2006-06-27 00:00:00***DENIED***
  
 PLEASE NOTE THAT SOME COMMENTS FROM LAST
 FIRE REVIEW HAVE NOT BEEN ADDRESSED.
  
 1) NO FIRE PROTECTION SHEETS WERE
 INCLUDED WITH THIS SUBMITTAL. BUILDINGS
 THAT ARE REQUIRED TO BE FIRE SPRINKLER
 PROTECTED SHALL HAVE FP SHEETS SUBMITTED
 WITH ACHITECTUAL PLANS FOR REVIEW.
 SEPARATE SHOP DRAWINGS AND PERMIT IS
 REQUIRED PRIOR TO INSTALLATION OF
 SYSTEM.
  
 2) OK
  
 3) OK
  
 4) ELEVATORS SHALL COMPLY WITH ASME
 A17.1.
  
 5) IN REGARDS TO ADDRESS REQUIREMENTS,
 SHT A-8 ILLUSTRATES 3" HAS BEEN CHANGED
 TO 6". PLEASE EXPLAIN.
  
 6) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 7) MULTI-PURPOSE FIRE EXTINGUISHERS ARE
 REQUIRED FOR EACH LIVING UNIT, NOT TO
 EXCEED A TRAVEL DISTANCE OF 75'.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722