| Plan Review Notes For Permit 05120948 |
| Permit Number |
05120948 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-06 00:00:00 | PLAN DENIED | | | 1- PLEASE REFER TO SECTION 110.1.2 | | | ISSUING CERTIFICATE OF OCCUPANCE # | | | 4,8,9,10 MUST BE ON PLANS. | | | 2- PLEASE SUPPLY ENERGY CALCULATIONS | | | WITH PLANS SECTION 13-103.2 2004 ENERGY | | | CODE. | | | 3- PLEASE REFER TO SECTION 607.5.2 FIRE | | | BARRIERS.2004 FBC M GARAGE WALL. | | | 4- NEED FIRE DAMPER IN 30X10 DUCT UP TO | | | 2ED FLOOR. | | | 5- PLEASE REFER TO SECTION 606.2.1 | | | SUPPLY AIR SYSTEM.AND SECTION 606.4.1 | | | SUPERVISON. | | | 6- PLEASE REFRE TO SECTION 602.2.1 | | | METERALS EXPOSED WITHIN PLENUMS. | | | 7- PLEASE REFER TO SECTION 307.2.3 | | | AUXILIARY AND SECONDARY DRAIN SYSTEM | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|