Plan Review Notes
Plan Review Notes For Permit 05120948
Permit Number 05120948
Review Stop P
Sequence Number 2
Notes
Date Text
2006-06-26 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
 1) PRREVIOUS COMMENTS #2,#3 DATED
 2-28-06 NOT ADDRESSED.
 2)THIRD FLOOR MASTER BATH WATER CLOSET
 SHOW CLEAR FLOOR SPACE AS REQUIRED IN
 THE DESIGN MANUEL, PG 7.43 CLEAR FLOOR
 SPACE AT TOILETS.
  
 3) SHT P-1 PLUMBING NOTES
 NOTE #16AIR CHAMBERS NOT APPROVED.
 REMOVE REFERENCE TO AIR CHAMBERS.
  
 SEE INCLOSED:
 COPIES OF THE FAIR HOUSING ACT.
  
  
 END OF COMMENTS QUESTIONS 561-805-66920
  