| 2006-01-24 00:00:00 | *** UNSAT *** |
| | |
| | 1)NOTE: PLEASE SEE PANEL IS BEING SHOWN |
| | AS EXISTING, HOWEVER PLEASE INDICATE IF |
| | THE EXISTING FEEDERS. THIS CAN BE NOTED. |
| | PLEASE ALSO INDICATE OF PANEL CONTAINS A |
| | MEANS OF DISCONNECT, MCB ?SINCE THIS |
| | SEEMS TO BE SHOWN AS A DETACHED BLDG. |
| | PLEASE ALSO INDICATE GROUNDING ELECTRODE |
| | , NEW OR EXISTING FOR THIS PANEL AT |
| | DETACHED BLDG. |
| | ALL PER 240.4,310.16,225.31,250.32 ETC. |
| | |
| | 2)NOTE: PLEASE SHOW CIRCUITING ON PLANS |
| | AND CORRELATE WITH THE PANEL SCHEDULE |
| | SUBMITTED. |
| | 215.5 |
| | PLEASE BE SURE TO INDICATE THE EM LT |
| | CIRCUITED TO THE SAME CIRCUIT FEEDING |
| | THE LOCAL LIGHTING BRANCH CIRCUIT. |
| | 700.12E. |
| | |
| | 3)NOTE: PLEASE SEE MIN OCP FOR WATER |
| | HEATER SHALL BE SIZED A MIN OF 125%. |
| | 422.13 |
| | |
| | 4)NOTE: PLEASE SEE WALL A/C UNIT ON |
| | PANEL SCHEDULE WHICH INDICATES A 5KW |
| | UNIT ON A 1-POLE 20A BRKR? PLEASE |
| | CORRELATE WITH LOAD CALCUALTIONS, AS |
| | LOAD CALCS INDICATE THE LOAD AS 1.5KW? |
| | 215.5 |
| | |
| | PLEASE SEE OTHER POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |