2006-07-07 00:00:00*********** UNSAT ************
  
 1) NOTE: PLEASE INDICATE THE SWITCHING
 CONTROLS FOR ALL NEW LIGHTING FIXTURES.
 210.70, LS101
  
 2) NOTE: PLEASE SEE MISSING GFI RECEPT
 REQUIRED FOR GARAGE. 210.8A, 250.52G
  
 3) NOTE: PLEASE SEE RECEPT SHOWN FOR GDO
 CAN NOT BE A DUPLEX RECEPT AS SHOWN.
 THIS MUST BE A DEDICATED SINGLE RECEPT
 RATED FOR THE NEW GDO.
 430, 430.148
  
 4) NOTE: PLEASE PROVIDE INFORMATION ON
 THE NEW CIRCUIT(S) BEING PROVIDED FOR
 THE GDO AND IF THE LIGTHING AND GARAGE
 RECEPTS WILL BE FROM EXISTING OR NEW
 CIRCUITS.
 106.1.2 FBC ADMIN SECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  