Plan Review Notes
Plan Review Notes For Permit 05120777
Permit Number 05120777
Review Stop B
Sequence Number 2
Notes
Date Text
2006-07-06 00:00:00 
  
 DENIED
  
 1) BEFORE THE FOLLOWING CORRECTIONS ARE
 MADE PLEASE VERIFY THAT GARAGE CAN BE
 BUILT IN THE SETBACKS SHOWN IF NOT MAJOR
 CHANGES MAY BE REQUIRED
  
 2) PROVIDE DETAIL ON NEW 2'-0" WALL THAT
 RUNS PERIMETER OF PATIO SLAB. SHALL
 CONTAIN BOND BEAM, VERTICAL COLUMNS, TIE
 INS AT 1'-4" COLUMNS
  
 3) PROVIDE DETAIL OF HEADER OR FRAMING
 AT GARAGE DOOR OPENING AS THIS IS NEW ON
 DRAWING. (SEE SECTION B ON S1.1) DETAIL
 16 ON S1.3 ONLY SHOWS TOP BEAM, HOW IS
 THE DOOR HEADER OR FRAMING ATTACHED
  
 4) MINIMUM ROOF SHEATHING FOR 24"
 CENTERS IS 5/8" PER R803.1 FBC
  
 5) ROOF OVERHANG DETAIL DOES NOT SEEM
 ADEQUATE? SUGGEST THAT WALL IS DROPPED
 3 1/2" AND OUTLOOKERS SET ON TOP OF WOOD
 PLATE AND ARE ATTACHED WITH HURRICANE
 CLIPS, THEY WOULD ALSO RUN IN TO THE
 FIRST RAFTER AND BE ATTACHED. ALSO
 PROVIDE PROJECTION SIZE
  
 6) DOORS ARE GENERALLY ATTACHED TO
 PRESURE TREATED WOOD BUCKS. THEY SHALL
 BE DESIGNED WITH ATTACHMENT THAT
 TRANSFERS THE LOADS TO THE STRUCTURE.
 PROVIDE DETAIL/NOTE FOR BUCK ATTACHMENT
 (SEE PAGE 3 OF DOOR PRODUCT APPROVAL)
 NOTE GARAGE DOOR ATTACHMENT IS INCLUDED
 IN THE PRODUCT APPROVAL
  
 7) SINGLES SHALL NOT BE USED ON SLOPES
 LESS THAN 2/12 PER 1507.2.2 FBC
  
 8) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW