| 2006-02-10 00:00:00 | *** PLEASE SEE NOTES UNDER MAIN BLDG |
| | ALSO FOR ADDRESS. |
| | |
| | PLEASE KNOW, THE LEGAL PROPERTY MAY NOT |
| | CHANGE AS THE ELECTRICAL SERVICEAND |
| | GENERATORS COME FROM GARAGE BLDG TO MAIN |
| | BLDG. |
| | PLEASE SEE ANY LEGAL PROPPERTY PCN |
| | CHNAGE ETC WILL REQUIRE LEGAL EASEMENTS |
| | ETC. |
| 2006-02-01 00:00:00 | ********** UNSAT ********** |
| | |
| | ** PLEASE KNOW, PLANS AND SUBMITTIALS |
| | ARE NOT COMPLETE AT THIS TIME. |
| | |
| | |
| | 1)NOTE: PLEASE SEE ALL CURRENT CODES |
| | SHALL BE REFERENCED TO THE CURRENT CODES |
| | IN EFFECT. PLEASE SEE PLANS CALL FOR |
| | 2001 FLORIDA BUILDING CODE. PLEASE KNOW, |
| | AS OF OCT 1ST, 2005 THE NEW FBC IS THE |
| | 2004 EDITION. PLEASE SEE THE FOLLOWING |
| | SHALL BE REFERENCED. 2003 NFPA-101, 2002 |
| | NFPA-70, AND 2002 NFPA-72 |
| | |
| | 2)NOTE: PLANS WILL REQUIRED BATTERY BACK |
| | UP LT FIXTURES IN MAIN ELECTRICAL RM, |
| | ELEVATOR RMS. |
| | PLEASE ALSO KNOW BATTERY BACK UP |
| | FIXTURES WILL BE REQUIRED IN STAIRWAY |
| | AND EGRESS PATHS TO PROVIDE A MIN OF 1FT |
| | CANDLE OF LIGHT BY SOME SORT OF BATTEY |
| | BACK UP FIXTURE. PLEASE SEE NFPA-101 |
| | 7.9.2.2, TRIPPING OR SHUTTING OFF ANY |
| | SINGLE DEVICE OR MEANS OF OVERCURRENT |
| | PROTECTION SHALL NOT LEAVE ANY ONE |
| | EGRESS PATH IN TOTAL DARKNESS. |
| | PLEASE PROVIDE PHOTOMETRICS FOR |
| | STAIRWAYS, AS THE 2003 LS 101 7.8.1.3 |
| | REQUIRES A MIN OF 10FY CANDLES(108LUX) |
| | IN STAIRWAYS UNDER NORMAL LIGHTING |
| | CONDITIONS AND 7.9.2.2 PERMITS THE |
| | DERATING TO A MIN OF 1FT CANDLE UNDER |
| | EMERGENCY CONDITIONS. |
| | 700.16.,700.12E ETC |
| | |
| | 3)NOTE: PLEASE SEE POSSIBLE BLDG |
| | COMMENTS AS STAIRWAY DOORS SEEM TO SWING |
| | IN, INSTEAD OF THE DIRECTION OF EGRESS. |
| | PLEASE SEE ANY POSSIBLE COMMENTS WITH |
| | RESPECT TO THE "FUTURE" TENANT SPACE. |
| | (GYM). |
| | |
| | 4)NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| | SPECS/CUT SHEETS FOR GENERATOR, ATS, |
| | ETC. PLEASE PROVIDE SPECS FOR ANY TANKS |
| | FOR THE PRIME-MOVER OF GEN. |
| | PLEASE BE SURE ALL SPECS ETC INDICATE |
| | LISTINGS FROM A NRTL. |
| | NO REVIEW CAN BE DONE AT THIS TIME. |
| | |
| | 5)NOTE: PLEASE SEE NO MAIN IS SHOWN ON |
| | THE LINE-SIDE OF ATS SHOWN. PLEASE SEE |
| | THE FOLLOWING COMMENT WITH RESPECT TO |
| | GFP FOR SYSTEMS 277/480V 1000A'[S OR |
| | MORE. |
| | 230.70,ETC. |
| | |
| | 6)NOTE: PLEASE SEE ATS MANUFACTUREA S |
| | GFP IS REQUIED BY THE NEC FOR SERVICE |
| | AND MAY REQUIRE A 4-POLE ATS FOR GFP TO |
| | WORK CORRECTLY. |
| | PLEASE PROVIDE INFORMATION; PLEASE SEE |
| | GENERATOR IS ALREADY SHOWN AS A |
| | SEPARATELY DERIVED SYSTEM AS REQUIRED, |
| | HOWEVER NOT ENOUGH ATS INFORMATION IS |
| | SUBMITTED FOR CORRELATION OF REVIEW FOR |
| | CODE COMPLIANCE. |
| | EXAMPLE, PLEASE SEE TEXT TAKEN FROM |
| | ASCO: |
| | "WHERE GROUND FAULTPROTECTION IS |
| | TRIGGERED BY THE CODE AND AN ALTERNATE |
| | POWER SUPPLY IS INCLUDED,SWITCHING OF |
| | THE NEUTRAL BECOMES NECESSARY. THE |
| | CIRCUIT SHOWN ABOVE ILLUSTRATESSUCH A |
| | CIRCUMSTANCE. THE SERVICE IS LARGER THAN |
| | 1,000 AMPS. CONSEQUENTLY, GROUNDFAULT |
| | PROTECTION IS REQUIRED AT THE MAIN |
| | SERVICE DISCONNECT AT A MINIMUM. IF IT |
| | IS INSTALLED THERE AND THE GENERATOR |
| | NEUTRAL GROUNDING WAS THROUGH A SOLID |
| | CONNECTION TO THE MAIN SERVICE NEUTRAL, |
| | A GROUND FAULT WHEN THE GENERATOR IS |
| | FEEDING THE LOAD WILL CAUSE THE MAIN |
| | SERVICE DISCONNECT TO OPEN. THIS WILL |
| | NOTDISCONNECT THE ARCING FAULT FROM |
| | THE GENERATOR. COORDINATION IS THUS |
| | LOST." |
| | |
| | 7)NOTE: PLEASE SEE SERVICE MAINS AS |
| | REQUIRED DO NOT INDICATE ANY GFP PER |
| | 230.95,240.13 ETC. |
| | |
| | 8)NOTE: PLEASE LABEL ALL MAINS, 1, 2, 3 |
| | ETC, 1OF? 2 OF ? ETC. |
| | |
| | 9)NOTE: PLEASE PROVIDE ONE LINE |
| | GROUNDING ELECTRODE DIAGRAM FOR BLDG, TO |
| | INCLUDE GROUNDING ELECTRODE RISER FOR |
| | ANY TRANSFORMERS. 250.30,250.58 |
| | |
| | 10)NOTE: PLEASE SEE PANELS , (MDP WHICH |
| | ARE NOT COMPLETE AT THIS TIME. PLEASE |
| | SEE SOME AREA OF PANELS WHERE XXX'S ARE |
| | SHOWN FOR REQUIRED INFORMATION. |
| | PLEASE SEE "GGP" WHERE BRANCH CIRCUIT |
| | INFORMATION APPEARS IN THE TITLE BLOCK |
| | OF SAID PANEL. |
| | PLEASE SEE OTHER PANELS WHERE ALL |
| | INFORMATION INDICATED IS SHOWN AS |
| | "SPARE"? PLEASE SPECIFY "FUTURE" USE AND |
| | FOR WHAT LOADS THESE WILL FEED. |
| | |
| | 11)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | AND PANELS. |
| | PLEASE SEE "GLH", "GMDP", GLH", ETC, |
| | THESE ARE SHOWN BEING FED FROM OTHER |
| | EQUIPMENT ON RISER THAN LISTED ON PANEL |
| | SCHEDULES. |
| | PLEASE ALSO SEE "GDP", "GGP", AND "GLP", |
| | PLEASE SEE RISER, PLEASE SEE "T1B" AS |
| | THIS IS FED FROM TWO SEPARATE PANELS, |
| | AND CORRELATE WIRTH RISER. |
| | 215.5 |
| | |
| | 12)NOTE: PLEASE SEE NOTES FOR |
| | DISTRIBUTION SYSTEM MENTIONS TO EXTEND |
| | TO MAIN BLDG, PLEASE SEE NOTES FROM MAIN |
| | BLDG REVIEW WHEN COMPLETED AS THIS MAY |
| | AFFECT ELECTRICAL SERVICE OR DESIGN AS |
| | SHOWN. |
| | |
| | 13)NOTE: PLEASE COMPLETE ALL SERVICE |
| | ENTRANCE CONDUCTORS ON RISER ALONG WITH |
| | ALL FEEDERS. |
| | PLEASE SEE MISSING SEC'S TO EM SYSTEM, |
| | ATS OR NEW MAIN DISCONNECT, PLEASE SEE |
| | MISSING FEEDERS FROPM GEN, PLEASE SEE |
| | MISSING SEC'S TO GMDP, ATS TO GDP ETC . |
| | PLEASE COMPLETE RISER. |
| | |
| | 14)NOTE: PLEASE SEE MISSING OVERCURRENT |
| | PROTECTION AT GENERATOR. PLEASE ALSO SEE |
| | MISSING LOAD CALCUALTIONS FOR INTENDED |
| | LOAD FOR GENERATOR. |
| | PLEASE ALSO SEE FOLLOWING COMMENT. |
| | |
| | 15)NOTE: PLEASE COMPLETE AND SUBMIT MIN |
| | LOAD CALCUALTIONS AS REQUIRED PER |
| | NEC.220 |
| | PLEASE SEE ALL MAIN DISTRIBUTIION |
| | SYSTEMS ARE SHOWING "BLANKS" FOR LOADS?? |
| | PLEASE BE SURE TO INDICATE ALL LOADS. NO |
| | REVIEW OF THESE CAN BE DOINE AT THIS |
| | TIME. |
| | 215.5 |
| | |
| | 16)NOTE: PLEASE SEE NOTES FOR GENERATORS |
| | AS INDICATED ON ELECTRICAL PLANS WHICH |
| | NOTES ALL GENERATOR CONDUITS PROCEEDING |
| | TO THE MAIN OFFICE BLDG?? |
| | PLEASE INDICATE WHERE GENFOR GARAGE IS |
| | LOCATED? |
| | PLEASE ALSO SEE COMMENTS FOR MAIN BLDG |
| | AS THESE NOTES INDICATE ALL THESE |
| | FEEDERS SHALL PROCEED TO THE FIRST FLR |
| | MAIN ELECTRICAL ROOM, HOWEVER THIS DOES |
| | NOT SEEM TO CORRELATE WITH WHAT IS SHOWN |
| | ON MAIN BLDG PLANS. |
| | 215.5 |
| | |
| | 17)NOTE: PLEASE SEE FBC 2004 CHAPTER 13, |
| | 13-413.1ABC.1.1, .2 FOR VOLTAGE DROP |
| | INFORMATION NEEDED. |
| | |
| | 18)NOTE: PELASE SEE LIGHTING |
| | REQUIREMENTS UNDER 13-415 FOR AREAS OF |
| | CONTROL AND TANDEM WIRING. |
| | PLEASE SPECIFY THIS INFORMATION ON |
| | PLANS. |
| | |
| | 19)NOTE: PLEASE SEE LANDSCAPE PLANS |
| | MENTIONS AND NOTES LIGHTING AND TO SEE |
| | ELECTRICAL PLANS FOR THESE, HOWEVER |
| | THESE ITEMS COULD NOT BE LOCATED ON |
| | ELECTRICAL PLANS. |
| | PLEASE SUBMIT WIND LOAD CALCUALTIONS FOR |
| | ALL SITE LIGHTING POLES TO MEET FBC 140 |
| | MPH. |
| | |
| | 20)NOTE: PLEASE SEE LANDSCAPE PLANS ARE |
| | SEALED "PHOTO-COPIES" OF ARCHITECT'S |
| | SIGNATURE. PLEASE SEE FS 481.221 WHICH |
| | REQUIRES THE SIGNATURE TO BE AN ORIGINAL |
| | SIGNATURE. |
| | |
| | ** PLEASE KNOW, REVIEW FOR MAIN BLDG HAS |
| | NOT COMMENCED AT THIS TIME. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ON.Y INSERT NEW REVISED SHEETS INTO |
| | COMPLETED SETS FOR REVIEW AND STAMPING. |
| | ONLY SUBMIT ONE COPY OF OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |