 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE TOTAL COST OF THE JOB MUST BE
 INCLUDED IN THE VALUATION ON THE
 APPLICATION. THIS INCLUDES THE GENERATOR
 AND ALL EQUIPMENT BEING INSTALLED AND
 LABOR.
  
 2} PLEASE REDRAW THE RISER DIAGRAM TO
 INCLUDE NEW PANELS FOR LOAD SHEDDING.
 ALSO IT ISN'T CLEAR FROM THE DRAWING
 SUBMITTED HOW THE ATS TIES IN.
  
 3} PROVIDE A SITE PLAN INDICATING THE
 LOCATION OF ALL SERVICE AND GENERATOR
 EQUIPMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  