2006-02-10 00:00:00700.6 TRANSFER EQUIPMENT.
 (A) GENERAL. TRANSFER EQUIPMENT,
 INCLUDING AUTOMATIC TRANSFER SWITCHES,
 SHALL BE AUTOMATIC, IDENTIFIED FOR
 EMERGENCY USE, AND APPROVED BY THE
 AUTHORITY HAVING JURISDICTION. TRANSFER
 EQUIPMENT SHALL BE DESIGNED AND
 INSTALLED TO PREVENT THE INADVERTENT
 INTERCONNECTION OF NORMAL AND EMERGENCY
 SOURCES OF SUPPLY IN ANY OPERATION OF
 THE TRANSFER EQUIPMENT. TRANSFER
 EQUIPMENT AND ELECTRIC POWER PRODUCTION
 SYSTEMS INSTALLED TO PERMIT OPERATION IN
 PARALLEL WITH THE NORMAL SOURCE SHALL
 MEET THE REQUIREMENTS OF ARTICLE 705.
2006-02-09 00:00:00 
 THE RISER DIAGRAM' S SUBMITTED ARE
 INCOMPLETE. THEY DO NOT SHOW HOW THE ATS
 FEEDS THE DISCONNECTS.
 PLEASE SUBMIT A COMPLETE RISER SHOWING
 ALL EQUIPMENT, GROUNDING, CONDIUT AND
 CONDUCTOR SIZES. THE RISER'S (TWO
 DIFFERENT ONE'S) SHOW THE ATS BEING FED
 FROM THE GENERATOR WITH A CONDUIT TO THE
 METER?
  
 PLEASE RESUBMIT A CXOMPLETED RISER
 DIAGRAM (2 COPIES).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  