2006-02-15 00:00:00-----------------DENIED-----------------
 1.AHU'S WITH A DESIGN CAPACITY EXCEEDING
 2000 CFM REQUIRE A DUCT MOUNTED SMOKE
 DETECTOR WITH AUDIBLE/VISUAL
 NOTIFICATION PER 2004 FBC,M SEC 606.2.1
  
 2.EXHAUST FAN AND DUCT DETAIL SHOWS A
 PITCHED ROOF APPLICATION. PROVIDE DETAIL
 FOR FLAT ROOF APPLICATION.
  
 3.CONDENSING UNITS ARE SHOWN ON 2ND
 FLOOR BALCONIES. ENSURE THAT PROPER
 CLEARANCE FOR AIR FLOW AND SERVICE CAN
 BE PROVIDED.
  
 4.PROVIDE TWO COPIES OF ENERGY
 CALCULATIONS PER 2004 FBC CH 13 SEC
 103.2
  
 5.DRYER SCHEDULE INDICATES SIDE WALL
 DISCHARGE OF DRYER EXHAUST. PLAN
 INDICATES ROOF DISCHARGE.PLEASE SHOW
 DETAIL FOR ROOF DISCHARGE OF DRYER
 EXHAUST.
  
 6.PAGE D1 SHOWS DETAIL OF 1 HOUR RATED
 ATTIC ACCESS.DOES THIS MEAN THE 3RD
 FLOOR CEILING IS RATED? PROVIDE UL
 LISTING OF RATED ASSEMBLY.
  
 7.PLAN INDICATES RATED ASSEMBLIES AT
 GARAGE CEILING AND WALL SEPARATING
 GARAGE FROM RESIDENCE. PLEASE PROVIDE UL
 LISTING OF RATED ASSEMBLY.
  
 8.PLAN INDICATES AHU LOCATED IN GARAGE.
 THIS WOULD MEAN THE SUPPLY AND RETURN
 DUCTS WILL PENETRATE THE RATED CEILING
 ABOVE THE GARAGE.PLEASE PROVIDE DETAIL
 FOR A RATED PENETRATION WITH UL LISTED
 ASSEMBLY PER 2004 FBC,M SEC 607.5.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 RONALD J REGUEIRO AT 561.805.6734 OR
 [email protected]