| 2006-04-17 00:00:00 | DENIED BY BUILDING |
| | |
| | 1621 WORTHINGTON ROAD |
| | 5 STORY PARKING GARAGE |
| | TYPE II-A (SPRINKLERED) |
| | MIXED OCCUPANCY (S-2 STORAGE & |
| | BUSINESS) NOTE: PLUMBING SHEET P3.4 |
| | INDICATES A FUTURE GYM WHICH WOULD BE AN |
| | ASSEMBLY OCCUPANCY. |
| | FLOOD ZONE A9 BFE 13' (+6"CITY REQ.) |
| | REQUIRED SOIL BEARING PER PLANS 2,000 |
| | PSF |
| | |
| | 1) STRUCTURE IS LOCATED IN AN A9 FLOOD |
| | ZONE AN ELEVTION CERTIFICATE WILL BE |
| | REQUIRED. ALL EQUIPMENT MUST ALSO BE |
| | LOCATED 6" ABOVE REQUIRED BFE. |
| | |
| | 2) SUBMIT A SIGNED AND SEALED SURVEY. |
| | INDICATE THE LOCATION OF THE ASSUMED |
| | PROPERTY LINE BETWEEN THE PROPOSED |
| | PARKING GARAGE AND THE PROPOSED BUILDING |
| | TO THE WEST. SEE FIRE SEPARATION |
| | DISTANCE FBC 702.1 AND 704.3. |
| | |
| | 3) FBC 1802.2.1AREA OF QUESTIONABLE |
| | SOIL.SUBMIT A GEOTECHNICAL REPORT |
| | TO VERIFY THE SAFE BEARING CAPACITY OF |
| | THE SOIL. |
| | |
| | 4)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 5)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 6) SUBMIT FIRE SPRINKLER DRAWINGS AS |
| | REQUIRED BY FBC 106.3.5. |
| | |
| | 7) FBC 13-103.0ENERGY CODE COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE CODE COMPLIANCE FORMS. |
| | FBC 13-101.1.6SHELL BUILDINGS. |
| | THE WHOLE BUILDING (INCL. FUTURE TENANT |
| | SPACE) SHALL BE CONSIDERED.SHELL |
| | BUILDINGS SHALL BE SHOWN TO COMPLY WITH |
| | METHOD B (SEE SUB-CHAPTER 4).ALL |
| | ASSUMPTIONS MADE ABOUT SYSTEMS, NOT |
| | SHOWN ON THE CURRENT PLANS, SHALL BE |
| | LISTED AND APPENDED TO THE FORM 400B FOR |
| | SUBMITTAL.THIS WILL BE COMPARED, AT A |
| | LATER DATE, TO THE ACTUAL SYSTEMS |
| | PROPOSED BY THE FUTURE TENANT(S).THE |
| | ASSUMPTIONS LISTED ON THE APPENDIX SHEET |
| | SHALL BE AT LEAST THE MINIMUM STANDARD |
| | (LIGHTING, HVAC ETC) TO ALLOW THE WHOLE |
| | BUILDING TO BE OCCUPIED FOR IT'S |
| | INTENDED PURPOSE. |
| | |
| | 8) FBC* 109.3.6.1SPECIAL INSPECTOR.A |
| | STRUCTURAL INSPECTION PLAN MUST BE |
| | SUBMITTED PRIOR TO THE ISSUANCE OF A |
| | BUILDING PERMIT FOR THE CONSTRUCTION OF |
| | A THRESHOLD BUILDING.A THRESHOLD |
| | BUILDING IS ANY BUILDING WHICH IS |
| | GREATER THAN THREE STORIES OR 50 FEET IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY |
| | OCCUPANCY WITH 5,000 SQFT AREA AND |
| | GREATER THAN 500 OCCUPANTS.THREE |
| | COPIES OF THE PLANS AND OTHER DOCUMENTS |
| | WILL BE REQUIRED FOR PERMITTING |
| | PURPOSES. ALSO, PLEASE ARRANGE WITH |
| | HAROLD PISKURA (INSPECTION SERVICES |
| | MANAGER - TEL:561 805 6711), A MEETING |
| | INVOLVING THE OWNER, THRESHOLD |
| | INSPECTOR, JOB INSPECTOR, CONTRACTOR AND |
| | ENGINEER. |
| | |
| | 9)FBC* 109.3.6.4.4 ALL PLANS FOR THE |
| | BUILDING WHICH ARE REQUIRED TO BE SIGNED |
| | AND SEALED BY THE ARCHITECT OR ENGINEER |
| | OF RECORD CON- TAIN A STATEMENT THAT, TO |
| | THE BEST OF THE ARCHITECT'S PR |
| | ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS |
| | DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 10) FBC* 106.1.3 QUALITY OF BUILDING |
| | PLANS. BUILDING PLANS SHALL BE DRAWN TO |
| | A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER |
| | ACCEPTABLE MEDIUM. |
| | |
| | 11) FBC 1603.1.4WIND DESIGN DATA.THE |
| | PLANS SHALL STATE THE BASIC WIND SPEED, |
| | WIND IMPORTANCE FACTOR, WIND EXPOSURE |
| | CATEGORY, INTERNAL PRESSURE COEFFICIENT, |
| | AND EXTERIOR COMPONENT AND CLADDING |
| | DESIGN WIND PRESSURES.ADD THIS |
| | INFORMATION TO THE PLANS. INFORMATION |
| | LEFT BLANK ON SHEET S4.O. |
| | |
| | 12) THE EDITION OF ASCE 7 REFERENCED IN |
| | THE 2004 FBC IS ASCE 7-02. PLEASE REVISE |
| | THE EDITIONS OF ASCE 7 SPECIFIED ON |
| | SHEET S4.0. |
| | |
| | 13) SPECIFY ON THE PLANS IF THE |
| | STRUCTURE IS DESIGNED AS ENCLOSED, |
| | PARTIALLY ENCLOSED OR OPEN. |
| | |
| | 14) SPECIFY THE SCALE OF THE LIFE SAFETY |
| | PLAN FOR THE EQUIPMENT ROOMS ON SHEET |
| | A003. |
| | |
| | 15) SPECIFY THE NEGATIVE AND POSITIVE |
| | WINDLOAD PRESSURES FOR THE STOREFRONTS |
| | AT THE TENNANT SPACE, THE EXTERIOR DOOR |
| | TO THE MECHANICAL ROOMS, AND THE DOORS |
| | TO THE EGRESS STAIRS. FBC 1609 |
| | |
| | 16) NOTE 2 ON S5.0 IS COVERED BY A |
| | PRINTING ERROR. PLEASE CORRECT. |
| | |
| | 17) SUBMIT PRODUCT APPROVALS FOR THE |
| | DOOR AND WINDOW OPENINGS SUBJECT TO |
| | WINDLOADING, ROOFING MATERIALS, STORM |
| | PANELS, ETC. |
| | NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| | EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| | THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| | SITE-SPECIFIC PRODUCT APPROVAL.THE |
| | SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| | PRODUCT APPROVAL NUMBER (FL###), |
| | AVAILABLE FROM THE DEPT OF COMMUNITY |
| | AFFAIRS PRODUCT APPROVAL WEBSITE WWW. |
| | FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX |
| | (IF YOU FIND THAT THE QUOTED WEB PAGE IS |
| | NO LONGER AVAILABLE, PLEASE INFORM THE |
| | PLAN REVIEWER) |
| | FBC 106.3.3*(CITY AMENDMENTS) REQUIRES |
| | PRODUCTS REGULATED BY DCA RULE 9B-72 TO |
| | BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 18) SUBMIT SPECIFICATIONS FOR THE FIRE |
| | RATED DOORS, DOOR CLOSERS, HARDWARE, |
| | ETC. |
| | |
| | 19) PLEASE REVISE OCCUPANCY TYPE FOR |
| | FUTURE GYMNASIUM TO GROUP A (ASSEMBLY, |
| | A-3). REVISE OCCUPANT LOAD CALCS., |
| | TENANT SEPARATION, ETC. ACCORDINGLY. THE |
| | PARKING AREA AND STORAGE AREA ARE GROUP |
| | S-2 STORAGE. |
| | |
