Plan Review Notes
Plan Review Notes For Permit 05120948
Permit Number 05120948
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-01-24 00:00:001. SITE PLAN DOES NOT ILLUSTRATE NEW OR
 EXISTING FIRE HYDRANTS. PLEASE DISPLAY
 ALL FIRE HYDRANTS FOR THE PROPOSED
 DEVELOPMENT.
  
 2. ALL BUILDINGS THREE OR MORE STORIES
 REGARDLESS OF OCCUPANCY TYPE ARE
 REQUIRED TO BE FIRE SPRINKLER PROTECTED
 IN ACCORDANCE WITH FS 553.895 (2).
  
 3. ALL CONSTRUCTION, RENOVATION, AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 4. FIRE SPRINKLER CONENCTIONS SHALL BE
 LOCATED NO FARTHER THAN 150 FEET FROM A
 FIRE HYDRANT.
  
 5. PLEASE PROVIDE PRSCRIPTIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 6. BUILDING ADDRESSES ARE REQUIRED ON
 PROPER ELEVATIONS. A MINIMUM OF AT LEAST
 6" HIGH NUMBERS ARE REQUIRED.
  
 7. PORTABLE FIRE EXTINGUISHERS ARE SHOWN
 ON THE DRAWINGS. MORE DETAILS NEEDED ON
 THE TYPE AND FIRE RATINGS.
  
 8. THE REQUIRED FIRE SPRINKLER SYSTEM
 SHALL BE MONITORED BY A UL LISTED
 CENTRAL STATION APPROVED FOR CENTRAL
 STATION SERVICE.
  
 9. NO FIRE SPRINKLER SYSTEM DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 PLANS.
  
 10. ALL REQUIRED SMOKE DETECTORS SHALL
 BE LOCATED AT LEAST THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
  
 11. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 12. PLEASE PROVIDE UL NUMBERS FOR THE
 TWO HOUR PARTY WALLS THAT ARE SHOWN.
  
 13. PLEASE CALL OUT ANY FENCE LOCATIONS
 ON THE SITE PLAN. A FENCE DETAIL IS
 OBSERVED ON PAGE SP-1 BUT IT IS NOT
 CALLED OUT ON THE SITE PLAN.
  
 14. PLEASE INDICATE HOW THE FIRE
 SPRINKLER SYSTEM BULK-MAIN IS TO BE RUN
 TO PROVIDE FIRE SPRINKLER PROTECTION.
 DESIGN ISSUES RESULT IF NOT PROPERTY
 CONSIDERED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
  
 804-4709