Plan Review Notes
Plan Review Notes For Permit 05120947
Permit Number 05120947
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-01-30 00:00:00PLAN REVIEW ONLY
  
 ******DENIED******
  
 1) NO FIRE PROTECTION SHEETS WERE
 INCLUDED WITH THIS SUBMITAL. FS 553.895
 REQUIRE BUILDINGS 3 OR MORE STORIES TO
 BE FIRE SPRINKLERED WITH EXCEPTION OF 1
 AND 2 DWELLING UNITS.
  
 2) PLEASE PROVIDE LOCATION OF FIRE
 HYDRANTS, THAT SHALL BE WET PRIOR TO,
 DURING AND AFTER CONSTRUCTION.
  
 3) SMOKE DETECTORS TO BE A MINIMUM OF 3'
 FROM HVAC DIFFUSERS.
  
 4) ELEVATORS TO COMPLY WITH ASME A17.1.
  
 5) ADDRESSES ARE REQUIRED ON UNITS, AND
 SHALL BE A MINIMUM OF 3" IN HEIGHT AND
 CONTRASTING TO THE BACKGROUND.
  
 6) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722
  