Plan Review Notes
Plan Review Notes For Permit 05120948
Permit Number 05120948
Review Stop E
Sequence Number 1
Notes
Date Text
2006-01-25 00:00:00REVIEW
 ********* UNSAT *************
  
 ***************************************
 PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW " AND NOT FOR
 PERMIT. PLEASE ALSO KNOW THE CUT-OFF
 DATE FOR THE PALM BEACH COUNTY IMPACT
 FEE INCREASE WAS JAN 12TH, 2006. ONLY
 "PERMIT APPLICATIONS WITH ALL FEES PAID
 BEFORE 5PM ON JAN 12TH WOULD BE UNDER
 THE OLD FEE SCHEDULE.
 *************************************
  
  
 1)NOTE: PLANS SUBMITTED FOR PLAN REVIEW
 UNDER ONE SINGLE MULTI-FAMILY BLDG,
 HOWEVER ELECTRICAL SERVICES SEEM TO
 INDICATE THE UNIT WILL BE A FEE-SIMPLE
 "TOWNHOUSE". ?? COULD NOT LOCATE ANY
 PROPERTY LINES ON SITE PLAN OR ANY
 INDICATTION OF SUCH. PLEASE SEE 230.2,
 ONLY ONE ELECTRICAL SERVICE WILL BE
 PERMITTED. PLEASE ALSO SEE OTHER
 COMMENTS IF INDEED EACH UNIT WILL BE
 SEPARATED BY PROPERTY LINES AND A 4HR
 FIRE WALL. PLEASE SEE 2004 FBC
 DEFINITIONS FOR "FIREWALL".
 PLEASE REVISE ELECTRICAL SERVICE PLANS
 AS NEEDED DEPENDING ON WHAT TYPE FO
 BLDG.
 ** PLEASE KNOW, IF BLDG(S) DO BECOME
 INDIVIDUALLY OWNED , WITH SEPARATE PCN
 NUMBERS ETC, THEN EACH UNIT WOULD BE A
 SEPARATEPERMIT APPLICATION WITH
 SEPARATE PLANS AND FEES.
 THIS WOULD AFFECT COMMENT #3 FOR THE
 DESIGN PROFESSIONAL REQUIREMENT.
 ** PLEASE SEE NOTE #4 FOR ADDRESSING OF
 BLDG.
  
 2)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION ON TITLE BLCOKS FOR
 ARCHITECTUAL FIRM AS SHOWN. PLEASE SEE
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004
 AND FS 481.219 WHICH REQUIRES THE
 CERTIFICATE OF AUTHORIZATION NUMEBR ON
 SAID TITLE BLOCK.
 PLEASE KNOW THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMET IS MADE BY OTHER REVIEWER(S).
 PLEASE SEE NEXT COMMENT AS THIS WILL
 AFFECT ELECTRICAL SHEETS.
  
 3)NOTE: PLEASE SEE FS 471.003(2)(H)
 WHICH REQUIRES THE ELECTRICAL PLANS TO
 BE DONE BY ANY ENGINEER.
 PLEASE ADJUST AS NESSESARY.
  
 4)NOTE: PLEASE SEE NOTES FROM ZONING AND
 ADDRESSING AS BLDG SEEM TO CONTAIN THE
 SMALL PORTION OF THE BLDG ON LAKE AVE
 WHICH WOULD BE THE ADDRESS AS LISTED ON
 PLANS. PLEASE SEE COMMENT #1, IF BLDG
 CHNAGES, THEN SEPARATE ADDRESSES WOULD
 BE APPLIED AND TITLE BLOCK WOULD BE
 ADJUSTED.
  
 5)NOTE: PLEASE SEE PLANS SHALL INDICATE
 THE CURRENT CODES IN EFFECT. PLEASE SEE
 THIS HAS NOT BEEN SUBMITTED FOR PERMIT
 AS OF YET AND THEREFORE DEPENDING ON
 WHEN THAT HAPPENS, THE 2005 NEC SHOULD
 BE ADOPTED IN THE MONTHS TO COME.
 PLEASE SEE THE CURRENT CODE IS THE 2004
 FBC. PLEASE SEE PLANS SHALL REFERENCE
 THE CURRENT NFPA-101 2003, NFPA-72 2002
 , AND 2002 NFPA-70 (NEC). PLEASE SEE
 REDLINED LOCATIONS ON THE PLANS WHERE
 THERE ARE REFERENCES TO THE "1996"
 AND "1999" NEC. PLEASE KNOW, AS OF JULY
 1ST, 2003 THE STATE OF FLORIDA ADOPTED
 THE 2002 NEC.
 PLEASE ADJUST LOCATIONS AND REQUIREMENTS
 AS NEEDED.
 PLEASE OTHER COMMENTS AFFECT BY THE CODE
 CHANGES BELOW.
  
