| 2006-01-25 00:00:00 | REVIEW |
| | ********* UNSAT ************* |
| | |
| | *************************************** |
| | PLEASE KNOW, PLANS HAVE ONLY BEEN |
| | SUBMITTED FOR "PLAN REVIEW " AND NOT FOR |
| | PERMIT. PLEASE ALSO KNOW THE CUT-OFF |
| | DATE FOR THE PALM BEACH COUNTY IMPACT |
| | FEE INCREASE WAS JAN 12TH, 2006. ONLY |
| | "PERMIT APPLICATIONS WITH ALL FEES PAID |
| | BEFORE 5PM ON JAN 12TH WOULD BE UNDER |
| | THE OLD FEE SCHEDULE. |
| | ************************************* |
| | |
| | |
| | 1)NOTE: PLANS SUBMITTED FOR PLAN REVIEW |
| | UNDER ONE SINGLE MULTI-FAMILY BLDG, |
| | HOWEVER ELECTRICAL SERVICES SEEM TO |
| | INDICATE THE UNIT WILL BE A FEE-SIMPLE |
| | "TOWNHOUSE". ?? COULD NOT LOCATE ANY |
| | PROPERTY LINES ON SITE PLAN OR ANY |
| | INDICATTION OF SUCH. PLEASE SEE 230.2, |
| | ONLY ONE ELECTRICAL SERVICE WILL BE |
| | PERMITTED. PLEASE ALSO SEE OTHER |
| | COMMENTS IF INDEED EACH UNIT WILL BE |
| | SEPARATED BY PROPERTY LINES AND A 4HR |
| | FIRE WALL. PLEASE SEE 2004 FBC |
| | DEFINITIONS FOR "FIREWALL". |
| | PLEASE REVISE ELECTRICAL SERVICE PLANS |
| | AS NEEDED DEPENDING ON WHAT TYPE FO |
| | BLDG. |
| | ** PLEASE KNOW, IF BLDG(S) DO BECOME |
| | INDIVIDUALLY OWNED , WITH SEPARATE PCN |
| | NUMBERS ETC, THEN EACH UNIT WOULD BE A |
| | SEPARATEPERMIT APPLICATION WITH |
| | SEPARATE PLANS AND FEES. |
| | THIS WOULD AFFECT COMMENT #3 FOR THE |
| | DESIGN PROFESSIONAL REQUIREMENT. |
| | ** PLEASE SEE NOTE #4 FOR ADDRESSING OF |
| | BLDG. |
| | |
| | 2)NOTE: PLEASE SEE MISSING LICENSE |
| | INFORMATION ON TITLE BLCOKS FOR |
| | ARCHITECTUAL FIRM AS SHOWN. PLEASE SEE |
| | FLORIDA ADMINISTRATIVE CODE 61G1-16.004 |
| | AND FS 481.219 WHICH REQUIRES THE |
| | CERTIFICATE OF AUTHORIZATION NUMEBR ON |
| | SAID TITLE BLOCK. |
| | PLEASE KNOW THIS IS REQUIRED FOR ALL |
| | SHEETS AND FOR ALL TRADES WHETHER OR NOT |
| | COMMET IS MADE BY OTHER REVIEWER(S). |
| | PLEASE SEE NEXT COMMENT AS THIS WILL |
| | AFFECT ELECTRICAL SHEETS. |
| | |
| | 3)NOTE: PLEASE SEE FS 471.003(2)(H) |
| | WHICH REQUIRES THE ELECTRICAL PLANS TO |
| | BE DONE BY ANY ENGINEER. |
| | PLEASE ADJUST AS NESSESARY. |
| | |
| | 4)NOTE: PLEASE SEE NOTES FROM ZONING AND |
| | ADDRESSING AS BLDG SEEM TO CONTAIN THE |
| | SMALL PORTION OF THE BLDG ON LAKE AVE |
| | WHICH WOULD BE THE ADDRESS AS LISTED ON |
| | PLANS. PLEASE SEE COMMENT #1, IF BLDG |
| | CHNAGES, THEN SEPARATE ADDRESSES WOULD |
| | BE APPLIED AND TITLE BLOCK WOULD BE |
| | ADJUSTED. |
| | |
| | 5)NOTE: PLEASE SEE PLANS SHALL INDICATE |
| | THE CURRENT CODES IN EFFECT. PLEASE SEE |
| | THIS HAS NOT BEEN SUBMITTED FOR PERMIT |
| | AS OF YET AND THEREFORE DEPENDING ON |
| | WHEN THAT HAPPENS, THE 2005 NEC SHOULD |
| | BE ADOPTED IN THE MONTHS TO COME. |
| | PLEASE SEE THE CURRENT CODE IS THE 2004 |
| | FBC. PLEASE SEE PLANS SHALL REFERENCE |
| | THE CURRENT NFPA-101 2003, NFPA-72 2002 |
| | , AND 2002 NFPA-70 (NEC). PLEASE SEE |
| | REDLINED LOCATIONS ON THE PLANS WHERE |
| | THERE ARE REFERENCES TO THE "1996" |
| | AND "1999" NEC. PLEASE KNOW, AS OF JULY |
| | 1ST, 2003 THE STATE OF FLORIDA ADOPTED |
| | THE 2002 NEC. |
| | PLEASE ADJUST LOCATIONS AND REQUIREMENTS |
| | AS NEEDED. |
| | PLEASE OTHER COMMENTS AFFECT BY THE CODE |
| | CHANGES BELOW. |
| | |
