| 2006-02-08 00:00:00 | IN ELEC FOR REVIEW. |
| | ******** UNSAT ******** |
| | |
| | 1)NOTE: PLEASE SEE MISSING INFORMATION |
| | AS REQUIRED FOR TITLE BLOCKS FOR |
| | ARCHITECTUAL FIRM. PLEASE SEE MISSING |
| | PRINTED NAME AND LICENSE # FOR SAID |
| | ARCHITECT. PLEASE SEE MISSING |
| | CERITFICATE OF AUTHORIZATION NUMBER. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G1-16.001, ABD FLORIDA STATUES 481.219 |
| | * PLEASE KNOW THIS IS REQUIRED ON ALL |
| | SHEETS AND FOR ALL TRADES WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S)> |
| | PLEASE SEE THIS COMMENT IS FOR |
| | ARCHITECTUAL FIRM AS ENGINEER FIRM SHOWS |
| | INFORMATION AS NEEDED, HOWEVER TITLE |
| | BLOCK FOR ARCH FIRM ARE LOCATED ON |
| | ENGINEERED PLANS. |
| | |
| | 2)NOTE: PLEASE BE SURE PLANS AND DESIGN |
| | REFLECT CURRENT CODES IN EFFECT. PLEASE |
| | SEE AS OF OCT 1ST,2005, THE CODE HAS |
| | CHANGED TO THE 2004 FLORIDA BLDG CODE. |
| | PLEASE ALSO ADJUST OTHER CODES |
| | ACCORDINGLY. |
| | PLEASE SEE A0.1 WHICH MENTIONS A 2001 |
| | NEC? PLEASE KNOW THE NFPA-70 (NEC) WENT |
| | FROM THE 1999 TO 2002 ON JULY 1ST,2003. |
| | THE 2002 NFPA-70 IS CURRENTLY THE CODE |
| | IN EFFECT. PLEASE ALSO MAKE REFERENCE TO |
| | THE CURRENT 2003 NFPA-101,2002 NFPA-72. |
| | |
| | 3)NOTE: PLEASE PROVIDE A COMMON |
| | GROUNDING RISER FOR SYSTEMS PROPOSED. |
| | PLEASE SEE 250.30,250.58. PLEASE SHOW A |
| | ONE-LINE DIAGRAM FOR THE SYSTEMA DN THE |
| | ATTACHMENT POINTS. |
| | ** PLEASE ALSO VERIFY/NOTE THE LOCATION |
| | IN WHICH THE SEPARATELY DERIVED SYSTEM |
| | SHALL BE BONDED. (FIRST MEANS OF |
| | DISCONNECT)? 250.24, 250.66 |
| | |
| | 4)NOTE: PLEASE SEE 225.31- 225.39 FOR |
| | THE MEANS OF DISCONNECT REQUIRED AT THE |
| | BLDG AS THE SERVICE MEANS OF DISCONNECT |
| | IS BEING SHOWN "DETACHED " FROM THE |
| | BLDG. PLEASE ALSO SEE 230.70 ETC FOR |
| | SERVICE MEANS OF DISCONNECT AND |
| | LOCATION. |
| | |
| | 5)NOTE: PLEASE SEE DETAIL NOTE MENTIONS |
| | TO MOUNT THE SERVICE MEANS OF DISCONNECT |
| | ON FENCE AND TO SEE DETAIL ON 2.1. |
| | PLEASE KNOW, A FENCE DETAIL FOR TYPE AND |
| | CONTRUCTION COULD NOT BE LOCATED ON 2.1. |
| | THIS MUST BE A STRUCTUALLY SOUND AND |
| | SUPPORTIVE TYPE OF INSTALLATION. |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE SEE 250.32 FOR GROUNDING |
| | ELECTRODE SYSTEM TO BE LOCATED AT THE |
| | DETACHED BLDG AS SERVICE IS NOT ON OR |
| | LOCATED AT THE MAIN BLDG. |
| | |
| | 7)NOTE: PLEASE SEE MAX OCP FOR |
| | TRANSFORMER TO BE 125% OR PERMITTED TO |
| | PROCEED TO THE STANDARD OF OCP. |
| | PLEASE SEE 450.3,240.6 |
| | |
| | 8)NOTE: PLEASE SEE A "POWER CONDITIONER" |
| | IS SHOWN ON RISER BEING FED FROM MDP, |
| | HOWEVER THIS COULD NOT BE LCATED ON SAID |
| | PANEL SCHEDULE? |
| | 215.5 |
| | |
| | 9)NOTE: PLEASE SEE MISSING PANEL(S) L1 |
| | AND N SCHEDULES? |
| | 215.5 |
| | |
| | 10)NOTE: PLEASE SEE ALL CONTINUOUS LOADS |
| | SHALL BE SHOWN AND BASED ON 125%. |
| | 215.3,2230.42 ETC . |
| | |
| | 11)NOTE: PLEASE PORVIDE AN EMERGENCY |
| | BATTERY BACK UP TYPE OF LT FIXTURE IN |
| | ELECTRICAL ROOM. |
| | 700.16,LS101 7.8,7.9 |
| | |
| | 12)NOTE: PLEASE SHOW ALL CONDUCTOR SIZES |
| | ON PANEL SCHEDULES FOR ALL BRANCH |
| | CIRCUITS. |
| | 215.5,240.4,310.16 |
| | |
| | 13)NOTE: PLEASE PROVIDE GROUNDING DETAIL |
| | FOR PHONE SYSTEMS. INSTALLATION ENTERING |
| | THE BLDG. |
| | 800.11,800.33,40,44 ETC. |
| | |
| | |
| | ** PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECRTRICAL PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT "NEW REVISED" SHEETS |
| | INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. PLEASE ONLY SUBMIT ONE COPY OF |
| | THE OLD/VOIDED SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFOMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |