Plan Review Notes
Plan Review Notes For Permit 05120948
Permit Number 05120948
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-11 00:00:00IN ELEC FOR REVIEW.
 ********** UNSAT 2ND REVIEW ***********
  
 ** PLEASE SEE PLANS ARE STILL ONLY BEING
 SUBMITTED FOR "PLAN REVIEW " AND NOT FOR
 PERMIT.
 SOME COMMENTS ARE FROM PREVIOUS REVIEW
 AND SOME ARE NEW.
  
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AND NEW
 NOTES ARE ADDED AT THE END OF PREVIOUS
 NOTES.
  
 ********* UNSAT *************
  
 1)NOTE: NOTE #1 SAME, PLEASE SEE AS ONLY
 SUBMITTED FOR PLAN REVIEW, IT IS STILL
 NOT KNOW, IF EACH UNIT WILL BE A LEGAL
 TOWNHOUSE WITH PROPERTY LINES SEPARATING
 UNITS ETC. ONLY IF THIS IS THE CASE WILL
 ONE SERVICE BE GRANTED FOR EACH
 TOWNHOUSE. IF THIS IS ONE BUILDING UNDER
 ONE LEGAL ADDRESSAND PERMITTED UNDER
 ONE PERMIT, THEN ONLY ONE SERVICE WILL
 BE GRANTED. AS PLANS ARE NOT SUBMITTED
 FOR PERMIT. THIS COMMENT SHALL REMAIN
 AND PLANS STILL MAY NEED TO BE REVISED
 AT A LATER DATE.
  
 ** PREVIOUS NOTE **
 PLANS SUBMITTED FOR PLAN REVIEW
 UNDER ONE SINGLE MULTI-FAMILY BLDG,
 HOWEVER ELECTRICAL SERVICES SEEM TO
 INDICATE THE UNIT WILL BE A FEE-SIMPLE
 "TOWNHOUSE". ?? COULD NOT LOCATE ANY
 PROPERTY LINES ON SITE PLAN OR ANY
 INDICATTION OF SUCH. PLEASE SEE 230.2,
 ONLY ONE ELECTRICAL SERVICE WILL BE
 PERMITTED. PLEASE ALSO SEE OTHER
 COMMENTS IF INDEED EACH UNIT WILL BE
 SEPARATED BY PROPERTY LINES AND A 4HR
 FIRE WALL. PLEASE SEE 2004 FBC
 DEFINITIONS FOR "FIREWALL".
 PLEASE REVISE ELECTRICAL SERVICE PLANS
 AS NEEDED DEPENDING ON WHAT TYPE FO
 BLDG.
 ** PLEASE KNOW, IF BLDG(S) DO BECOME
 INDIVIDUALLY OWNED , WITH SEPARATE PCN
 NUMBERS ETC, THEN EACH UNIT WOULD BE A
 SEPARATEPERMIT APPLICATION WITH
 SEPARATE PLANS AND FEES.
 THIS WOULD AFFECT COMMENT #3 FOR THE
 DESIGN PROFESSIONAL REQUIREMENT.
 ** PLEASE SEE NOTE #4 FOR ADDRESSING OF
 BLDG.
  
 2)NOTE: OK.
  
 3)NOTE: NOTE #3 ? IT IS NOT KNOWN AT
 THIS TIME IF ARCHITECT MAY SIGN, DATE
 AND SEAL PLANS. IF PROJECT IS ONE
 BUILDING WITH ONE SERVICE THEN PLANS
 WILL BE REQUIRED TO BE SIGNED , DATED
 AND SEALED BY A PE.
  
 ** PREVIOUS NOTE **
 PLEASE SEE FS 471.003(2)(H)
 WHICH REQUIRES THE ELECTRICAL PLANS TO
 BE DONE BY ANY ENGINEER.
 PLEASE ADJUST AS NESSESARY.
  
 4)NOTE: NOTE #4 NO, PLEASE SEE ADDRESS
 ON PLANS/TITLE BLOCKS STILL INDICATE
 1200 LAKE AVE.PLEASE SEE THE ADDRESS
 ASSIGNED FOR THE BUILDING IS 766 N ST.
 PLEASE SEE IF THESE UNITS ARE DONE UNDER
 SEPARATE PERMITS AS LEGAL "TOWNHOUSE",
 THEN THERE WILL BELEGAL PROPERTY
 ADDRESS FOR EACH.
  
