Plan Review Notes
Plan Review Notes For Permit 05121076
Permit Number 05121076
Review Stop E
Sequence Number 2
Notes
Date Text
2006-04-24 00:00:00******** UNSAT2ND REVIEW ********
  
 ** PLEASE SEE SOME NOTES FROM FIRST
 REVIEW AND NEW NOTE WHICH NEED TO BE
 ADDRESSED.
 SEE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW AND LABLED ACCORDINGLY.
  
 1)NOTE:NO, PLEASE SEE THE MISSING
 CETIFICATE OF AUTHORIZATION NUMBER FOR
 ARCHITECTURAL FIRM COULD NOT BE LOCATED
 ON SIAD SHEETS.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES.**
 PLANS ARE LABLED THAT THIS # IS PENDING.
 PLEASE KNOW, UNTIL SUCH CA # IS ISSUED
 FROM THE STATE, PLANS MAY NOT LIST
 ANYTHING OTHER THAN THE ARCHITECT AS AN
 INDIVIDUAL.
 THIS A FLORIDA STATUE AND THERE ARE NO
 EXCEPTIONS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE MISSING INFORMATION
 AS REQUIRED FOR TITLE BLOCKS FOR
 ARCHITECTUAL FIRM. PLEASE SEE MISSING
 PRINTED NAME AND LICENSE # FOR SAID
 ARCHITECT. PLEASE SEE MISSING
 CERITFICATE OF AUTHORIZATION NUMBER.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.001, ABD FLORIDA STATUES 481.219
 * PLEASE KNOW THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S)>
 PLEASE SEE THIS COMMENT IS FOR
 ARCHITECTUAL FIRM AS ENGINEER FIRM SHOWS
 INFORMATION AS NEEDED, HOWEVER TITLE
 BLOCK FOR ARCH FIRM ARE LOCATED ON
 ENGINEERED PLANS.
  
 2)NOTE: OK.
  
 3)NOTE: OK.
  
 4)NOTE: OK, NEW SERVICE.
  
 5)NOTE: OK, NEW SERVICE.
  
 6)NOTE:OK, NEW SERVICE.
  
 7)NOTE:NO, PLEASE SEE TABLE 450.3, A
 MAXOCP FOR THIS 225 KVA TRANSFORMER IS
 350A'S. (125%). CAN NOT USE THE 250% ASS
 THI DOES NOT MEET THE EXCCEPTIONS AS
 NOTED IN TABLE. PLEASE REVISE THE 400A
 OCP AS SHOWN.
  
 ** PREVIOUS NOTE**
 PLEASE SEE MAX OCP FOR TRANSFORMER TO BE
 125% OR PERMITTED TO PROCEED TO THE
 STANDARD OF OCP.
 PLEASE SEE 450.3,240.6
  
 8)NOTE: OK.
  
 9)NOTE: OK.
  
 10)NOTE: OK, NOTED AS 125% FOR THE
 ENTIRE SERVICE ABOVE THE MIN FOR
 CONTINOUS LOADS. OK.
  
 11)NOTE: OK.
  
 12)NOTE: OK.
  
 13)NOTE: OK.
  
 NEW NOTE**
  
 14) NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1 , .2 AND .3.
 PLEASE SEE SPACE CONTROL IN SEPARATE
 SPACES AS A TIME CLOCK IS BEING SHOWN
 FOR MAIN BLDG, HOWEVER LIGHTING CONTROLS
 IN SEPARATE SPACES ARE REQUIRED. PLEASE
 SPECIFY AT LOCATIONS ON LIGHTING PLANS
 AND DETAIL DEVICES TO BE IMPLEMENTED.
 PLEASE KNOW, IF USING A TIMED DEVICE,
 NOT MORE THAN 4HRS ON OVER-RIDE IS
 PERMITTED.
 THIS DOES NOT INCLUDE AREAS OF REQUIRED
 EGRESS.
  
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECRTRICAL PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT "NEW REVISED" SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE ONLY SUBMIT ONE COPY OF
 THE OLD/VOIDED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFOMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved