Plan Review Notes
Plan Review Notes For Permit 05121076
Permit Number 05121076
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-02-08 00:00:00******DENIED******
  
 1) SHT A0.2 ILLUSTRATES (2) SETS OF
 DOORS THAT ARE OPPOSING TO EACH OTHER.
 DOORS SHALL SWING IN DIRECTION OF TRAVEL
 WHERE SERVING OCCUPANT LOAD GREATER THAN
 50.
  
 2) REQUIRED BUILDING FIRE PROTECTION
 SYSTEMS AND MEANS OF EGRESS NOT
 IMMEDIATELY EFFECTED BY THIS WORK TO BE
 MAINTAINED DURING THIS PROJECT.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 4) WILL THE NEW LOCK AND CARD READER
 ACCESS SYSTEM IMPACT THE MEANS OF
 EGRESS?
  
 5) DUCT SMOKE DETECTORS SHALL BE
 INSTALLED IN AIR SUPPLY SYSTEM, AND
 INITIATE A GENERAL FIRE ALARM WHEN
 ACTIVATED IN ACCORDANCE WITH LOCAL
 REQUIREMENT.
  
 6) DRAWING INDEX INDICATES A FIRE
 PROTECTION SHEET THAT APPEARS TO HAVE
 BEEN REMOVED PRIOR TO THIS REVIEW.
  
 7) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 8) PLEASE SEE APPLICABLE CODE REVIEW.
 NFPA 101, 2003 EDITION SHALL BE
 REFERENCED.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722