| Plan Review Notes For Permit 05120947 |
| Permit Number |
05120947 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-27 00:00:00 | ***DENIED*** | | | | | | PLEASE NOTE THAT SOME COMMENTS FROM LAST | | | FIRE REVIEW HAVE NOT BEEN ADDRESSED. | | | | | | 1) NO FIRE PROTECTION SHEETS WERE | | | INCLUDED WITH THIS SUBMITTAL. BUILDINGS | | | THAT ARE REQUIRED TO BE FIRE SPRINKLER | | | PROTECTED SHALL HAVE FP SHEETS SUBMITTED | | | WITH ACHITECTUAL PLANS FOR REVIEW. | | | SEPARATE SHOP DRAWINGS AND PERMIT IS | | | REQUIRED PRIOR TO INSTALLATION OF | | | SYSTEM. | | | | | | 2) OK | | | | | | 3) OK | | | | | | 4) ELEVATORS SHALL COMPLY WITH ASME | | | A17.1. | | | | | | 5) IN REGARDS TO ADDRESS REQUIREMENTS, | | | SHT A-8 ILLUSTRATES 3" HAS BEEN CHANGED | | | TO 6". PLEASE EXPLAIN. | | | | | | 6) CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 7) MULTI-PURPOSE FIRE EXTINGUISHERS ARE | | | REQUIRED FOR EACH LIVING UNIT, NOT TO | | | EXCEED A TRAVEL DISTANCE OF 75'. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|