2006-10-14 08:44:22DENIED;
 WHEN PLANS WERE SUBMITED FOR PLAN REVIEW THERE WAS NO
 GAS PLANS. THE GAS PLAN THAT YOU SUBMITED
 AS A REVISION MUST BE SUBMITED WITH A GAS
 APPLICATION SIGNED BY A LICENSED GAS CONTRACTOR.
 CHANGE
 PAGE NUMBER, A PAGE P-3 ALL READY EXISTS.
 THE FOLLOWING CORRECTIONS ARE
 REQUIRED TO THE GAS PLAN BEFORE SUBMITING FOR PERMIT;
 1. 00) AIR CHAMBERS ARE NOT APPROVED.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.A) FBC-2004 FUEL GAS SEC. 404.12
 OUTLET
 CLOSURES: GAS OUTLETS THAT DO NOT CON-
 NECT TO APPLIANCES SHALL BE CAPPED GAS
 TIGHT.SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 IF THERE IS AN EXISTING GAS SYSTEM THAT
 SYSTEM SHOULD BE INCLUDED INTO THE PLAN.