| Plan Review Notes For Permit 05121002 |
| Permit Number |
05121002 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-06-27 00:00:00 | ******* UNSAT********* | | | | | | 1) NOTE: PLEASE CORRELATE ELECTRICAL | | | PLANS WITH BUILDING REFLECTED CEILING | | | PLANS. | | | PLEASE SEE EM LTS,,,, | | | PLEASE SEE JOB BOXES SHOWN FOR FANS. | | | | | | 2) NOTE: PLEASE SEE MISSING MIN EGRESS | | | LIGHTING. PLEASE SEE NOW LOCATIONS WHICH | | | REQUIRE A LT FIXTURE OF SOME SORT FOR | | | EGRESS IS ONLY SHOWING "J" BOX.?? | | | PLEASE SEE LS101 7.8, 7.9, 2003 | | | PLEASE SEE BATH RM SHOWS THE NEW GFI, | | | ONLY NO NEW OR EXISTING LTS ARE SHOWN? | | | CONTROL? | | | | | | | | | 3) NOTE: PLEASE SEE AHU HEAT IS SHOWN AS | | | 5.5KW AND YET THE OCP SEEMS HIGH AT 60A. | | | IS THIS 5.5KW PER PHASE? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|