| 2006-02-25 00:00:00 | PLUMBING PLAN REVIEW EXAMINER |
| | PAUL SCHMITZ 561-805-6692 |
| | [email protected] |
| | FBC PLUMBING 2004 |
| | FBC FUEL GAS 2004 |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE |
| | CH 1, ADMINISTRATION, 2004 EDITION ( |
| | ATFBC)FBC BUILDING 2004, CH 11 |
| | DENIED |
| | |
| | 1) SHT A9-1BREAK ROOM #102,122. |
| | DEETAIL 4/A9.3, 9/A9.1 |
| | DEPTH OF SINK SHALL BE A MAXIMUM OF |
| | 6-1/2 INCHES. |
| | 2) SHT A8.1 JANITOR CLOSET RM #126, |
| | SHOW EXISTING SERVICE SINK. |
| | 3) SHT A8.1 DRINKING FOUNTAIN NOT SHOWN |
| | (A)WHERE ONLY ONE DRINKING FOUNTAIN IS |
| | PROVIDED ON A FLOOR, THERE SHALL BE A |
| | DRINKING FOUNTAIN WHICH IS ACCESSIBLE TO |
| | INDIVIDUALS WHO USE WHEELCHAIRS IN |
| | ACCORDANCE WITH SECTION 11-4.15 AND ONE |
| | ACCESSIBLE TO THOSE WHO HAVE DIFFICULTY |
| | BENDING OR STOOPING. (THIS CAN BE |
| | ACCOMMODATED BY THE USE OF A ?HI-LO? |
| | FOUNTAIN; BY PROVIDING ONE FOUNTAIN |
| | ACCESSIBLE TO THOSE WHO USE WHEELCHAIRS |
| | AND ONE FOUNTAIN AT A STANDARD HEIGHT |
| | CONVENIENT FOR THOSE WHO HAVE DIFFICULTY |
| | BENDING; BY PROVIDING A FOUNTAIN |
| | ACCESSIBLE UNDER SECTION 11-4.15 AND A |
| | WATER COOLER; OR BY SUCH OTHER MEANS AS |
| | WOULD ACHIEVE THE REQUIRED ACCESSIBILITY |
| | FOR EACH GROUP ON EACH FLOOR.) |
| | (B)WHERE MORE THAN ONE DRINKING |
| | FOUNTAIN OR WATER COOLER IS PROVIDED ON |
| | A FLOOR, AT LEAST 50 PERCENT OF THOSE |
| | PROVIDED SHALL COMPLY WITH SECTION |
| | 11-4.15 AND SHALL BE ON AN ACCESSIBLE |
| | ROUTE. |
| | 4) SHT P-3 WATER RISER, SEC 606.1 (4) |
| | FULLY OPEN VALVES SHALL BE INSTALLEDIN |
| | THE FOLLOWING LOCATIONS.ON EVERY WATER |
| | DOWN FEED PIPE. |
| | 5) SHT P.3 WATER RISER. |
| | SEC 604.9 WATER HAMMER. A WATER HAMMER |
| | ARESSTOR SHALL BE INSTALLED WHERE QUICK |
| | CLOSING VALVES ARE UTILIZED. |
| | COMPLY WITH ASSE 1010 |
| | |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |