| 2006-01-23 00:00:00 | 1. WRONG LIFE SAFETY CODE EDITION NOTED | | | ON PLANS. SHOULD READ NFPA 101, 2003 | | | EDITION. | | | | | | 2. ALL CONSTRUCTION, DEMOLITION, AND | | | RENOVATION TO COMPLY WITH NFPA 241. | | | | | | 3. ALL EXITS TO REMAIN CLEAR AND | | | UNOBSTRUCTED WHILE WORK ACTIVITIES ARE | | | OCCURRING. | | | | | | 4. ANY POTENTIAL FIRE WATCH ACTIVITIES | | | MUST BE APPROVED BY THE FIRE MARSHAL OR | | | ASSISTANT FIRE MARSHAL. PLEASE SEE NOTE | | | # 11, ON PAGE E-3. | | | | | | 5. GASOLINE POWERED DEMOLITION OR | | | RENOVATION EQUIPMENT SHALL NOT BE USED | | | INDOORS WITHOUT PROPER VENTILATION. | | | CARBON MONOXIDE DANGERS COULD PRESENT | | | THEMSELVES WITHOUT THE PROPER | | | SAFEGUARDS. | | | | | | 6. FIRE SPRINKLER WORK MUST BE DONE BY A | | | LICENSED FIRE SPRINKLER CONTRACTOR. (2 | | | HEADS) | | | | | | 7. TEMPORARY DUST BARRIERS PLANNED FOR | | | USE MUST MEET MINIMUM FLAME SPREAD | | | CRITERIA. NON FIRE RATED VISQUEEN SHOULD | | | NOT BE USED. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|