| 2006-01-24 00:00:00 | 1. SITE PLAN DOES NOT ILLUSTRATE NEW OR |
| | EXISTING FIRE HYDRANTS. PLEASE DISPLAY |
| | ALL FIRE HYDRANTS FOR THE PROPOSED |
| | DEVELOPMENT. |
| | |
| | 2. ALL BUILDINGS THREE OR MORE STORIES |
| | REGARDLESS OF OCCUPANCY TYPE ARE |
| | REQUIRED TO BE FIRE SPRINKLER PROTECTED |
| | IN ACCORDANCE WITH FS 553.895 (2). |
| | |
| | 3. ALL CONSTRUCTION, RENOVATION, AND |
| | DEMOLITION TO COMPLY WITH NFPA 241. |
| | |
| | 4. FIRE SPRINKLER CONENCTIONS SHALL BE |
| | LOCATED NO FARTHER THAN 150 FEET FROM A |
| | FIRE HYDRANT. |
| | |
| | 5. PLEASE PROVIDE PRSCRIPTIVE STRENGTH |
| | REQUIREMENTS FOR ALL HANDRAILS AND |
| | GUARDRAILS. |
| | |
| | 6. BUILDING ADDRESSES ARE REQUIRED ON |
| | PROPER ELEVATIONS. A MINIMUM OF AT LEAST |
| | 6" HIGH NUMBERS ARE REQUIRED. |
| | |
| | 7. PORTABLE FIRE EXTINGUISHERS ARE SHOWN |
| | ON THE DRAWINGS. MORE DETAILS NEEDED ON |
| | THE TYPE AND FIRE RATINGS. |
| | |
| | 8. THE REQUIRED FIRE SPRINKLER SYSTEM |
| | SHALL BE MONITORED BY A UL LISTED |
| | CENTRAL STATION APPROVED FOR CENTRAL |
| | STATION SERVICE. |
| | |
| | 9. NO FIRE SPRINKLER SYSTEM DRAWINGS OR |
| | HYDRAULIC CALCULATIONS PROVIDED WITH |
| | PLANS. |
| | |
| | 10. ALL REQUIRED SMOKE DETECTORS SHALL |
| | BE LOCATED AT LEAST THREE FEET FROM AIR |
| | CONDITIONER DIFFUSERS. |
| | |
| | 11. PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATIONS FOR WALLS AND CEILINGS. |
| | |
| | 12. PLEASE PROVIDE UL NUMBERS FOR THE |
| | TWO HOUR PARTY WALLS THAT ARE SHOWN. |
| | |
| | 13. PLEASE CALL OUT ANY FENCE LOCATIONS |
| | ON THE SITE PLAN. A FENCE DETAIL IS |
| | OBSERVED ON PAGE SP-1 BUT IT IS NOT |
| | CALLED OUT ON THE SITE PLAN. |
| | |
| | 14. PLEASE INDICATE HOW THE FIRE |
| | SPRINKLER SYSTEM BULK-MAIN IS TO BE RUN |
| | TO PROVIDE FIRE SPRINKLER PROTECTION. |
| | DESIGN ISSUES RESULT IF NOT PROPERTY |
| | CONSIDERED. |
| | |
| | MIKE CARSILLO, CHIEF FIRE PREVENTION |
| | OFFICER |
| | |
| | 804-4709 |