEASE ALSO SEE 620.24 WHICH |
| | REQUIRES A DEDICATED BRANCH CIRCUIT FOR |
| | ANY ELEVATOR EQUIPMENT ROOM /AREA FOR |
| | SERVICE. |
| | |
| | 21)NOTE: PLEASE KNOW, ANEMERGENCY |
| | BATTERY BACK UP TYPE LT FIXTURE WILL BE |
| | REQUIRED AT ANY ELEVATOR EQUIPMENT |
| | LOCATION.700.16,LS101 7.8/7.9 |
| | |
| | 22)NOTE: PLEASE SEE WHAT APPEARS TO BE |
| | OUTSIDE LTS ON 2ND FLOOR LEVEL WHICH |
| | INDICATES THESE LTS TO BE CIRCUIT B-8 |
| | AND A-8, HOWEVER ALSO INDICATE THESE TO |
| | BE ON A TC (TIMECLOCK)? PLEASE CORRELATE |
| | THESE IF INDEED THEY ARE TO BE ON WITH |
| | THE FIRST FLR OUTSIDE TC CIRCUIT? |
| | |
| | 23)NOTE: PLEASE SEE THE MISSING REQUIRED |
| | DEDICATED SIGN CIRCUIT AS PER 600.5 |
| | |
| | 24)NOTE: PLEASE SEE THE NEW FBC 2004, |
| | CHAPTER 13 (ENERGY CODE) FOR EXPANDED |
| | REQUIMENTS FOR COMMERCIAL BLDGS. |
| | 13-413,13-415 ETC. |
| | PLEASE ADJUST AS NEEDED. |
| | |
| | 25)NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9 |
| | WHICH REQUIRES A MIN OF BATTERY BACK UP |
| | EM LTS FOR MEANS OF EGRESS TO THE PUBLIC RIGHT-OF-WAY. |
| | PLEASE SEE FIRE REVIEW |
| | COMMENTS ALSO FOR THIS. |
| | PLEASE SEE 7.8.1.3 WHICH NOW REQUIRES A |
| | MIN OF 10 FT CANDLES (108 LUX) FOR ALL |
| | LEVELS OF STAIRS DURING NORMAL POWERE |
| | AND THE PERMITTED DE-RATINGS ALLOWED BY |
| | 7.9.2.2 UNDER EMERGENCY CONDITIONS. |
| | TO 10.8 LUX. |
| | |
| | 26)NOTE: PLEASE PROVIDE A FIXTURE |
| | SCHEDULE AND CORRELATE WITH THE PLANS. |
| | PLEASE SEE NOTES #24 AND #25 FOR TYPES |
| | OF FIXTURES. |
| | |
| | 27)NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF ALL EM/EXT LTS. THESE |
| | SHALL BE CIRCUITED TO THE LOCAL BRANCH |
| | CIRCUIT SUPPLYINGLIGHTING IN THAT |
| | AREA. |
| | |
| | 28)NOTE: PLEASE SEE 210.8A6 WHICH |
| | REQUIES ALL RECEPTS SERVIING KITCHEN |
| | COUNTERSPACES TO BE GFI/GFI PROTECTED. |
| | |
| | 29)NOTE: PLEASE SEE 210.8B3 FOR KITCHENS |
| | IN OTHER THAN DWELLING UNITS. |
| | |
| | 30)NOTE: PLEASE SEE MISSING THE REQUIRED |
| | DEDICATED BATH CIRCUITS PER |
| | 210.52D,210.11C3. SHALL BE #12 AND 20. |
| | PLEASE SEE #14, 15A SHOWN FOR BOTH APTS |
| | UPSTAIRS. |
| | ** PLEASE SEE WHAT APPEARS TO BE APT |
| | WHICH SHOWS A CIRCUIT #8 FOR BATH GFI'S. |
| | PLEASE KNOW, THE DEDICATED BATH CIRCUIT |
| | MAY NOT FEED ANY OTHER AREAS. |
| | |
| | 31)NOTE: PLEASE SEE THE CIRCUIT |
| | INDICATED ON PLANS FOR WHAT APPEARS TO |
| | BE A WASHER LOCATION IS SHOWN AS A SPARE |
| | ON PANEL SCHEDULE?? |
| | PLEASE SEE 210.11C2, 220.16B WHICH |
| | REQUIRES A LAUNDRY CIRCUIT AND WASHER |
| | CIRCUIT TO BE A MIN 1500 VA , 20A AND |
| | #12 AWG. |
| | PLEASE ADJUST LOAD CALCUALTIONS ETC. |
| | |
| | 32)NOTE: PLEASE SEE MISSING SMOKE |
| | DETECTORS AS REQUIRED UNDER NFPA-72 |
| | 11.5.1.1. |
| | MISSING INSIDE AND OUTSIDE ALL SLEEPING |
| | RMS. |
| | PLEASE ALSO SEE 11.8.3.5 FOR LOCATIONS |