| | 6)NOTE: PLEASE INDICATE ALL CIRCUTING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULES. |
| | |
| | 7)NOTE: PLEASE SEE MISSING FOOTER STEEL |
| | TO BE PART OF THE GROUNDING ELECTRODE |
| | SYSTEM AS REQUIRED PER 250.50. PLANS REF |
| | 250.83C(1996). |
| | |
| | 8)NOTE: PLEASE LIST THE REQUIREDARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE PER 210.12 (2002) PLEASE SEE |
| | SD'S ARE BEING SHOWN AS CIRCUITED TO THE |
| | BATH LIGHTING CIRCUIT ON PANEL SCHEDULE, |
| | THIS IS OK, HOWEVER PLEASE KNOW ARC |
| | FAULT BRKR WOULD THEN BE REQUIRED. |
| | SD'S MAY BE CIRCUTED TO A BEDRM CIRCUIT. |
| | |
| | 9)NOTE: PLEASE SEE IF PLANS DO BECOME |
| | INDIVIDUAL UNITS AND SEPARATE SERVICES |
| | ARE PERMITTED, PLEASE SEE RISER SHOWS AN |
| | "EQUIPMENT GROUNDING CONDUCTOR" FROM THE |
| | METER TO THE FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE 250.6, AS THE EQUIPMENT |
| | GROUNDING CONDUCTOR IS ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | |
| | 10)NOTE: PLEASE PROVIDE A NOTE ON PLANS |
| | WITH REFERENCE TO THE MIN CLEARNECES |
| | REQUIRED FOR SD'S AND PLACEMENT PER |
| | NFPA-72 2002 11.8.3.5 |
| | |
| | 11)NOTE: PLEASE SEE REDLINED PLANS FOR |
| | MISSINF RECEPTS PER 210.52 FOR 2' OR |
| | MORE OF WALL SPACE. |
| | |
| | 12)NOTE: PLEASE CONFIRM A/C CU |
| | LOCATIONS, AS THESE APPEAR TO BE LOCATED |
| | IN AN AREA ON 2N FLR BALCONY? THIS ARE |
| | APPEARS MAYBE TO BE ENCLOSED? |
| | |
| | 13)NOTE: PLEASE SEE MISSING LT AT ENTRY |
| | REQUIRED PER 210.70,LS 101 7.8. |
| | |
| | 14)NOTE: PLEASE SEE RECEPTS LOCATED IN |
| | LAUNDRY ROOM OTHER THAN WASHER, ARE |
| | REQUIRED TO BE GFI PER 210.8A |
| | |
| | 15)NOTE: PLEASE SEE MISSING ELECTRICAL |
| | DEVICES FOR WASHER AND DRYER ON UNIT BL. |
| | 215.5 |
| | |
| | 16)NOTE: PLEASE BE SURE TO CORRELATE |
| | PLANS WITH WHAT TYPE OF SERVICE IS GOING |
| | TO BE INSTALLED, PLEASE BE SURE |
| | EQUIPMENT(METER, MAINS ETC) ARE SHOWN ON |
| | PLANS AS WELL AS RISER. |
| | 215.5 |
| | |
| | 17)NOTE: PLEASE SEE WHIRLPOOL TUB IS |
| | LISTED AS OPTIONAL ON PANEL SCHEDULE |
| | ALONG WITH ALARM PANEL. PLEASE SEE THESE |
| | LOCATIONS FOR DEVICES NEED TO BE SHOWN |
| | ON PLASN FOR REVIEW. ACCESS PANEL FOR |
| | GFI AND LOCATION OF POSSISBLE FUTURE |
| | ALARAM PANEL NEEDS TO BE VERIFIED. |
| | ** PLEASE KNOW, ANY ELECTRICAL DEVICES |
| | ETC SHOWN AS "OPTIONAL" ON PLANS SHALL |
| | BE REVISED AND SUBMITTED FOR REVIEW AND |
| | TO BE ON JOBSITE BEFORE ROUGH** |
| | |
| | 18)NOTE: PLEASE SEE UNIT "BL", WHICH |
| | APPEARS TO SHOW ELECTRICAL FOR ELEVATOR |
| | UNDER STAIRS WITH NO ACCESS ETC. |
| | 110.26 , 210.70 |
| | |
| | 19)NOTE: PLEASE SEE IF UNITS DO COME IN |
| | AS INDIVIDUAL AND ARE DONE BY THE |
| | ARCHITECT, PLEASE PROVIDE A SIGNED, |
| | DATED AND SEALED LETTER FOR VERIFICATION |
| | OF LEGAL SIGNATURE AS PLANS APPEAR TO BE |
| | |
| | |
| | ** PLEASE SEE ANY OTHER COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO SETS FOR |
| | REVIEW AND STAMPING. |
| | ONE COPY OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | ** PLEASE SEE BLDG COMMENTS WITH RESPECT |
| | TO PRODUCT APPROVALS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2006-01-24 00:00:00 | IN ELEC FOR REVIEW, PLAN REVIEW IN |
| | PROGRESS. |
| | PLANS WILL BE UNSAT,NOTES TO FOLLOW. |