Plan Review Notes
Plan Review Notes For Permit 05120795
Permit Number 05120795
Review Stop M
Sequence Number 2
Notes
Date Text
2006-01-03 00:00:00*** DENIED ***
 1) PLEASE OBSERVE THE SUPPLY AIR CFM'S
 AND RETURN AIR CFM'S AND PROVIDE FOR A
 BALANCED RETURN AIR, PER 2004 FBC/M
 601.4 .
  
 2) PLEASE SEE ELECT. REVIEW NOTE #2 .
  
 3) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.