| 2006-02-15 00:00:00 | DENIED: |
| | 1.PLAN SHEET A0.1 BUILDING CODE REVIEW |
| | INDICATES THE 2001 FLORIDA BUILDING |
| | CODE.AS OF OCTOBER 1, 2005 THE 2004 |
| | FLORIDA BUILDING CODE WENT INTO EFFECT. |
| | |
| | |
| | 2.PLEASE CLARIFY CLEARANCE FOR SERVICE |
| | AND REPLACEMENT OF THE ACWS.PLAN SHEET |
| | M-3 DOES NOT APPEAR TO GIVE ANY |
| | CLEARANCE.SHOW COMPLIANCE WITH 2004 |
| | 306.1. |
| | |
| | 3.PLEASE INDICATE DUCT SMOKE DETECTORS |
| | ON PLAN IN ACCORDANCE WITH 2004 FMC |
| | 606.2.1 |
| | |
| | 4.PLAN SHEET M-4 ROOF TOP DETAIL, |
| | PLEASE INDICATE TERMINATION OF |
| | CONDENSATE.PLEASE NOTE, PVC INSTALLED |
| | ON THE ROOF SHALL HAVE PROTECTION FROM |
| | UV RAYS.PROVIDE INFORMATION HOW THIS |
| | WILL BE ACCOMPLISHED. |
| | |
| | 5.PROVIDE DETAIL OF THE SUPPORT FOR |
| | THE CONDENSATE LINE. |
| | |
| | 6.PLAN SHEET M-4 PROVIDES SUPPORT |
| | DETAIL FOR THE RTU.PLEASE INDICATE |
| | SUPPORT DETAIL FOR THE CHILLER ALSO. |
| | PLEASE EQUIPMENT & SUPPORTS EXPOSED TO |
| | THE WIND SHALL BE DESIGNED & INSTALLED |
| | FOR TO RESIST WIND PRESSURES ON THE |
| | EQUIPMENT & SUPPORTS AS DETERMINED IN |
| | CHAPTER 16 OF THE 2004 FBC. |
| | |
| | PLEASE PROVIDE INSTALLATION INSTRUCTIONS |
| | FOR EQUIPMENT. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |
| | |