Plan Review Notes
Plan Review Notes For Permit 05121002
Permit Number 05121002
Review Stop E
Sequence Number 3
Notes
Date Text
2006-06-27 00:00:00******* UNSAT*********
  
 1) NOTE: PLEASE CORRELATE ELECTRICAL
 PLANS WITH BUILDING REFLECTED CEILING
 PLANS.
 PLEASE SEE EM LTS,,,,
 PLEASE SEE JOB BOXES SHOWN FOR FANS.
  
 2) NOTE: PLEASE SEE MISSING MIN EGRESS
 LIGHTING. PLEASE SEE NOW LOCATIONS WHICH
 REQUIRE A LT FIXTURE OF SOME SORT FOR
 EGRESS IS ONLY SHOWING "J" BOX.??
 PLEASE SEE LS101 7.8, 7.9, 2003
 PLEASE SEE BATH RM SHOWS THE NEW GFI,
 ONLY NO NEW OR EXISTING LTS ARE SHOWN?
 CONTROL?
  
  
 3) NOTE: PLEASE SEE AHU HEAT IS SHOWN AS
 5.5KW AND YET THE OCP SEEMS HIGH AT 60A.
 IS THIS 5.5KW PER PHASE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  