| Plan Review Notes For Permit 05120947 |
| Permit Number |
05120947 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-30 00:00:00 | PLAN REVIEW ONLY | | | | | | ******DENIED****** | | | | | | 1) NO FIRE PROTECTION SHEETS WERE | | | INCLUDED WITH THIS SUBMITAL. FS 553.895 | | | REQUIRE BUILDINGS 3 OR MORE STORIES TO | | | BE FIRE SPRINKLERED WITH EXCEPTION OF 1 | | | AND 2 DWELLING UNITS. | | | | | | 2) PLEASE PROVIDE LOCATION OF FIRE | | | HYDRANTS, THAT SHALL BE WET PRIOR TO, | | | DURING AND AFTER CONSTRUCTION. | | | | | | 3) SMOKE DETECTORS TO BE A MINIMUM OF 3' | | | FROM HVAC DIFFUSERS. | | | | | | 4) ELEVATORS TO COMPLY WITH ASME A17.1. | | | | | | 5) ADDRESSES ARE REQUIRED ON UNITS, AND | | | SHALL BE A MINIMUM OF 3" IN HEIGHT AND | | | CONTRASTING TO THE BACKGROUND. | | | | | | 6) CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (561) 805-6722 | | | |
|