| Plan Review Notes For Permit 05120836 |
| Permit Number |
05120836 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-02-10 00:00:00 | 700.6 TRANSFER EQUIPMENT. | | | (A) GENERAL. TRANSFER EQUIPMENT, | | | INCLUDING AUTOMATIC TRANSFER SWITCHES, | | | SHALL BE AUTOMATIC, IDENTIFIED FOR | | | EMERGENCY USE, AND APPROVED BY THE | | | AUTHORITY HAVING JURISDICTION. TRANSFER | | | EQUIPMENT SHALL BE DESIGNED AND | | | INSTALLED TO PREVENT THE INADVERTENT | | | INTERCONNECTION OF NORMAL AND EMERGENCY | | | SOURCES OF SUPPLY IN ANY OPERATION OF | | | THE TRANSFER EQUIPMENT. TRANSFER | | | EQUIPMENT AND ELECTRIC POWER PRODUCTION | | | SYSTEMS INSTALLED TO PERMIT OPERATION IN | | | PARALLEL WITH THE NORMAL SOURCE SHALL | | | MEET THE REQUIREMENTS OF ARTICLE 705. | | 2006-02-09 00:00:00 | | | | THE RISER DIAGRAM' S SUBMITTED ARE | | | INCOMPLETE. THEY DO NOT SHOW HOW THE ATS | | | FEEDS THE DISCONNECTS. | | | PLEASE SUBMIT A COMPLETE RISER SHOWING | | | ALL EQUIPMENT, GROUNDING, CONDIUT AND | | | CONDUCTOR SIZES. THE RISER'S (TWO | | | DIFFERENT ONE'S) SHOW THE ATS BEING FED | | | FROM THE GENERATOR WITH A CONDUIT TO THE | | | METER? | | | | | | PLEASE RESUBMIT A CXOMPLETED RISER | | | DIAGRAM (2 COPIES). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|