| 2006-07-06 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) BEFORE THE FOLLOWING CORRECTIONS ARE |
| | MADE PLEASE VERIFY THAT GARAGE CAN BE |
| | BUILT IN THE SETBACKS SHOWN IF NOT MAJOR |
| | CHANGES MAY BE REQUIRED |
| | |
| | 2) PROVIDE DETAIL ON NEW 2'-0" WALL THAT |
| | RUNS PERIMETER OF PATIO SLAB. SHALL |
| | CONTAIN BOND BEAM, VERTICAL COLUMNS, TIE |
| | INS AT 1'-4" COLUMNS |
| | |
| | 3) PROVIDE DETAIL OF HEADER OR FRAMING |
| | AT GARAGE DOOR OPENING AS THIS IS NEW ON |
| | DRAWING. (SEE SECTION B ON S1.1) DETAIL |
| | 16 ON S1.3 ONLY SHOWS TOP BEAM, HOW IS |
| | THE DOOR HEADER OR FRAMING ATTACHED |
| | |
| | 4) MINIMUM ROOF SHEATHING FOR 24" |
| | CENTERS IS 5/8" PER R803.1 FBC |
| | |
| | 5) ROOF OVERHANG DETAIL DOES NOT SEEM |
| | ADEQUATE? SUGGEST THAT WALL IS DROPPED |
| | 3 1/2" AND OUTLOOKERS SET ON TOP OF WOOD |
| | PLATE AND ARE ATTACHED WITH HURRICANE |
| | CLIPS, THEY WOULD ALSO RUN IN TO THE |
| | FIRST RAFTER AND BE ATTACHED. ALSO |
| | PROVIDE PROJECTION SIZE |
| | |
| | 6) DOORS ARE GENERALLY ATTACHED TO |
| | PRESURE TREATED WOOD BUCKS. THEY SHALL |
| | BE DESIGNED WITH ATTACHMENT THAT |
| | TRANSFERS THE LOADS TO THE STRUCTURE. |
| | PROVIDE DETAIL/NOTE FOR BUCK ATTACHMENT |
| | (SEE PAGE 3 OF DOOR PRODUCT APPROVAL) |
| | NOTE GARAGE DOOR ATTACHMENT IS INCLUDED |
| | IN THE PRODUCT APPROVAL |
| | |
| | 7) SINGLES SHALL NOT BE USED ON SLOPES |
| | LESS THAN 2/12 PER 1507.2.2 FBC |
| | |
| | 8) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |
| | BLDG PLAN REVIEW |