 6)NOTE: PLEASE INDICATE ALL CIRCUTING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
  
 7)NOTE: PLEASE SEE MISSING FOOTER STEEL
 TO BE PART OF THE GROUNDING ELECTRODE
 SYSTEM AS REQUIRED PER 250.50. PLANS REF
 250.83C(1996).
  
 8)NOTE: PLEASE LIST THE REQUIREDARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210.12 (2002) PLEASE SEE
 SD'S ARE BEING SHOWN AS CIRCUITED TO THE
 BATH LIGHTING CIRCUIT ON PANEL SCHEDULE,
 THIS IS OK, HOWEVER PLEASE KNOW ARC
 FAULT BRKR WOULD THEN BE REQUIRED.
 SD'S MAY BE CIRCUTED TO A BEDRM CIRCUIT.
  
 9)NOTE: PLEASE SEE IF PLANS DO BECOME
 INDIVIDUAL UNITS AND SEPARATE SERVICES
 ARE PERMITTED, PLEASE SEE RISER SHOWS AN
 "EQUIPMENT GROUNDING CONDUCTOR" FROM THE
 METER TO THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6, AS THE EQUIPMENT
 GROUNDING CONDUCTOR IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 10)NOTE: PLEASE PROVIDE A NOTE ON PLANS
 WITH REFERENCE TO THE MIN CLEARNECES
 REQUIRED FOR SD'S AND PLACEMENT PER
 NFPA-72 2002 11.8.3.5
  
 11)NOTE: PLEASE SEE REDLINED PLANS FOR
 MISSINF RECEPTS PER 210.52 FOR 2' OR
 MORE OF WALL SPACE.
  
 12)NOTE: PLEASE CONFIRM A/C CU
 LOCATIONS, AS THESE APPEAR TO BE LOCATED
 IN AN AREA ON 2N FLR BALCONY? THIS ARE
 APPEARS MAYBE TO BE ENCLOSED?
  
 13)NOTE: PLEASE SEE MISSING LT AT ENTRY
 REQUIRED PER 210.70,LS 101 7.8.
  
 14)NOTE: PLEASE SEE RECEPTS LOCATED IN
 LAUNDRY ROOM OTHER THAN WASHER, ARE
 REQUIRED TO BE GFI PER 210.8A
  
 15)NOTE: PLEASE SEE MISSING ELECTRICAL
 DEVICES FOR WASHER AND DRYER ON UNIT BL.
 215.5
  
 16)NOTE: PLEASE BE SURE TO CORRELATE
 PLANS WITH WHAT TYPE OF SERVICE IS GOING
 TO BE INSTALLED, PLEASE BE SURE
 EQUIPMENT(METER, MAINS ETC) ARE SHOWN ON
 PLANS AS WELL AS RISER.
 215.5
  
 17)NOTE: PLEASE SEE WHIRLPOOL TUB IS
 LISTED AS OPTIONAL ON PANEL SCHEDULE
 ALONG WITH ALARM PANEL. PLEASE SEE THESE
 LOCATIONS FOR DEVICES NEED TO BE SHOWN
 ON PLASN FOR REVIEW. ACCESS PANEL FOR
 GFI AND LOCATION OF POSSISBLE FUTURE
 ALARAM PANEL NEEDS TO BE VERIFIED.
 ** PLEASE KNOW, ANY ELECTRICAL DEVICES
 ETC SHOWN AS "OPTIONAL" ON PLANS SHALL
 BE REVISED AND SUBMITTED FOR REVIEW AND
 TO BE ON JOBSITE BEFORE ROUGH**
  
 18)NOTE: PLEASE SEE UNIT "BL", WHICH
 APPEARS TO SHOW ELECTRICAL FOR ELEVATOR
 UNDER STAIRS WITH NO ACCESS ETC.
 110.26 , 210.70
  
 19)NOTE: PLEASE SEE IF UNITS DO COME IN
 AS INDIVIDUAL AND ARE DONE BY THE
 ARCHITECT, PLEASE PROVIDE A SIGNED,
 DATED AND SEALED LETTER FOR VERIFICATION
 OF LEGAL SIGNATURE AS PLANS APPEAR TO BE
  
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 ** PLEASE SEE BLDG COMMENTS WITH RESPECT
 TO PRODUCT APPROVALS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-01-24 00:00:00IN ELEC FOR REVIEW, PLAN REVIEW IN
 PROGRESS.
 PLANS WILL BE UNSAT,NOTES TO FOLLOW.