Plan Review Notes
Plan Review Notes For Permit 05120948
Permit Number 05120948
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-15 00:00:0005120948
  
 1) FL STATUTES. 713.13. NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK
 OF THE COURT BEFORE A PERMIT WILL BE
 ISSUED. NOTE: 713.13(2) IF THE WORK
 DESCRIBED IN THE NOTICE OF COMMENCEMENT
 IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERFORMED IN A MANNER SO
 AS NOT TO ADVERSELY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER. THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCEL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALLY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 4) (2004 FBC) 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, AND RULES AND
 REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 5) FBC.1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 6) EGRESS WINDOWS (2ND/3RD FLOORS)
 PROVIDE THE MANUFACTURERS CUT SHEETS
 WITH NET CLEAR OPENING SIZES MINIMUM OF
 5.7 SQ FT.
 R310.1.1
  
 7)R310.4 THE TEMPORARY INSTALLATION OR
 CLOSURE OF STORM SHUTTERS, PANELS, AND
 OTHER APPROVED HURRICANE PROTECTION
 DEVICES SHALL BE PERMITTED ON EMERGENCY
 ESCAPE AND RESCUE OPENINGS DURING THE
 THREAT OF A STORM. SUCH DEVICES SHALL
 NOT BE REQUIRED TO COMPLY WITH THE
 OPERATIONAL CONSTRAINTS OF SECTION
 R310.1.4 . WHILE SUCH PROTECTION IS
 PROVIDED, AT LEAST ONE MEANS OF ESCAPE
 FROM THE DWELLING OR DWELLING UNIT SHALL
 BE PROVIDED. THE MEANS OF ESCAPE SHALL
 BE WITHIN THE FIRST FLOOR OF THE
 DWELLING OR DWELLING UNIT AND SHALL NOT
 BE LOCATED WITHIN A GARAGE. OCCUPANTS IN
 ANY PART OF THE DWELLING OR DWELLING
 UNIT SHALL BE ABLE TO ACCESS THE MEANS
 OF ESCAPE WITHOUT PASSING THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
  
 8) ) PROVIDE STORM PANEL INFORMATION
 INSTALLATION SCHEDULE AND KEY PLANWITH
 THE SPECIFIC ANCHORS & MOUNTING DETAILS
 FOR ALL NON-IMPACT GLAZING.
  
 9)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 LOADS SHALL BE SHOWN, REGARDLESS OF
 WHETHER WIND LOADS GOVERN
 THE DESIGN OF THE LATERAL-FORCE
 ?RESISTING SYSTEM OF THE BUILDING.
 1) - BASIC WIND SPEED, MPH
 2) - WIND IMPORTANCE FACTOR, & BUILDING
 CLASSIFICATION.
 3) - WIND EXPOSURE
 4) - INTERNAL PRESSURE COEFFICIENT.
 5 ) - COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 10): THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
 A) WINDOWS FIXED AND OPERATABLE
 B) EXTERIOR DOORS SWING AND FIXED
 C) MULLIONS IF ANY
 D) STORM SHUTTERS
 E) ROOF ASSEMBLY
 F) TRUSS ANCHORS,
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL
 OR SITE SPECIFIC FORM PER RULE 9B-72.
 SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11) MULTISTORY TOWNHOUSES ARE COVERED BY
 THE REQUIREMENTS OF FAIR HOUSING
 ACCESSIBILITY GUIDELINES IF THERE ARE
 FOUR OR MORE UNITS IN THE BUILDING AND
 THE BUILDING CONTAINS ONE OR MORE
 ELEVATORS. QUESTIONS AND ANSWERS ABOUT
 THE GUIDELINES, 59 FR 33362-33368, JUNE
 28, 1994, QUESTION 13 AND SEE
 WWW.FAIRHOUSIGFIRST.ORG/FAQ/TOWNHOUSES.H
  
 12) THE BATHROOM DETAIL ON SHEET D-3
 DOES NOT MATCH ANY BATHROOM DETAIL ON
 THE FLOOR PLANS. PLEASE CLARIFY. ALSO
 SHOW THE DETAIL DRAWING FOR GRAB
 BAR BACKING. SEE FHA. PAGE 6.4/6.5/6.12
  
 13)A 30X48? CLEAR FLOOR SPACE MUST BE
 PROVIDED AT SHOWER STALLS, PARALLEL TO
 THE FIXTURE AND FLUSH WITH THE CONTROL
 WALL. TOILET CANNOT BE IN THE CLEAR
 FLOOR SPACE. ALSO SHOW THE CLEAR FLOOR
 SPACE FOR ALL BATHROOM FIXTURES.
 SEE PAGES 7.43 ? 7.56.
  
 14) SHEET D-1 INDICATES THE 2ND AND 3RD
 BEING POURED AS PART OF THE 2HR RATED
 WALL.THE COMMON WALL FOR TOWNHOUSES
 SHALL BE CONTINUOUS FROM THE FOUNDATION
 TO THE UNDERSIDE OF THE ROOF SHEATHING,
 DECK OR SLAB AND SHALL EXTEND THE FULL
 LENGTH OF THE COMMON WALL INCLUDING
 WALLS EXTENDING THROUGH AND SEPARATING
 ATTACHED ACCESSORY STRUCTURES. R317.2.1.
 THIS SHEET NEEDS TO BE SEALED AND
 SIGNED. (D-1)
  
 15) A DETAIL DRAWING OF THE FLOOR
 CONNECTION TO THE COMMON WALL IS
 REQUIRED SHOWING ALL THE MATERIALS TO BE
 USED. ALSO STATE THE LIVE AND DEAD LOAD
 OF EACH FLOOR, AND THE SPACING OF THE
 TRUSSES. SUBMIT THE INFORMATION FOR THE
 FLOOR FROM AMERICAN FLOOR SYSTEM.
  
 16) R806.1 ENCLOSED ATTICS AND ENCLOSED
 RAFTER SPACES FORMED WHERE CEILINGS ARE
 APPLIED DIRECTLY TO THE ROOF RAFTERS
 SHALL HAVE CROSS VENTILATION.SHOW
 INFORMATION ON DRAWINGS. ALSO SEE FBC
 1203 FOR MORE INFORMATION
  
 17) FBC 2320.3.1.2 GROUPS R1, R2 AND R4
 OCCUPANCIES. IN FLOOR-CEILING ASSEMBLIES
 SEPARATING USABLE SPACES INTO TWO OR
 MORE APPROXIMATE AREAS WITH NO AREA
 GREATER THAN 500 SQUARE FEET (46.5 M 2
 ). DRAFTSTOPPING SHALL BE PROVIDED
 PARALLEL TO THE MAIN FRAMING MEMBERS IN
 THE FLOOR-CEILING ASSEMBLIES OF
 MULTIPLE-FAMILY DWELLINGS, MOTELS AND
 HOTELS ABOVE AND IN LINE WITH THE TENANT
 SEPARATION, WHEN TENANT SEPARATION WALLS
 DO NOT EXTEND TO THE FLOOR SHEATHING
 ABOVE.
  
 18) R324.1 SPRINKLER SYSTEM REQUIREMENTS
 FOR BUILDINGS THREE STORIES OR MORE IN
 HEIGHT. NFPA 101, AS REGARDING THE
 REQUIREMENTS FOR FIRE PROTECTION
 SPRINKLERS, IS APPLICABLE TO ALL
 MULTIPLE-FAMILY RESIDENTIAL BUILDINGS,
 WHETHER DESIGNATED AS TOWNHOUSES,
 CONDOMINIUMS, APARTMENT HOUSES,
 TENEMENTS, GARDEN APARTMENTS OR BY ANY
 OTHER NAME. THE ATTORNEY GENERAL HAS
 DETERMINED THAT FOR THE PURPOSE OF THE
 FIRE PROTECTION SPRINKLER REQUIREMENTS
 IN SECTION 553.895(2), FLORIDA STATUTES,
 TOWNHOUSES THAT ARE THREE OR MORE
 STORIES TALL AND CONSIST OF THREE OR
 MORE UNITS TOGETHER ARE MULTIPLE-FAMILY
 DWELLINGS.
  
 19) R613.6.2 WINDOW AND DOOR BUCKS.
 UNLESS OTHERWISE TESTED, BUCKS SHALL
 EXTEND BEYOND THE INTERIOR FACE OF THE
 WINDOW OR DOOR FRAME SUCH THAT FULL
 SUPPORT OF THE FRAME IS PROVIDED.
 SEE SHEET D-4 #5.
  
 20) SHEETS S-3 / S-3.1 DO NOT REFLECT
 THE SECOND FLOOR AS STATED ON THE
 DRAWING INDEX SHEET. THESE SHEETS
 REFLECT THE 3RD FLOOR. THE 2ND FLOOR
 STRUCTURAL PLANS ARE MISSING FROM THE
 PACKAGE. ADJUST THE SHEETS TO SHOW THE
 CORRECT FLOOR PLANS.
  
 21) SHEET A-9 REFERS TO SHEET (D-6 # 2),
 HOWEVER, THERE IS NO #2 DETAIL ON SHEET
 D-6. PLEASE MODIFY PLANS ACCORDINGLY TO
 REFLECT THE CORRECT DETAIL DRAWINGS.
 DETAIL DRAWINGS
 SHALL SHOW ALL DIMENSIONS ON THE
 DRAWINGS. WHAT IS THE WIDTH, LENGTH AND
 HEIGHT OF THE BALCONY? ALSO WHAT TYPE OF
 MATERIAL IS THE BRACKET UNDER THE
 BALCONY MADE OFF? SHOW THE ATTACHMENT
 DETAILS OF EACH OVERHANG AT THE
 BALCONIES.
  
 22) SHOULD THERE BE A SHEET 5-5 OR S-5?
 INDICATE ON THE STRUCTURAL SHEETS THE
 DETAILS SHOWN ON SHEETS 5-5 AND SHEET
 S-6.
  
 23) SUBMIT AN ABBREVIATION SHEET WITH
 THE MEANING OF ALL ABBREVIATIONS ON THE
 DRAWINGS.
  
 24) 11-4.6.2 LOCATION.
 ACCESSIBLE PARKING SPACES SERVING A
 PARTICULAR BUILDING SHALL BE LOCATED ON
 THE SHORTEST SAFELY ACCESSIBLE ROUTE OF
 TRAVEL FROM ADJACENT PARKING TO AN
 ACCESSIBLE ENTRANCE. IN PARKING
 FACILITIES THAT DO NOT SERVE A
 PARTICULAR BUILDING, ACCESSIBLE PARKING
 SHALL BE LOCATED ON THE SHORTEST
 ACCESSIBLE ROUTE OF TRAVEL TO AN
 ACCESSIBLE PEDESTRIAN ENTRANCE OF THE
 PARKING FACILITY. IN BUILDINGS WITH
 MULTIPLE ACCESSIBLE ENTRANCES WITH
 ADJACENT PARKING, ACCESSIBLE PARKING
 SPACES SHALL BE DISPERSED AND LOCATED
 CLOSEST TO THE ACCESSIBLE ENTRANCES.
 EACH PARKING SPACE MUST BE NO LESS THAN
 12 FEET (3658 MM) WIDE.
 (1) ALL SPACES MUST BE LOCATED ON AN
 ACCESSIBLE ROUTE NO LESS THAN 44 INCHES
 (1118 MM) WIDE SO THAT USERS WILL NOT BE
 COMPELLED TO WALK OR WHEEL BEHIND PARKED
 VEHICLES. SHOW THE ACCESSIBLE ROUTE TO
 BUILDING #1. SEE ADDITIONAL INFORMATION
 IN PACKAGE.
  
 25) R312.2 GUARD OPENING LIMITATIONS.
 REQUIRED GUARDS ON OPEN SIDES OF
 STAIRWAYS, RAISED FLOOR AREAS, BALCONIES
 AND PORCHES SHALL HAVE INTERMEDIATE
 RAILS OR ORNAMENTAL CLOSURES WHICH DO
 NOT ALLOW PASSAGE OF A SPHERE 4 INCHES
 (102MM) OR MORE IN DIAMETER.
  
 26) R311.5.2 HEADROOM.
 THE MINIMUM HEADROOM IN ALL PARTS OF THE
 STAIRWAY SHALL NOT BE LESS THAN 6 FEET 8
 INCHES (2036 MM) MEASURED VERTICALLY
 FROM THE SLOPED PLANE ADJOINING THE
 TREAD NOSING OR FROM THE FLOOR SURFACE
 OF THE LANDING OR PLATFORM. SEE PAGES
 A-9 / A-10.
  
 27) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST
 FOR RESIDENT BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY S. 553.79(5)
 FLORIDA STATUTES TO THE MIN- IMUM
 INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
 SEE APPLICATION IN PACKAGE.
  
 28) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 MYRON JACOBS
 BUILDING PLANS EXAMINER
 TEL: (561)805-6726
  
  
  
2006-03-11 00:00:00 
  
  
  
  
  
  