| | 20) ON SHEET S1.0 SOME OF THE SECTION |
| | MARKERS ARE NOT AT THE PROPER LOCATIONS. |
| | PLEASE CORRECT. |
| | |
| | 21) ON SHEET S2.0 THERE ARE TWO |
| | DIFFERENT SECTION DRAWINGS LABELED |
| | 5/S2.0. SECTION 6/S2.0 SHOULD BE LABELED |
| | AS 7/S2.0. |
| | |
| | 22) PROVIDE A COLUMN SCHEDULE. SEE NOTE |
| | 14 ON S1.0. |
| | |
| | 23) SHEETS S1.1 AND A1.2 HAVE SECTIONS |
| | MARKED X/X. PLEASE CLARIFY. |
| | |
| | 24) MARKS 5/S3.0 ON SHEET S1.1 MARK |
| | 6/S3.0 ON SHEET S1.2 ARE NOT AT THE |
| | CORRECT LOCATIONS. PLEASE CORRECT. |
| | |
| | 25) PLEASE REVISE NOTE 8.06 ON A000 TO |
| | COMPLY WITH THE 2004 FLORIDA BUILDING |
| | CODE. SEE FBC 1609.1.4. |
| | |
| | 26) THE NUMBERS OF PARKING SPACES LISTED |
| | FOR THE FIRST FLOOR ON A002 AND A003 DO |
| | NOT CONCUR. |
| | |
| | 27) THE ELEVATOR SHALL COMPLY WITH FBC |
| | 11-4.10 FOR ACCESSIBILITY AND WITH ASME |
| | A17.1-1990, 'SAFETY CODE FOR ELEVATORS |
| | AND ESCALATORS'. |
| | |
| | 28) FBC 3002.4STRETCHER ACCESSIBLE |
| | ELEVATOR.AT LEAST ONE PASSENGER |
| | ELEVATOR SHALL ACCOMMODATE AN AMBULANCE |
| | STRETCHER 76" LONG AND 24" WIDE IN THE |
| | HORIZONTAL POSITION.THIS ELEVATOR |
| | SHALL BE IDENTIFIED BY SIGNAGE.AMEND |
| | THE PLANS TO DEMONSTRATE COMPLIANCE. |
| | |
| | 29) FBC 11-4.1.2(5)(B) REQUIRES ONE IN |
| | EVERY EIGHT ACCESSIBLE SPACES TO BE VAN |
| | ACCESSIBLE AND BE DESIGNED AS REQUIRED |
| | BY SECTION 11-4.6.3. BASED ON THE NUMBER |
| | OF ACCESSIBLE SPACES, TWO VAN ACCESSIBLE |
| | SPACES ARE REQUIRED. FBC 11-4.6.4 |
| | REQUIRES VAN ACCESSIBLE SIGNAGE. FBC |
| | 11-4.6.5 REQUIRES 98" MINIMUM VERTICAL |
| | CLEARANCE AT THE VAN ACCESSIBLE PARKING |
| | SPACES AND ALONG THE ACCESS ROUTE TO AND |
| | EXITS FROM SUCH SPACES. NO SPRINKLER |
| | PIPING, ROOF DRAIN PIPING, ETC. WITHIN |
| | THE REQUIRED 98" CLEARANCE. SHOW |
| | COMPLIANCE. |
| | |
| | 30)FBC 406.2.2 REQUIRES THE CLEAR HEIGHT |
| | OF EACH FLOOR LEVEL IN VECHICAL AND |
| | PEDESTRIAN TRAFFIC AREAS TO BE NOT LESS |
| | THAN 7 FEET. |
| | |
| | 31) SHOW COMPLIANCE WITH FBC 11-4.6.2 |
| | INDICATE THE ACCESSIBLE ROUTE OF TRAVEL |
| | FROM THE PARKING GARAGE TO THE |
| | ACCESSIBLE ENTRANCE OF THE BUILDING IT |
| | SERVES.ACCESSIBLE PARKING SPACES MUST |
| | BE LOCATED ON AN ACCESSIBLE ROUTE NO |
| | LESS THAN 44" WIDE SO THAT USERS WILL |
| | NOT BE COMPELLED TO WALK OR WHEEL BEHIND |
| | PARKED VECHILES. |
| | |
| | 32) ON SHEET A003 UNDER APPLICABLE |
| | CODES, HIGH VELOCITY HURRICANE ZONES, |
| | CHAPTERS 15 & 16 DO NOT APPLY TO THIS |
| | PROJECT. PLEASE REVISE. CITY OF WEST |
| | PALM BEACH IS NOT LOCATED IN THE HVHZ. |
| | ALSO ON A003 THE SECTION TITLED |
| | HURRICANE CRITERIA CHAPTER 15 & 16 NEEDS |
| | TO BE REVISED. SEE NOTES ON PLANS. |
| | |
| | 33)FBC 11-4.15.2 SPECIFIES THAT |
| | ACCESSIBLE DRINKING FOUNTIANS SHALL BE |
| | NO HIGHER THAN 36" TO THE SPOUT OUTLET. |
| | REVISE DRINKING FOUNTAIN DRAWING ON |
| | A006. |
| | |
| | 34) NOTE 1 ON SHEET A006 FOR FAIR |
| | HOUSING GUIDELINES DOES NOT APPLY TO |
| | THIS PROJECT. THIS PARKING GARAGE IS NOT |
| | ACCESSORY TO A RESIDENTIAL OCCUPANCY. |
| | |
| | 35) THE FIRE RATING OF THE WALLS IS NOT |
| | INDICATED ON THE LIFE SAFETY PLANS, |
| | ALTHOUGH THE LEGEND IS GIVEN ON SHEET |
| | A003. SPECIFY THE FIRE RATINGS OF THE |
| | WALLS AND FLOOR/CEILINGS. |
| | |
| | 36) THE EXIT FROM THE SOUTHEAST EGRESS |
| | STAIR DOES NOT EXIT TO THE EXTERIOR OF |
| | THE BUILDING. FBC 406.2.5 DOES NOT ALLOW |
| | VECHICLE RAMPS TO SERVE AS AN EXIT |
| | ELEMENT. |
| | |
| | 37) PROVIDE A STAIR DETAIL SPECIFYING |
| | THE RISERS, TREADS, VERTICAL RISE |
| | BETWEEN LANDINGS, HEADROOM, HANDRAILS, |
| | GUARDS, STAIR WIDTH, ETC. PLEASE USE A |
| | LARGER SCALE THAN SHOWN ON A2O2 & A203. |
| | SEE FBC 1009. |
| | |
| | 38) NOTE: THE COMMON PATH OF TRAVEL IN |
| | THE FUTURE TENNANT SPACE IS ACCEPTABLE |
| | FOR A BUSSINESS OCCUPANCY, BUT MAY NOT |
| | BE FOR AN ASSEMBLY OCCUPANCY. THE COMMON |
| | PATH OF TRAVEL IS 20' FOR ASSEMBLY WITH |
| | MORE THAN 50 OCCUPANTS. |
| | |
| | 39) FBC 1008.1.2 REQUIRES EGRESS DOORS |
| | TO SWING IN THE DIRRECTION OF TRAVEL |
| | WHERE SERVING AN OCCUPANT LOAD OF 50 OR |
| | MORE PERSONS. EGRESS STAIRS DO NOT |
| | COMPLY. |
| | |
| | 40) THE EXIT TO THE EXTERIOR IS NOT |
| | SHOWN FOR THE NORTHWEST EGRESS STAIR. |
| | THE SITE PLAN ON A001 SHOWS EXTERIOR |
| | STAIRS AT THIS LOCATION. PROVIDE |
| | DETAILS. |
| | |
| | 41) THE DOOR SCHEDULE ON A400 LISTS ALL |
| | DOORS AS 3-0 X 8-0, THIS APPEARS TO |
| | DIFFER WITH THE EGRESS WIDTHS PROVIDED |
| | ON THE LIFE SAFETY PLAN AT THE TENNANT |
| | SPACE. FBC 1008.1.1 REQUIRES A MINIMUM |
| | CLEAR WIDTH OF NOT LESS THAN 32". |
| | |
| | 42) THE EXIT LIGHTS AT THE ELEVATOR AND |
| | DOOR 115 APPEAR TO BE LOCATED |
| | INCORRECTLY. THE EXIT LIGHT AT DOOR 116 |
| | IS LOCATED SO THAT IT WILL DIRECT PEOPLE |
| | BACK INTO THE GARAGE. PLEASE CORRECT. |
| | |
| | 43) SPECIFY GUARDS AND VECHICLE BARRIERS |
| | AS REQUIRED BY FBC 406.2.3 AND 406.2.4 |
| | AND DESIGNED IN ACCORDANCE WITH FBC |
| | 1607.7. PROVIDE DETAILS. |
| | |
| | 44) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| | WHICH REQUIRES NEW PLANS IN ORDER TO |
| | ADDRESS THE ABOVE COMMENTS, THE OLD |
| | SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| | REMAINING OLD SHEETS, TO FORM A SET OF |
| | 'OLD/VOID SHEETS', FOR COMPARISON OF |
| | REVISIONS WHEN REVIEWING THE RESUBMITTED |
| | PLANS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |