| 2006-06-18 00:00:00 | IN ELEC FOR REVIEW, REVIEW IN PROGRESS. |
| | ***** UNSAT 2ND REVIEW **** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW DUE TO MANY ITEMS ON |
| | PLANS BEING COMPLETELY REVISED. |
| | |
| | ** PLEASE SEE THAT AN ADDRESS WAS |
| | ASSIGNED FOR PROJECT AND SHOULD BE |
| | REFLECTED IN TITLE BLOCKS OF ALL SHEETS. |
| | (1621 WORTHINGTON RD.) |
| | |
| | 1) NOTE: PLEASE SUBMIT ALL MANUFACTURE'S |
| | CUT/SPEC SHEETS FOR THE FOLLOWING. |
| | FUEL TANK, WP ENCLOSURE FOR GEN. |
| | THE GEN AND ATS SPCES WERE SUBMITTED AND |
| | ARE OK. |
| | PLEASE HOWEVER "HIGHLIGHT" THE GEN AS |
| | INDICATED ON PLANS ON THE SPEC SHEETS. |
| | |
| | ** ON PREVIOUS REVIEW** |
| | |
| | 2) NOTE: PLEASE SUBMIT PHOTO-METRICS |
| | UNDER NORMAL AND EM CONDITIONS FOR ALL |
| | EGRESS AREAS. THE NORMAL WERE SUBMITTED, |
| | HOWEVER COULD NOT LOCATE EM LEVELS. |
| | MIN 1FT CANDLE. NFPA -101 7.8.1.3 , |
| | 7.9.2.2. |
| | |
| | ** PREVIOUS REVIEW** |
| | |
| | 3) NOTE: PLEASE SEE FXTURE TYPES ON E0.1 |
| | DO NOT CORRELATE WIHT MANY FIXTURES IN |
| | GARAGE AND STAIRS. |
| | STILL NEED TO VERIFY TYPE OF FIXTURE FOR |
| | STAIRS. |
| | 215.5 |
| | |
| | 4) NOTE: PLEASE INDICATE THE OCP ON THE |
| | GENERATOR FOR EACH BREAKER THAT IS BEING |
| | INDICATED ON RISER. |
| | PLEASE INDICATE THE INTENDED LOAD(S). |
| | (IT IS NOTED THAT THE LOAD ON GGDP IS |
| | BEING SHOWN, HOWEVER RISER ALSO SHOWS |
| | GEN FEEDING OTHER LOADS? |
| | 215.5,220,702.5 ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | |
| | 5) NOTE: PLEASE SEE CALCULATIONS FOR FBC |
| | CHAPTER 13 ARE NEEDED PER 13-415.1.AB.1, |
| | 13-415.2.ABC.1. |
| | PLEASE PROVIDE WITH ENERGY CALCS. |
| | PLEASE SEE ENGERY CALCSMUST BE SIGNED, |
| | DATED AND SEALED BY THE RESPONSIBLE |
| | DESIGNER OF RECORD. |
| | PLEASE SEE CALCS SUBMITTED FOR GYM SPACE |
| | WERE NOT SIGNED/SEALED. |
| | ** PLEASE SEE NEW "ST" DEVICES LOCATED |
| | IN ROOMS DO NOT INDICATE THE MAX TIMED |
| | FOR "ON". |
| | PLEASE SEE THIS CAN/SHOULD ALSO BE |
| | LOCATED ON ELECTRICAL LEGEND. |
| | |
| | ** PREVIOUS NOTES** |
| | |
| | 6) NOTE: PLEASE SEE LOADS WERE SHOWN AS |
| | "BLANK" ON PREVIOUS PLANS. PLEASE SEE |
| | LOADS ARE NOW SHOWN, HOWEVER CONTINUOUS |
| | LOADS WHICH ARE REQUIRED TO BE SHOWN |
| | @125% DO NOT INDICATE THIS? |
| | PLEASE ALSO SEE ANY LARGEST MOTORS SHALL |
| | ALSO INDICATE 125%. |
| | PLEASE CLARIFY LOADS WHICH ARE BEING |
| | SHOWN ON "GMDP" FOR "GLH/GL1" AS BOTH |
| | PANELS ARE SHOWN WITHOUT ANY LOADS. |
| | WHERE IS THE 20KV COMING FROM? |
| | 215.5, 230.42,215.3 220 |
| | |
| | 7) NOTE: PLEASE SEE "GGDP" SHALL |
| | INDICATE A SIGN AS EM MAIN. |
| | PLEASE SEE 702.7 FOR SIGNALS REQUIRED. |
| | 702.8,701.8,701.9, 230.2E |
| | |
| | ** FOLLOW NOTES DO NOT APPLY TO KAMM |
| | CONSULTING ENG'S. |
| | |
| | 8) NOTE: PLEASE SEE "S" SHEETS ARE BIENG |
| | SEAL WHICH IS NO LONGER ACCEPTABLE UNDER |
| | FAC 61G15-23.001. |
| | PLEASE KNOW, IN FEB 04, A RULING BY THE |
| | FLORIDA BOARD OF PROFESSIONAL ENGINEER'S |
| | FOR A CHANGE IN THE WORDING IN THE SEAL. |
| | PLEASE KNOW, THE WORDING OF |
| | "CERTIFICATE" COULD NO LONGER BE USED |
| | AND THE NEW WORDING OF "LICENSE" WAS |
| | REQUIRED IN SAID SEAL. |
| | PLEASE KNOW THAT AN EXTENSION WAS |
| | GRANTED TODEC 31ST, 2005 , HOWEVER ALL |
| | PLANS AFTER SUCH DATE SHALL CONTAIN THE |
| | NEW SEAL WITH THE WORDING OF "LICENSE". |
| | THIS MAY ALSO BE IN BUILDING REVIEW |
| | COMMENTS. |
| | |
| | 9) NOTE: PLEASE SEE LANDSCAPE PLANS ARE |
| | STILL INDICATING ELECTRICAL LIGHTING |
| | ETC. |
| | PLEASE KNOW, ALL ELECTRICAL LIGHTING |
| | SHALL BE REMOVED FROM SAID PLANS, OR |
| | REVISE ELECTRICAL PLANS TO INCLUDE |
| | THESE. |
| | PLEASE ALSO SEE FBC CHAPTER 13 FOR |
| | OUTSIDE LANDSCAPE LT-ING. |
| | |
| | 10) NOTE: PLEASE SEE MISSING REQUIRED |
| | INFORMATION IN TITLE BLOCK FOR LANDSCAPE |
| | ARCHITECT AND FIRM. |
| | PLEASE SEE 61G1-16.004, FS 481.219 |
| | MISSING CERTIFICATE OF AUTHORIZATION #. |
| | |
| | 11) NOTE: PLEASE SEE FS 553.80(2)(B) |
| | WITH RESPECT TO ANY REPEAT COMMENTS. |
| | THIS IS ONLY A NOTICE. |
| | |
| | ** PLEASE ONLY SUBMIT ONE COPY OF |
| | OLD/VOIDED SETS FOR REVIEW AND |
| | REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | ** NOTE ADDED TO FRONT SCREEN. |
| | NOTICE OF COMMENCMENT IN PACKAGE HAS |
| | EXPIRED PER FS 713.13(2). |
| | WILL NEED A NEW RE-RECORDED NOC BEFORE |
| | PICKING UP PERMIT. |