| 2006-05-25 00:00:00 | 1) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 2) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3) 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS |
| | CODE SHALL BE PERMORMED IN A MANNER SO |
| | AS NOT TO ADVERSLY IMPACT THE CONDITION |
| | OF ADJACENT PROPERTY, UNLESS SUCH |
| | ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE |
| | PROPERTY OWNER.THIS INCLUDES BUT IS NOT |
| | LIMITED TO THE CONTROL OF DUST, NOISE, |
| | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| | THE STORAGE OF CONSTRUCTION MATERIALS. |
| | NEW CONSTRUCTION ACTIVITY SHALL NOT |
| | ADVERSELY IMPACT HISTORIC SURFACE WATER |
| | DRAINAGE FLOWS SERVING ADJACENT |
| | PROPERTIES, & MAY REQUIRE SPECIAL |
| | DRAINAGE DESIGNCOMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED |
| | SITES.ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENET, INCLUDING |
| | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, |
| | DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN |
| | EXCESS OF 800SQ FT OF PERMEABLE LAND |
| | AREA ON ANY PARCELL SHALL AS A PERMIT |
| | CONDITION, PROVIDE A PROFESSIONALY |
| | PREPARED DRAINAGE PLAN CLEARLY |
| | INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 4) WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | A) WINDOWS FIXED AND OPERATABLE |
| | B)EXTERIOR DOORS SWINGING AND FIXED |
| | C)MULLIONS IF ANY |
| | D)ROOF ASSEMBLY |
| | E)TRUSS ANCHORS ETC. |
| | PRODUCTS WITH STATEWIDE APPROVAL |
| | ARE REQUIRED TO BE SUBMITTED WITH A |
| | COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE |
| | PRODUCT DOES NOT HAVE STATEWIDE |
| | APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC |
| | FORM PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 5) R802.10.1 TRUSS DESIGN DRAWINGS. |
| | TRUSS DESIGN DRAWINGS, PREPARED IN |
| | CONFORMANCE WITH SECTION R802.10.1 , |
| | SHALL BE PROVIDED TO THE BUILDING |
| | OFFICIAL AND APPROVED PRIOR TO |
| | INSTALLATION. TRUSS DESIGN DRAWINGS |
| | SHALL INCLUDE, AT A MINIMUM, THE |
| | INFORMATION SPECIFIED BELOW. TRUSS |
| | DESIGN DRAWING SHALL BE PROVIDED WITH |
| | THE SHIPMENT OF TRUSSES DELIVERED TO THE |
| | JOBSITE. |
| | |
| | 6) R903.4.1 |
| | WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW |
| | WATER IS NOT PROVIDED, OVERFLOW SCUPPERS |
| | SHALL BE PLACED IN WALLS OR PARAPETS NOT |
| | LESS THAN 2 INCHES (51 MM) NOR MORE THAN |
| | 4 INCHES (102 MM) ABOVE THE FINISHED |
| | ROOF COVERING AND SHALL BE LOCATED AS |
| | CLOSE AS PRACTICAL TO REQUIRED VERTICAL |
| | LEADERS OR DOWNSPOUTS OR WALL AND |
| | PARAPET SCUPPERS. AN OVERFLOW SCUPPER |
| | SHALL BE SIZED IN ACCORDANCE WITH THE |
| | FLORIDA BUILDING CODE, PLUMBING . |
| | SPECIFY CLEARLY THE SIZE OF THE ROOF |
| | DRAIN AND SCUPPERS. |
| | |
| | 7) SHEET A-1. THE CLAEAR FLOOR SPACE |
| | CANNOT EXTEND INTO THE SHOWER. THE CLEAR |
| | FLOOR SPACE DIMENSIONS ARE TO BE APPLIED |
| | OR SUPERIMPOSED OVER A PLAN DURING THE |
| | DESIGN PROCESS TO DETERMINE IF THE SPACE |
| | REQUIREMENTS ARE BEING MET. |
| | FH.7.43/7.56. A 30"X48" CLEAR FLOOR |
| | SPACE MUST BE PROVIDED AT SHOWER |
| | STALLS,PARALLEL TO THE FIXTURE AND FLUSH |
| | WITH THE CONTROL WALL. |
| | ***RESPONSE NOTED, BUT TYPE "B" BATH |
| | DETAIL 6 ON SHT D3 DOES NOT COMPLY WITH |
| | CLEAR FLOOR SPACE REQUIREMENTS FOR THE |
| | SHOWER AS INDICATED. FH. 7.53 - 7.58 |
| | |
| | 8) ON SHEET D-1 DETAIL #2 SHOWS THE |
| | THIRD FLOOR BEING POURED INTO THE 2HR |
| | RATED WALL. EACH FLOOR SHALL BE |
