| Date |
Text |
| 2006-04-24 00:00:00 | ******** UNSAT2ND REVIEW ******** |
| | |
| | ** PLEASE SEE SOME NOTES FROM FIRST |
| | REVIEW AND NEW NOTE WHICH NEED TO BE |
| | ADDRESSED. |
| | SEE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW AND LABLED ACCORDINGLY. |
| | |
| | 1)NOTE:NO, PLEASE SEE THE MISSING |
| | CETIFICATE OF AUTHORIZATION NUMBER FOR |
| | ARCHITECTURAL FIRM COULD NOT BE LOCATED |
| | ON SIAD SHEETS. |
| | THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| | ALL TRADES.** |
| | PLANS ARE LABLED THAT THIS # IS PENDING. |
| | PLEASE KNOW, UNTIL SUCH CA # IS ISSUED |
| | FROM THE STATE, PLANS MAY NOT LIST |
| | ANYTHING OTHER THAN THE ARCHITECT AS AN |
| | INDIVIDUAL. |
| | THIS A FLORIDA STATUE AND THERE ARE NO |
| | EXCEPTIONS. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE MISSING INFORMATION |
| | AS REQUIRED FOR TITLE BLOCKS FOR |
| | ARCHITECTUAL FIRM. PLEASE SEE MISSING |
| | PRINTED NAME AND LICENSE # FOR SAID |
| | ARCHITECT. PLEASE SEE MISSING |
| | CERITFICATE OF AUTHORIZATION NUMBER. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G1-16.001, ABD FLORIDA STATUES 481.219 |
| | * PLEASE KNOW THIS IS REQUIRED ON ALL |
| | SHEETS AND FOR ALL TRADES WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S)> |
| | PLEASE SEE THIS COMMENT IS FOR |
| | ARCHITECTUAL FIRM AS ENGINEER FIRM SHOWS |
| | INFORMATION AS NEEDED, HOWEVER TITLE |
| | BLOCK FOR ARCH FIRM ARE LOCATED ON |
| | ENGINEERED PLANS. |
| | |
| | 2)NOTE: OK. |
| | |
| | 3)NOTE: OK. |
| | |
| | 4)NOTE: OK, NEW SERVICE. |
| | |
| | 5)NOTE: OK, NEW SERVICE. |
| | |
| | 6)NOTE:OK, NEW SERVICE. |
| | |
| | 7)NOTE:NO, PLEASE SEE TABLE 450.3, A |
| | MAXOCP FOR THIS 225 KVA TRANSFORMER IS |
| | 350A'S. (125%). CAN NOT USE THE 250% ASS |
| | THI DOES NOT MEET THE EXCCEPTIONS AS |
| | NOTED IN TABLE. PLEASE REVISE THE 400A |
| | OCP AS SHOWN. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SEE MAX OCP FOR TRANSFORMER TO BE |
| | 125% OR PERMITTED TO PROCEED TO THE |
| | STANDARD OF OCP. |
| | PLEASE SEE 450.3,240.6 |
| | |
| | 8)NOTE: OK. |
| | |
| | 9)NOTE: OK. |
| | |
| | 10)NOTE: OK, NOTED AS 125% FOR THE |
| | ENTIRE SERVICE ABOVE THE MIN FOR |
| | CONTINOUS LOADS. OK. |
| | |
| | 11)NOTE: OK. |
| | |
| | 12)NOTE: OK. |
| | |
| | 13)NOTE: OK. |
| | |
| | NEW NOTE** |
| | |
| | 14) NOTE: PLEASE SEE FBC CHAPTER 13, |
| | 13-415.1.ABC.1.1 , .2 AND .3. |
| | PLEASE SEE SPACE CONTROL IN SEPARATE |
| | SPACES AS A TIME CLOCK IS BEING SHOWN |
| | FOR MAIN BLDG, HOWEVER LIGHTING CONTROLS |
| | IN SEPARATE SPACES ARE REQUIRED. PLEASE |
| | SPECIFY AT LOCATIONS ON LIGHTING PLANS |
| | AND DETAIL DEVICES TO BE IMPLEMENTED. |
| | PLEASE KNOW, IF USING A TIMED DEVICE, |
| | NOT MORE THAN 4HRS ON OVER-RIDE IS |
| | PERMITTED. |
| | THIS DOES NOT INCLUDE AREAS OF REQUIRED |
| | EGRESS. |
| | |
| | |
| | ** PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECRTRICAL PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT "NEW REVISED" SHEETS |
| | INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. PLEASE ONLY SUBMIT ONE COPY OF |
| | THE OLD/VOIDED SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFOMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |