| Plan Review Notes For Permit 05121022 |
| Permit Number |
05121022 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-02 00:00:00 | DENIED; | | | 1.WASHING MACHINE WASTE CONNECTION TO BE | | | 3"FBC-2004 SEC. 406.3. A SANIARY CROSS | | | CAN NOT BE USED. 3"X2" Y FITTING MUST BE | | | USED SEC. 706.3 (EXCEPTION) CLEANOUT AT | | | 48"AFF IS ALSO REQUIRED. | | | 2.SHOW LOCATION OF VENT FOR FLOOR DRAIN | | | AND TRAP PRIMER AND TYPE OF PRIMMER TO | | | BE USED. | | | 3.WATER HEATER DETAIL, SHOW MEANS OF | | | CONTROLING THERMAL EXPANTION. SEC. | | | 607.3. | | | 4.WATER HAMMER ARRESTORS REQUIRED ON | | | WATER PIPES AT WASHER HOOK UP. SEC 604.9 | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|