Plan Review Notes
Plan Review Notes For Permit 05120948
Permit Number 05120948
Review Stop B
Sequence Number 2
Notes
Date Text
2006-05-25 00:00:001) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 4) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 A) WINDOWS FIXED AND OPERATABLE
 B)EXTERIOR DOORS SWINGING AND FIXED
 C)MULLIONS IF ANY
 D)ROOF ASSEMBLY
 E)TRUSS ANCHORS ETC.
 PRODUCTS WITH STATEWIDE APPROVAL
 ARE REQUIRED TO BE SUBMITTED WITH A
 COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE
 PRODUCT DOES NOT HAVE STATEWIDE
 APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 5) R802.10.1 TRUSS DESIGN DRAWINGS.
 TRUSS DESIGN DRAWINGS, PREPARED IN
 CONFORMANCE WITH SECTION R802.10.1 ,
 SHALL BE PROVIDED TO THE BUILDING
 OFFICIAL AND APPROVED PRIOR TO
 INSTALLATION. TRUSS DESIGN DRAWINGS
 SHALL INCLUDE, AT A MINIMUM, THE
 INFORMATION SPECIFIED BELOW. TRUSS
 DESIGN DRAWING SHALL BE PROVIDED WITH
 THE SHIPMENT OF TRUSSES DELIVERED TO THE
 JOBSITE.
  
 6) R903.4.1
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW
 WATER IS NOT PROVIDED, OVERFLOW SCUPPERS
 SHALL BE PLACED IN WALLS OR PARAPETS NOT
 LESS THAN 2 INCHES (51 MM) NOR MORE THAN
 4 INCHES (102 MM) ABOVE THE FINISHED
 ROOF COVERING AND SHALL BE LOCATED AS
 CLOSE AS PRACTICAL TO REQUIRED VERTICAL
 LEADERS OR DOWNSPOUTS OR WALL AND
 PARAPET SCUPPERS. AN OVERFLOW SCUPPER
 SHALL BE SIZED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, PLUMBING .
 SPECIFY CLEARLY THE SIZE OF THE ROOF
 DRAIN AND SCUPPERS.
  
 7) SHEET A-1. THE CLAEAR FLOOR SPACE
 CANNOT EXTEND INTO THE SHOWER. THE CLEAR
 FLOOR SPACE DIMENSIONS ARE TO BE APPLIED
 OR SUPERIMPOSED OVER A PLAN DURING THE
 DESIGN PROCESS TO DETERMINE IF THE SPACE
 REQUIREMENTS ARE BEING MET.
 FH.7.43/7.56. A 30"X48" CLEAR FLOOR
 SPACE MUST BE PROVIDED AT SHOWER
 STALLS,PARALLEL TO THE FIXTURE AND FLUSH
 WITH THE CONTROL WALL.
 ***RESPONSE NOTED, BUT TYPE "B" BATH
 DETAIL 6 ON SHT D3 DOES NOT COMPLY WITH
 CLEAR FLOOR SPACE REQUIREMENTS FOR THE
 SHOWER AS INDICATED. FH. 7.53 - 7.58
  
 8) ON SHEET D-1 DETAIL #2 SHOWS THE
 THIRD FLOOR BEING POURED INTO THE 2HR
 RATED WALL. EACH FLOOR SHALL BE
 INDEPENDANTLY ATTATCHED TO THE 2HR
 DEVIDING WALL.
  
 9) A DETAIL DRAWING OF THE FLOOR JOIST
 CONNECTION TO THE COMMON WALL IS
 REQUIRED SHOWING ALL MATERIALS WHICH
 WILL BE USED ,ALSO STATE THE LIVE AND
 DEAD LOADS OF EACH FLOOR AND THE SPACING
 OF THE FLOOR JOISTS.
  
  
 10) R324.1 SPRINKLER SYSTEM REQUIREMENTS
 FOR BUILDINGS THREE STORIES OR MORE IN
 HEIGHT. NFPA 101, AS REGARDING THE
 REQUIREMENTS FOR FIRE PROTECTION
 SPRINKLERS, IS APPLICABLE TO ALL
 MULTIPLE-FAMILY RESIDENTIAL BUILDINGS,
 WHETHER DESIGNATED AS TOWNHOUSES,
 CONDOMINIUMS, APARTMENT HOUSES,
 TENEMENTS, GARDEN APARTMENTS OR BY ANY
 OTHER NAME. THE ATTORNEY GENERAL HAS
 DETERMINED THAT FOR THE PURPOSE OF THE
 FIRE PROTECTION SPRINKLER REQUIREMENTS
 IN SECTION 553.895(2), FLORIDA STATUTES
 , TOWNHOUSES THAT ARE THREE OR MORE
 STORIES TALL AND CONSIST OF THREE OR
 MORE UNITS TOGETHER ARE MULTIPLE-FAMILY
 DWELLINGS. THEREFORE, THESE TYPES OF
 TOWNHOUSES ARE NOT EXEMPT. A SEPERATE
 PERMIT IS REQUIRED FOR THE SPRINKLER
 SYSTEM.
  
 11) R401.4 SOIL TESTS.
 IN AREAS LIKELY TO HAVE EXPANSIVE,
 COMPRESSIBLE, SHIFTING OR OTHER UNKNOWN
 SOIL CHARACTERISTICS, THE BUILDING
 OFFICIAL SHALL DETERMINE WHETHER TO
 REQUIRE A SOIL TEST TO DETERMINE THE
 SOIL ?S CHARACTERISTICS AT A PARTICULAR
 LOCATION. THIS TEST SHALL BE MADE BY AN
 APPROVED AGENCY USING AN APPROVED
 METHOD.
  
 12) SHEET D-1 SHOWS THE THIRD FLOOR AS
 PART OF THE 2 HOUR FIRE WALL. EACH
 INDIVIDUAL TOWNHOUSE SHALL BE
 STRUCTURALLY INDEPENDENT OF EACH OTHER.
 SEE R317.2.4 AND F.S.481.203 (7)(C).
  
 13) RULE 61G155-23.001(1) F.A.C.
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS HAS CLEANED UP THE APPEARENCE
 OF THE SEAL BY ELIMINATING OBSOLETE
 CONTENT AND CHANGING THE WORD
 "CERTIFICATE" TO "LICENSE". A GRACE
 PERIOD RAN THROUGH DEC. 31,2005.
 SHEETS S-1-1 TO S-6
  
 14 ) 61G1-16.004FL. ADMIN. CODE.
 PLANS PREPARED BY A REGISTERED ARCHITECT
 SHALL INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS. ALSO SEE
 61G15-23.002.
  
 15) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 16) HI-LIGHT OR CIRCLE WHICH ROOF
 ASSEMBLY WILL BE USED FROM THE
 PACKAGE.SUBMIT THE PAGES WHICH STATE ALL
 THE MATERAIALS,THE SYSTEM TO BE USED AND
 THE LAST PAGE WITH THE GENERAL
 LIMITATIONS: WHEN THE ASSEMBLY IS
 CHOSEN, BE SURE TO READ THE LIMITATION
 AND NOTE WHAT IS REQUIRED. THE STATE
 COVER SHEETS ARE MISSING FORM ALL THE
 PRODUCT APPROVALS, SEE NOTE #4.
  
 17) FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  