| Plan Review Notes For Permit 05120933 |
| Permit Number |
05120933 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-14 08:44:22 | DENIED; | | | WHEN PLANS WERE SUBMITED FOR PLAN REVIEW THERE WAS NO | | | GAS PLANS. THE GAS PLAN THAT YOU SUBMITED | | | AS A REVISION MUST BE SUBMITED WITH A GAS | | | APPLICATION SIGNED BY A LICENSED GAS CONTRACTOR. | | | CHANGE | | | PAGE NUMBER, A PAGE P-3 ALL READY EXISTS. | | | THE FOLLOWING CORRECTIONS ARE | | | REQUIRED TO THE GAS PLAN BEFORE SUBMITING FOR PERMIT; | | | 1. 00) AIR CHAMBERS ARE NOT APPROVED. | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE.A) FBC-2004 FUEL GAS SEC. 404.12 | | | OUTLET | | | CLOSURES: GAS OUTLETS THAT DO NOT CON- | | | NECT TO APPLIANCES SHALL BE CAPPED GAS | | | TIGHT.SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | IF THERE IS AN EXISTING GAS SYSTEM THAT | | | SYSTEM SHOULD BE INCLUDED INTO THE PLAN. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | | | | | | | | | | | | | | | | | | | | | | . |
|