 ** PREVIOUS NOTE**
 PLEASE SEE NOTES FROM ZONING AND
 ADDRESSING AS BLDG SEEM TO CONTAIN THE
 SMALL PORTION OF THE BLDG ON LAKE AVE
 WHICH WOULD BE THE ADDRESS AS LISTED ON
 PLANS. PLEASE SEE COMMENT #1, IF BLDG
 CHNAGES, THEN SEPARATE ADDRESSES WOULD
 BE APPLIED AND TITLE BLOCK WOULD BE
 ADJUSTED.
  
 5)NOTE: NOTE #5 NO, PLEASE SEE THIS WAS
 DONE ON COVER SHEET, HOWEVER ELECTRICAL
 PLANS MENTIONS THE LATEST CODES, AND THE
 LATEST CODES WHICH ARE OUT, ARE NOT
 ADOPTED YET. THEREFORE ELECTRICAL PLANS
 SHALL ALSO INDICATE THE CODES AS NOTED.
 2002 NFPA-72, 2002 NFPA-70
  
 ** PREVIOUS NOTE **
 PLEASE SEE PLANS SHALL INDICATE
 THE CURRENT CODES IN EFFECT. PLEASE SEE
 THIS HAS NOT BEEN SUBMITTED FOR PERMIT
 AS OF YET AND THEREFORE DEPENDING ON
 WHEN THAT HAPPENS, THE 2005 NEC SHOULD
 BE ADOPTED IN THE MONTHS TO COME.
 PLEASE SEE THE CURRENT CODE IS THE 2004
 FBC. PLEASE SEE PLANS SHALL REFERENCE
 THE CURRENT NFPA-101 2003, NFPA-72 2002
 , AND 2002 NFPA-70 (NEC). PLEASE SEE
 REDLINED LOCATIONS ON THE PLANS WHERE
 THERE ARE REFERENCES TO THE "1996"
 AND "1999" NEC. PLEASE KNOW, AS OF JULY
 1ST, 2003 THE STATE OF FLORIDA ADOPTED
 THE 2002 NEC.
 PLEASE ADJUST LOCATIONS AND REQUIREMENTS
 AS NEEDED.
 PLEASE OTHER COMMENTS AFFECT BY THE CODE
 CHANGES BELOW.
  
 6)NOTE: OK
  
 7)NOTE: OK.
  
 8)NOTE: OK
  
 9)NOTE: NOTE #9, PLEASE SEE THE
 EQUIPMENT GROUNDING CONDUCTOR WAS
 REMOVED FROM THE METER TO THE MAIN AS
 NOTED ON PREVIOUS REVIEW, HOWEVER SEE
 NOW THE EQUIPMENT GROUNDING CONDUCTOR
 HAS NOW ALSO BEEN REMOVED AFTER THE
 MAIN??
 250.24B, 250.110,250.122
  
 ** PREVIOUS NOTE **
 PLEASE SEE IF PLANS DO BECOME
 INDIVIDUAL UNITS AND SEPARATE SERVICES
 ARE PERMITTED, PLEASE SEE RISER SHOWS AN
 "EQUIPMENT GROUNDING CONDUCTOR" FROM THE
 METER TO THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6, AS THE EQUIPMENT
 GROUNDING CONDUCTOR IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 10)NOTE:NOTE #10 NO, PLEASE SEE ONLY A
 PARTIAL NOTE WAS ADDED WITH RESPECT TO
 THE SD'S BEING LOCATED 3' FROM HVAC
 DIFFUSERS. PLEASE SEE THE NFPA BELOW, AS
 IT ALSO REQUIRES SD'S TO BE LCOATED 3'
 FROM KITCHEN AND BATH DOORS, AND 20'
 FROM ALL COOKING APPLIANCES WITH
 EXCEPTIONS. IF USING EXCEPTION, THEN
 PLANS SHALL INDICATE THE TYPE OF SD TO
 BE INSTALLED.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE A NOTE ON PLANS
 WITH REFERENCE TO THE MIN CLEARNECES
 REQUIRED FOR SD'S AND PLACEMENT PER
 NFPA-72 2002 11.8.3.5
  
 11)NOTE: OK
  
 12)NOTE:NOTE #12, PLEASE SEE LOCATION
 OF CU IS SHOWN ON BALCONY OF 2ND FLR ,
 HOWEVER MIN CLEARENCS ARE NOT SHOWN PER
 110.26. PLEASE ALSO SEE MECHANICAL
 NOTES.
  
 ** PREVIOUS NOTE **
 PLEASE CONFIRM A/C CU LOCATIONS, AS
 THESE APPEAR TO BE LOCATED IN AN AREA ON
 2N FLR BALCONY? THIS ARE APPEARS MAYBE
 TO BE ENCLOSED?
  
 13)NOTE: OK.
  
 14)NOTE: OK.
  
 15)NOTE: OK.
  