| | OF SD'S WHICH ARE REQUIRED TO BE A MIN |
| | OF 3' FROM KITCHEN AND BATH DOORS AND |
| | SHALL BE A MIN OF 20' FROM ANY COOKING |
| | APPLIANCES. (COOKING APPLIANCES WITH |
| | EXCEPTIONS). |
| | PLEASE ALSO SEE NOTE ON PLANS WHICH |
| | MENTIONS SD'S ARE TO BE WIRED AHEAD OF |
| | THE SWITCHES ON EITHER BATH OR KITCHEN |
| | LIGHTING CIRCUIT, PLEASE SEE THIS IS OK, |
| | HOWEVER ARC FAULT PROTECTION WILL THEN |
| | BE REQUIRED FOR THOSE LIGHTING CIRCUITS, |
| | PLEASE SEE BATH LTS ARE ALSO WIRED TO BE |
| | A DEDICATED CIRCUIT FOR EACH BATH RM. |
| | ** PLEASE SEE COMMENT FOR REQUIRED ARC |
| | FAULT. |
| | |
| | 33)NOTE: PLEASE LIST ALL THE REQUIRED |
| | ARC FAULT PROTECTED CIRCUITS AS REQUIRED |
| | PER 2002 NEC 210.12B |
| | |
| | 34)NOTE: PLEASE SEE A MIN OF TWO SMALL |
| | APPLIANCE CIRCUITS ARE SHOWN, HOWEVER |
| | ONLY ONE IS SHOWN FOR KITCHEN. PLEASE |
| | ADJUST CIRCUITING AS THE MIN OF TWO SM |
| | APPL CIRCUITS SHALL BE IN KITCHEN. 210.11C1,220.16A, |
| | 215.5 ETC |
| | |
| | 35)NOTE: PLEASE SEE ELECTRICAL PLANS ARE |
| | MISSING ALL A?C SYSTEMS?? AHU'S, CU'S. |
| | PLEASE SHOW ALL DISCONNECTS AS REQUIRED |
| | PER 440.11, 110.26 |
| | |
| | 36)NOTE: PLEASE SEE 210.63 FOR THE |
| | SERVICE RECEPT REQUIRED. (GFI) 210.8A |
| | |
| | 37)NOTE: PLEASE SEE MANY CIRCUITS ON |
| | PLANS MENTIONS "GEN LTS" GEN RECEPTS" |
| | PLEASE LIST THESE TO BE SPECIFIC TO THE |
| | AREAS IN WHICH THEY ARE FEEDING. |
| | |
| | 38)NOTE: PLEASE LABEL APTS ON PLANS AND |
| | CORRELATE. PLEASE SEE WHAT APPEARS TO BE |
| | APT "B". |
| | |
| | 39)NOTE: PLEASE VERIFY WHAT IS SHOWN AS |
| | A QUAD RECEPT IN KITCHEN ON FIRST FLR |
| | WHICH IS SHOWN AS 15AON PANEL |
| | SCHEDULE? |
| | PLEASE ALSO SEE PREVIOUS COMMENT WITH |
| | RESPECT TO GFI PROTECTION. |
| | |
| | 40)NOTE: PLEASE SEE PLANS WHICH SHOWS A |
| | CIRCUIT FOR WHAT IS LISTED ON PANEL |
| | SCHEDULE AS BEING A MICROWAVE # 14, |
| | HOWEVR NO DEVICE OR LOCATION IS SHOWN ON |
| | PLANS. |
| | |
| | 41)NOTE: PLEASE SEE SWITCHES WHICH ARE |
| | SHOWN WIRED TO A 3-WAY SYSTEM, HOWEVER |
| | DO NOT INDICATE BEING S3. |
| | PLEASE SEE REDLINED LOCAITONS. |
| | |
| | 42)NOTE:PLEASE SEE REDLINED MISSING |
| | RECEPT PER 210.52, 2' OF WALL. |
| | |
| | 43)NOTE: PLEASE SHOW THE LOCATION OF THE |
| | SERVICE ON PLANS/BLDG. |
| | 230.70,240.24,110.26, ETC |
| | |
| | ** PLEASE KNOW, DUE TO PLANS NOT BEING |
| | COMPLETE AND THE EXTENT OF COMMENTS, |
| | PLEASE COMPLETE ALL OF THE ABOVE TO |
| | ALLEAVIATE FUTHER COMMENTS ON THE |
| | FOLLOWING REVIEW. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | ONLY ONE COPY OF OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE TO GO OVER ANY COMMENTS OR |
| | QUESTIONS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| 2006-01-12 00:00:00 | SENT TO INCOMING AS BLDG IS MIXED USE |
| | AND SHOULD BE ON COMMERCIAL BOARD. |