Plan Review Notes For Permit 05120783
Permit Number 05120783
Review Stop P
Sequence Number 1
Notes
Date Text
2006-01-18 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT CS-1 AVAILABLE CODES AND SITE
 DATA INDICATES DESIGNED TO FBC-2001. AS
 OF 10-1-05 THE FBC-2004 HAS BEEN IN
 EFFECT. PLEASE CHANGE CODE REFERENCE.
 SECTION 101.2.
 2. ALL SHEETS. SEARCH OF THE DBPR
 LICENSE SEARCH INDICATES THAT THE
 ARCHITECTURAL BUSINESS NUMBER IS
 AA26000717. (SEE ATTACHED SHEETS). TITLE
 BLOCK INDICATES AAC001708. PLEASE
 CLARIFY. FAC 61G1-16.004(2) & FS
 481.2055.
 3. SHT G-1 DETAIL 4/G-1 ACCESSIBLE
 MOUNTING HEIGHTS SHOW THE W/C TO BE 1'5"
 OFF THE WALL TO THE CENTERLINE OF THE
 FIXTURE. PER FIGURE 29 THE W/C SHALL BE
 SET 1'6" TO CENTER OF FIXTURE OFF THE
 WALL. SECTION 11-3.1. - W/C FRONTAL
 ELEVATION SHOWS THE DISPENSER AT 1'6".
 PER SECTION 11-4.16.6 AND FIG. 29B THE
 MINIMUM HEIGHT IS 1'7".
 4. SHT A-1 DETAIL 1B PROPOSED BATHROOM
 FLOOR PLAN SHOWS W/C AS 19" OFF THE WALL
 TO THE CENTER OF THE FIXTURE. PER
 SECTION 11-4.16.2 AND FIGURE 28. SECTION
 11-3.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]