Plan Review Notes
Plan Review Notes For Permit 05121076
Permit Number 05121076
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-08 00:00:00IN ELEC FOR REVIEW.
 ******** UNSAT ********
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 AS REQUIRED FOR TITLE BLOCKS FOR
 ARCHITECTUAL FIRM. PLEASE SEE MISSING
 PRINTED NAME AND LICENSE # FOR SAID
 ARCHITECT. PLEASE SEE MISSING
 CERITFICATE OF AUTHORIZATION NUMBER.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.001, ABD FLORIDA STATUES 481.219
 * PLEASE KNOW THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S)>
 PLEASE SEE THIS COMMENT IS FOR
 ARCHITECTUAL FIRM AS ENGINEER FIRM SHOWS
 INFORMATION AS NEEDED, HOWEVER TITLE
 BLOCK FOR ARCH FIRM ARE LOCATED ON
 ENGINEERED PLANS.
  
 2)NOTE: PLEASE BE SURE PLANS AND DESIGN
 REFLECT CURRENT CODES IN EFFECT. PLEASE
 SEE AS OF OCT 1ST,2005, THE CODE HAS
 CHANGED TO THE 2004 FLORIDA BLDG CODE.
 PLEASE ALSO ADJUST OTHER CODES
 ACCORDINGLY.
 PLEASE SEE A0.1 WHICH MENTIONS A 2001
 NEC? PLEASE KNOW THE NFPA-70 (NEC) WENT
 FROM THE 1999 TO 2002 ON JULY 1ST,2003.
 THE 2002 NFPA-70 IS CURRENTLY THE CODE
 IN EFFECT. PLEASE ALSO MAKE REFERENCE TO
 THE CURRENT 2003 NFPA-101,2002 NFPA-72.
  
 3)NOTE: PLEASE PROVIDE A COMMON
 GROUNDING RISER FOR SYSTEMS PROPOSED.
 PLEASE SEE 250.30,250.58. PLEASE SHOW A
 ONE-LINE DIAGRAM FOR THE SYSTEMA DN THE
 ATTACHMENT POINTS.
 ** PLEASE ALSO VERIFY/NOTE THE LOCATION
 IN WHICH THE SEPARATELY DERIVED SYSTEM
 SHALL BE BONDED. (FIRST MEANS OF
 DISCONNECT)? 250.24, 250.66
  
 4)NOTE: PLEASE SEE 225.31- 225.39 FOR
 THE MEANS OF DISCONNECT REQUIRED AT THE
 BLDG AS THE SERVICE MEANS OF DISCONNECT
 IS BEING SHOWN "DETACHED " FROM THE
 BLDG. PLEASE ALSO SEE 230.70 ETC FOR
 SERVICE MEANS OF DISCONNECT AND
 LOCATION.
  
 5)NOTE: PLEASE SEE DETAIL NOTE MENTIONS
 TO MOUNT THE SERVICE MEANS OF DISCONNECT
 ON FENCE AND TO SEE DETAIL ON 2.1.
 PLEASE KNOW, A FENCE DETAIL FOR TYPE AND
 CONTRUCTION COULD NOT BE LOCATED ON 2.1.
 THIS MUST BE A STRUCTUALLY SOUND AND
 SUPPORTIVE TYPE OF INSTALLATION.
 215.5
  
 6)NOTE: PLEASE SEE 250.32 FOR GROUNDING
 ELECTRODE SYSTEM TO BE LOCATED AT THE
 DETACHED BLDG AS SERVICE IS NOT ON OR
 LOCATED AT THE MAIN BLDG.
  
 7)NOTE: PLEASE SEE MAX OCP FOR
 TRANSFORMER TO BE 125% OR PERMITTED TO
 PROCEED TO THE STANDARD OF OCP.
 PLEASE SEE 450.3,240.6
  
 8)NOTE: PLEASE SEE A "POWER CONDITIONER"
 IS SHOWN ON RISER BEING FED FROM MDP,
 HOWEVER THIS COULD NOT BE LCATED ON SAID
 PANEL SCHEDULE?
 215.5
  
 9)NOTE: PLEASE SEE MISSING PANEL(S) L1
 AND N SCHEDULES?
 215.5
  
 10)NOTE: PLEASE SEE ALL CONTINUOUS LOADS
 SHALL BE SHOWN AND BASED ON 125%.
 215.3,2230.42 ETC .
  
 11)NOTE: PLEASE PORVIDE AN EMERGENCY
 BATTERY BACK UP TYPE OF LT FIXTURE IN
 ELECTRICAL ROOM.
 700.16,LS101 7.8,7.9
  
 12)NOTE: PLEASE SHOW ALL CONDUCTOR SIZES
 ON PANEL SCHEDULES FOR ALL BRANCH
 CIRCUITS.
 215.5,240.4,310.16
  
 13)NOTE: PLEASE PROVIDE GROUNDING DETAIL
 FOR PHONE SYSTEMS. INSTALLATION ENTERING
 THE BLDG.
 800.11,800.33,40,44 ETC.
  
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECRTRICAL PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT "NEW REVISED" SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE ONLY SUBMIT ONE COPY OF
 THE OLD/VOIDED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFOMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]