Plan Review Notes
Plan Review Notes For Permit 05120843
Permit Number 05120843
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-01-23 00:00:001. WRONG LIFE SAFETY CODE EDITION NOTED
 ON PLANS. SHOULD READ NFPA 101, 2003
 EDITION.
  
 2. ALL CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 3. ALL EXITS TO REMAIN CLEAR AND
 UNOBSTRUCTED WHILE WORK ACTIVITIES ARE
 OCCURRING.
  
 4. ANY POTENTIAL FIRE WATCH ACTIVITIES
 MUST BE APPROVED BY THE FIRE MARSHAL OR
 ASSISTANT FIRE MARSHAL. PLEASE SEE NOTE
 # 11, ON PAGE E-3.
  
 5. GASOLINE POWERED DEMOLITION OR
 RENOVATION EQUIPMENT SHALL NOT BE USED
 INDOORS WITHOUT PROPER VENTILATION.
 CARBON MONOXIDE DANGERS COULD PRESENT
 THEMSELVES WITHOUT THE PROPER
 SAFEGUARDS.
  
 6. FIRE SPRINKLER WORK MUST BE DONE BY A
 LICENSED FIRE SPRINKLER CONTRACTOR. (2
 HEADS)
  
 7. TEMPORARY DUST BARRIERS PLANNED FOR
 USE MUST MEET MINIMUM FLAME SPREAD
 CRITERIA. NON FIRE RATED VISQUEEN SHOULD
 NOT BE USED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709