| 2006-03-10 00:00:00 | ******DENIED****** |
| | |
| | 1) KNOX BOX LOCKING CAPS ARE REQUIRED |
| | FOR FIRE DEPARTMENT CONNECTION. |
| | |
| | 2) FIRE DEPARTMENT CONNECTION TO BE |
| | LOCATED NO FURTHER THAN 150' FROM A FIRE |
| | HYDRANT. |
| | |
| | 3) SEPARATE SHOP DRAWINGS AND PERMITS |
| | REQUIRED FOR FIRE SPRINKLER AND FIRE |
| | ALARM SYSTEMS. |
| | |
| | 4) 2A-10B,C RATED FIRE EXTINGUISHERS TO |
| | BE MOUNTED AT DISTANCE NOT TO EXCEED |
| | 75'. |
| | |
| | 5) PARKING GARAGE TO COMPLY WITH |
| | APPLICABLE BUILDING CODES AND NFPA 88A. |
| | |
| | 6) WILL PROPOSED TENANT SPACE MEET |
| | SEPARATION REQUIREMENTS? |
| | |
| | 7) PLEASE PROVIDE CLARIFICATION ON HOW |
| | AND WHERE PERSONS WILL BE EXITING THE |
| | BUILDING. |
| | |
| | 8) THE STAIRWELL DOOR SWINGS ON UPPER |
| | FLOORS APPEAR TO SWING AGAINST DIRECTION |
| | OF TRAVEL. |
| | |
| | 9) PANIC DOORS ARE MENTIONED ON SHT |
| | A-400, HOWEVER THIS IS NOT ILLUSTRATED |
| | IN THE DOOR SCHEDULE. |
| | |
| | 10) THE COOLING TOWER TO COMPLY WITH |
| | NFPA 214. |
| | |
| | 11) FIRE ALARM SYSTEM SHALL BE UL LISTED |
| | FOR CENTRAL STATION SERVICE. |
| | |
| | 12) NO FIRE SPRINKLER LAY OUT HAS BEEN |
| | SUBMITTED WITH DRAWINGS. |
| | |
| | 13) DUCT SMOKE DETECTOR SHALL INITIATE A |
| | GENERAL FIRE ALARM IN ACCORDANCE WITH |
| | LOCAL REQUIREMENTS. |
| | |
| | 14) ARE SMOKE DETECTORS PLANNED FOR |
| | ELEVATOR RECALL? |
| | |
| | 15) IT WOULD APPEAR THAT MORE |
| | AUDIBLE/VISUAL DEVICES ARE NEEDED ON |
| | UPPER FLOORS. |
| | |
| | 16) EXIT LIGHTS TO BE MOUNTED AT |
| | DISTANCES NOT TO EXCEED 100'. |
| | |
| | 17) PLEASE EXPLAIN WHY EXIT SIGNS DIRECT |
| | PERSONS INTO STAIWELLS ON FLOOR #1. |
| | |
| | 18) PLEASE PROVIDE MANUFACTURER SPEC |
| | SHEETS FOR GENERATOR. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLANS REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |