Plan Review Notes
Plan Review Notes For Permit 05120948
Permit Number 05120948
Review Stop M
Sequence Number 2
Notes
Date Text
2006-06-30 00:00:00DENIED:2004 FLORIDA BUILDING CODE
  
 RESPONSE TO COMMENTS DATED 2-6-06 BY
 HAROLD MOSER.
  
 COMMENT 1 - OK
 COMMENT 2 - OK
 COMMENT 3 - OK
 COMMENT 4 - OK
 COMMENT 5 - PLEASE NOTE, SHOULD THE A/C
 UNIT HAVE THE CAPACITY TO PRODUCE MORE
 THAN 2,000 CFM, A DUCT SMOKE DETECTOR
 WITH AUDIBLE/VISUAL NOTIFICATION IS
 REQUIRED.2004 FMC 606.2.1.THIS
 COMMENT REMAINS DUE TO THE FACT ENERGY
 CALCULATIONS WERE SUBMITTED FOR 56.8 BTU
 UNIT TO BE INSTALLED.THE EQUIPMENT
 SCHEDULES SHOWN ON PLAN SHEETS M-1
 THROUGH M-8 APPEAR TO BE THE SAME.
 PLEASE CLARIFY.
  
 COMMENT 6 - OK
 COMMENT 7 - OK
  
 ***************NEW COMMENTS*************
 8.DRYER SCHEDULE PROVIDES
 MAXIMUM LENGHT OF DRYER EXHAUST WITH THE
 NUMBER OF NUMBER OF 90'S INSTALLED.
 PLEASE VERIFY LAYOUT OF EXHAUST DUCT AS
 CERTIAN RUNS APPEAR TO EXCEED THE 25 FT
 REQUIREMENT PER 2001 FMC 504.6.1.
 PLEASE NOTE, THE PLANS APPEAR TO DEPICT
 "FLEX DUCT" FOR THE EXHAUST.PER 2004
 FMC 501.4 EXHAUST DUCTS SHALL BE METAL
 AND CONSTRUCTED IN ACCORDANCE TO CHAPTER
 6.
  
 9.PLEASE PROVIDE UL LISTING
 FOR THE FLOOR/CEILING ASSEMBLY.PLEASE
 NOTE, SUBMITTAL FOR THE "PRE-ENGINEERED"
 FLOOR SYSTEM REQUIRED FOR REVIEW.
  
 10. PLEASE PROVIDE MANUFACTURE'S
 INSTALLATION INSTRUCTIONS FOR THE FIRE
 DAMPERS ON THE JOBSITE FOR INSPECTION.
  
 11. PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2001 FMC
 TABLE 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  