| | INDEPENDANTLY ATTATCHED TO THE 2HR |
| | DEVIDING WALL. |
| | |
| | 9) A DETAIL DRAWING OF THE FLOOR JOIST |
| | CONNECTION TO THE COMMON WALL IS |
| | REQUIRED SHOWING ALL MATERIALS WHICH |
| | WILL BE USED ,ALSO STATE THE LIVE AND |
| | DEAD LOADS OF EACH FLOOR AND THE SPACING |
| | OF THE FLOOR JOISTS. |
| | |
| | |
| | 10) R324.1 SPRINKLER SYSTEM REQUIREMENTS |
| | FOR BUILDINGS THREE STORIES OR MORE IN |
| | HEIGHT. NFPA 101, AS REGARDING THE |
| | REQUIREMENTS FOR FIRE PROTECTION |
| | SPRINKLERS, IS APPLICABLE TO ALL |
| | MULTIPLE-FAMILY RESIDENTIAL BUILDINGS, |
| | WHETHER DESIGNATED AS TOWNHOUSES, |
| | CONDOMINIUMS, APARTMENT HOUSES, |
| | TENEMENTS, GARDEN APARTMENTS OR BY ANY |
| | OTHER NAME. THE ATTORNEY GENERAL HAS |
| | DETERMINED THAT FOR THE PURPOSE OF THE |
| | FIRE PROTECTION SPRINKLER REQUIREMENTS |
| | IN SECTION 553.895(2), FLORIDA STATUTES |
| | , TOWNHOUSES THAT ARE THREE OR MORE |
| | STORIES TALL AND CONSIST OF THREE OR |
| | MORE UNITS TOGETHER ARE MULTIPLE-FAMILY |
| | DWELLINGS. THEREFORE, THESE TYPES OF |
| | TOWNHOUSES ARE NOT EXEMPT. A SEPERATE |
| | PERMIT IS REQUIRED FOR THE SPRINKLER |
| | SYSTEM. |
| | |
| | 11) R401.4 SOIL TESTS. |
| | IN AREAS LIKELY TO HAVE EXPANSIVE, |
| | COMPRESSIBLE, SHIFTING OR OTHER UNKNOWN |
| | SOIL CHARACTERISTICS, THE BUILDING |
| | OFFICIAL SHALL DETERMINE WHETHER TO |
| | REQUIRE A SOIL TEST TO DETERMINE THE |
| | SOIL ?S CHARACTERISTICS AT A PARTICULAR |
| | LOCATION. THIS TEST SHALL BE MADE BY AN |
| | APPROVED AGENCY USING AN APPROVED |
| | METHOD. |
| | |
| | 12) SHEET D-1 SHOWS THE THIRD FLOOR AS |
| | PART OF THE 2 HOUR FIRE WALL. EACH |
| | INDIVIDUAL TOWNHOUSE SHALL BE |
| | STRUCTURALLY INDEPENDENT OF EACH OTHER. |
| | SEE R317.2.4 AND F.S.481.203 (7)(C). |
| | |
| | 13) RULE 61G155-23.001(1) F.A.C. |
| | THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS HAS CLEANED UP THE APPEARENCE |
| | OF THE SEAL BY ELIMINATING OBSOLETE |
| | CONTENT AND CHANGING THE WORD |
| | "CERTIFICATE" TO "LICENSE". A GRACE |
| | PERIOD RAN THROUGH DEC. 31,2005. |
| | SHEETS S-1-1 TO S-6 |
| | |
| | 14 ) 61G1-16.004FL. ADMIN. CODE. |
| | PLANS PREPARED BY A REGISTERED ARCHITECT |
| | SHALL INCLUDE A TITLE BLOCK WHICH MUST: |
| | - STATE THE FIRM NAME, ADDRESS AND |
| | TELEPHONE NUMBER |
| | - STATE THE FIRM LICENSE NUMBER |
| | - STATE PROJECT NAME OR IDENTIFICATION |
| | - STATE DATE PREPARED |
| | - INCLUDE AN ORIGINAL SIGNATURE AND |
| | DATED SEAL |
| | - INCLUDE THE PRINTED NAME OF THE |
| | ARCHITECT SEALING THE PLANS. ALSO SEE |
| | 61G15-23.002. |
| | |
| | 15) WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MIN- |
| | IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 16) HI-LIGHT OR CIRCLE WHICH ROOF |
| | ASSEMBLY WILL BE USED FROM THE |
| | PACKAGE.SUBMIT THE PAGES WHICH STATE ALL |
| | THE MATERAIALS,THE SYSTEM TO BE USED AND |
| | THE LAST PAGE WITH THE GENERAL |
| | LIMITATIONS: WHEN THE ASSEMBLY IS |
| | CHOSEN, BE SURE TO READ THE LIMITATION |
| | AND NOTE WHAT IS REQUIRED. THE STATE |
| | COVER SHEETS ARE MISSING FORM ALL THE |
| | PRODUCT APPROVALS, SEE NOTE #4. |
| | |
| | 17) FBC 13-103.1.2 BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED, THE SUBMITTED |
| | ENERGY CODE COMPLIANCE FORMS SHALL BE |
| | SIGNED BY THE BUILDING OWNER, THE |
| | OWNER'S ARCHETECT OR OTHER AUTHORIZED |
| | AGENT LEGALLY DESIGNATED BY THE OWNER. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | TEL:(561)805-6726 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |