2006-02-15 00:00:00DENIED:
 1.PLAN SHEET A0.1 BUILDING CODE REVIEW
 INDICATES THE 2001 FLORIDA BUILDING
 CODE.AS OF OCTOBER 1, 2005 THE 2004
 FLORIDA BUILDING CODE WENT INTO EFFECT.
  
  
 2.PLEASE CLARIFY CLEARANCE FOR SERVICE
 AND REPLACEMENT OF THE ACWS.PLAN SHEET
 M-3 DOES NOT APPEAR TO GIVE ANY
 CLEARANCE.SHOW COMPLIANCE WITH 2004
 306.1.
  
 3.PLEASE INDICATE DUCT SMOKE DETECTORS
 ON PLAN IN ACCORDANCE WITH 2004 FMC
 606.2.1
  
 4.PLAN SHEET M-4 ROOF TOP DETAIL,
 PLEASE INDICATE TERMINATION OF
 CONDENSATE.PLEASE NOTE, PVC INSTALLED
 ON THE ROOF SHALL HAVE PROTECTION FROM
 UV RAYS.PROVIDE INFORMATION HOW THIS
 WILL BE ACCOMPLISHED.
  
 5.PROVIDE DETAIL OF THE SUPPORT FOR
 THE CONDENSATE LINE.
  
 6.PLAN SHEET M-4 PROVIDES SUPPORT
 DETAIL FOR THE RTU.PLEASE INDICATE
 SUPPORT DETAIL FOR THE CHILLER ALSO.
 PLEASE EQUIPMENT & SUPPORTS EXPOSED TO
 THE WIND SHALL BE DESIGNED & INSTALLED
 FOR TO RESIST WIND PRESSURES ON THE
 EQUIPMENT & SUPPORTS AS DETERMINED IN
 CHAPTER 16 OF THE 2004 FBC.
  
 PLEASE PROVIDE INSTALLATION INSTRUCTIONS
 FOR EQUIPMENT.
  