 16)NOTE: NOTE# 16, NO, THIS IS NOT
 SETTLED AS OF YET. PLEASE SEE PLANS DO
 NOT INDICATE THE MAIN NEXT TO METER. (IF
 PERMITTED).
  
 ** PREVIOUS NOTE**
 PLEASE BE SURE TO CORRELATE
 PLANS WITH WHAT TYPE OF SERVICE IS GOING
 TO BE INSTALLED, PLEASE BE SURE
 EQUIPMENT(METER, MAINS ETC) ARE SHOWN ON
 PLANS AS WELL AS RISER.
 215.5
  
 17)NOTE: OK. AP WAS LOCATE DON BUILDING
 - 1 PLANS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE WHIRLPOOL TUB IS
 LISTED AS OPTIONAL ON PANEL SCHEDULE
 ALONG WITH ALARM PANEL. PLEASE SEE THESE
 LOCATIONS FOR DEVICES NEED TO BE SHOWN
 ON PLASN FOR REVIEW. ACCESS PANEL FOR
 GFI AND LOCATION OF POSSISBLE FUTURE
 ALARAM PANEL NEEDS TO BE VERIFIED.
 ** PLEASE KNOW, ANY ELECTRICAL DEVICES
 ETC SHOWN AS "OPTIONAL" ON PLANS SHALL
 BE REVISED AND SUBMITTED FOR REVIEW AND
 TO BE ON JOBSITE BEFORE ROUGH**
  
 18)NOTE: OK.
  
 19)NOTE:NOTE #19 NO, UNCLEAR AT THIS
 TIME AS PLANS ARE STILL BEING SUBMITTED
 BY THE ARCHITECT WHICH A LETTER COULD
 NOT BE LOCATED IN PLANS AND PAPERWORK
 SUBMITTED.
 IF PLANS ARE DONE BY THE ARCH, THIS LTR
 SHLL BE PROPERLY NOTORIZED PER FS
 117.05.
  
 ** PREVIOUS NOTE **
 PLEASE SEE IF UNITS DO COME IN
 AS INDIVIDUAL AND ARE DONE BY THE
 ARCHITECT, PLEASE PROVIDE A SIGNED,
 DATED AND SEALED LETTER FOR VERIFICATION
 OF LEGAL SIGNATURE AS PLANS APPEAR TO BE
 INITIALS.
  
 ************************************
 NEW NOTES
  
 20) NOTE: PLEASE SEE THAT A TYPE WRITTEN
 RESPONSE FROM DESIGN TEAM WILL HELP IN
 THE REVIEW PROCESS WHICH WILL RESPOND TO
 EACH COMMENT INDIVIDUALLY.
  
 21) NOTE: PLEASE SUBMIT TEH AIC RATINGS
 FOR ALL SERVICE EQUIPMENT.
 110.9, 215.5
 THIS WAS ON PREVOUS PLANS BUT HAS NOW
 BEEN REMOVED. PLEASE KNOW, DEPENDING ON
 THE PERMITTING AND SERVICE WHICH WILL BE
 PERMITTED THE AIC RATINGS AND EQUIPMENT
 MAY CHANGE.
  
 22) NOTE: PLEASE SEE NOTES FROM BUILDING
 REVIEWER FOR MISSING INFORMATION FOR THE
 "S" SHEETS PER FAC 61G15-23.002, FS
 471.023
 MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER AND THE PRINTED NAME AND LICENSE
 NUMBER OF ENGINEER ON TITLE BLOCK.
  
 23) NOTE: PLEASE SEE PANEL SCHEDULE
 SHALL BE SPECIFIC FOR ALL CIRCUITING.
 PLEASE SEE RECEPTS, AND LIGHTING
 CIRCUITS SHALL INDICATE ROOMS OR AREAS
 IN WHICH THEY ARE FEEDING.IE: BEDRM #3
 RECEPTS, KITCHEN LT ETC.
 **IT IS KNOW THAT DURING CONSTRUCTION,
 THESE WILL MOSTLY CHANGE AND MAY NEED TO
 BE REVISED AT A LATER DATE, HOWEVER MUST
 BE SPECIFIC AT THIS TIME.
  
 24) NOTE: PLEASE SEE A SD MAY BE
 REQUIRED AT 2ND LEVEL IN BUILDING ONE IN
 THE IMEDIATE VICINIY OF THE STAIRS, THIS
 IS REDLINED ON ONE SET AT LOCATION BUT
 IF NOT ADDED TO PLANS THE LOCATION SHALL
 BE VERIFIED IN FIELD.
 NFPA-72 11.5.1.1
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 ** PLEASE SEE BLDG COMMENTS WITH RESPECT
 TO PRODUCT APPROVALS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]