| Date |
Text |
| 2006-02-15 00:00:00 | -----------------DENIED----------------- |
| | 1.AHU'S WITH A DESIGN CAPACITY EXCEEDING |
| | 2000 CFM REQUIRE A DUCT MOUNTED SMOKE |
| | DETECTOR WITH AUDIBLE/VISUAL |
| | NOTIFICATION PER 2004 FBC,M SEC 606.2.1 |
| | |
| | 2.EXHAUST FAN AND DUCT DETAIL SHOWS A |
| | PITCHED ROOF APPLICATION. PROVIDE DETAIL |
| | FOR FLAT ROOF APPLICATION. |
| | |
| | 3.CONDENSING UNITS ARE SHOWN ON 2ND |
| | FLOOR BALCONIES. ENSURE THAT PROPER |
| | CLEARANCE FOR AIR FLOW AND SERVICE CAN |
| | BE PROVIDED. |
| | |
| | 4.PROVIDE TWO COPIES OF ENERGY |
| | CALCULATIONS PER 2004 FBC CH 13 SEC |
| | 103.2 |
| | |
| | 5.DRYER SCHEDULE INDICATES SIDE WALL |
| | DISCHARGE OF DRYER EXHAUST. PLAN |
| | INDICATES ROOF DISCHARGE.PLEASE SHOW |
| | DETAIL FOR ROOF DISCHARGE OF DRYER |
| | EXHAUST. |
| | |
| | 6.PAGE D1 SHOWS DETAIL OF 1 HOUR RATED |
| | ATTIC ACCESS.DOES THIS MEAN THE 3RD |
| | FLOOR CEILING IS RATED? PROVIDE UL |
| | LISTING OF RATED ASSEMBLY. |
| | |
| | 7.PLAN INDICATES RATED ASSEMBLIES AT |
| | GARAGE CEILING AND WALL SEPARATING |
| | GARAGE FROM RESIDENCE. PLEASE PROVIDE UL |
| | LISTING OF RATED ASSEMBLY. |
| | |
| | 8.PLAN INDICATES AHU LOCATED IN GARAGE. |
| | THIS WOULD MEAN THE SUPPLY AND RETURN |
| | DUCTS WILL PENETRATE THE RATED CEILING |
| | ABOVE THE GARAGE.PLEASE PROVIDE DETAIL |
| | FOR A RATED PENETRATION WITH UL LISTED |
| | ASSEMBLY PER 2004 FBC,M SEC 607.5. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT |
| | RONALD J REGUEIRO AT 561.805.6734 OR |
| | [email protected] |