| Date |
Text |
| 2006-06-30 00:00:00 | DENIED:2004 FLORIDA BUILDING CODE |
| | |
| | RESPONSE TO COMMENTS DATED 2-6-06 BY |
| | HAROLD MOSER. |
| | |
| | COMMENT 1 - OK |
| | COMMENT 2 - OK |
| | COMMENT 3 - OK |
| | COMMENT 4 - OK |
| | COMMENT 5 - PLEASE NOTE, SHOULD THE A/C |
| | UNIT HAVE THE CAPACITY TO PRODUCE MORE |
| | THAN 2,000 CFM, A DUCT SMOKE DETECTOR |
| | WITH AUDIBLE/VISUAL NOTIFICATION IS |
| | REQUIRED.2004 FMC 606.2.1.THIS |
| | COMMENT REMAINS DUE TO THE FACT ENERGY |
| | CALCULATIONS WERE SUBMITTED FOR 56.8 BTU |
| | UNIT TO BE INSTALLED.THE EQUIPMENT |
| | SCHEDULES SHOWN ON PLAN SHEETS M-1 |
| | THROUGH M-8 APPEAR TO BE THE SAME. |
| | PLEASE CLARIFY. |
| | |
| | COMMENT 6 - OK |
| | COMMENT 7 - OK |
| | |
| | ***************NEW COMMENTS************* |
| | 8.DRYER SCHEDULE PROVIDES |
| | MAXIMUM LENGHT OF DRYER EXHAUST WITH THE |
| | NUMBER OF NUMBER OF 90'S INSTALLED. |
| | PLEASE VERIFY LAYOUT OF EXHAUST DUCT AS |
| | CERTIAN RUNS APPEAR TO EXCEED THE 25 FT |
| | REQUIREMENT PER 2001 FMC 504.6.1. |
| | PLEASE NOTE, THE PLANS APPEAR TO DEPICT |
| | "FLEX DUCT" FOR THE EXHAUST.PER 2004 |
| | FMC 501.4 EXHAUST DUCTS SHALL BE METAL |
| | AND CONSTRUCTED IN ACCORDANCE TO CHAPTER |
| | 6. |
| | |
| | 9.PLEASE PROVIDE UL LISTING |
| | FOR THE FLOOR/CEILING ASSEMBLY.PLEASE |
| | NOTE, SUBMITTAL FOR THE "PRE-ENGINEERED" |
| | FLOOR SYSTEM REQUIRED FOR REVIEW. |
| | |
| | 10. PLEASE PROVIDE MANUFACTURE'S |
| | INSTALLATION INSTRUCTIONS FOR THE FIRE |
| | DAMPERS ON THE JOBSITE FOR INSPECTION. |
| | |
| | 11. PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS IN ACCORDANCE WITH 2001 FMC |
| | TABLE 403.3. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |