| Date |
Text |
| 2005-12-30 00:00:00 | ******** UNSAT ********** |
| | |
| | |
| | 1)NOTE: PLEASE KNOW, THE RESERCH FOR THE |
| | MENTIONED ADDRESS HAS SHOWN REAR |
| | BUILDING BUILT AS A GARAGE AND A |
| | PRELIMINARY SERCH DOES NOT INDICATE A |
| | LEGAL CONVERSION. PLEASE CONTACT APRIL |
| | PICCIRILLO (805-6658) FOR A RESERCH |
| | REQUEST TO FIND OF ANY PERMITS HAVE BEEN |
| | PULLED FOR THE CONVERSION FROM A GARAGE |
| | TO A GUESTHOUSE/COTTAGE FROM 1962 TO THE |
| | PRESENT. |
| | PLEASE ALSO CONTACT ZONING TO FIND OUT |
| | OF UNIT IN REAR WOULD BE LEGAL. |
| | |
| | PLEASE KNOW THE ELECTRICAL PERMIT TO BE |
| | REVIEWED AND CLEARED ONCE THIS IS DONE. |
| | ** PLEASE SEE MINOR ELECTRICAL COMMENTS |
| | WHICH CAN BE REDLINED IF ZONING IS OK. |
| | |
| | 1)>GROUNDING ELECTRODE SYSTEM AT THE |
| | DEATCHED BLDG. 250.32 |
| | 2)>ARC FAULT FOR BED RM AREA IN |
| | COTTAGE(IF PERMITTED).210.12 |
| | 3)> INDICATE THE MEANS OF DISCONNECT AT |
| | THE DETACHED BLDG. 225.31 |
| | 4)> SIZE OF PANEL AT DETACHED BLDG.(OCP |
| | SHOWS 60A FEED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE.\ |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |