Plan Review Notes
Plan Review Notes For Permit 05120752
Permit Number 05120752
Review Stop B
Sequence Number 1
Notes
Date Text
2006-02-04 00:00:00 
 1) A NOTORIZE LETTER FROM THE OWNER IS
 REQUIRED, STATING THAT HE/SHE WILL
 REMOVE THE AWNINGE IN PERIODS OF HIGH
 WINDS OF 75 MPH.3105.5.1 LOADS.
 RIGID AWNINGS AND CANOPY SHUTTERS SHALL
 BE DESIGNED TO RESIST THE LOADS SET
 FORTH IN CHAPTER 16 OF THIS CODE EXCEPT
 THAT STRUCTURES OR PARTS THEREOF WHICH
 ARE INTENDED TO BE REMOVED OR
 REPOSITIONED DURING PERIODS OF HIGH WIND
 VELOCITY SHALL BE DESIGNED IN THEIR OPEN
 OR EXTENDED POSITION TO DESIGN PRESSURES
 BASED ON A BASIC WIND SPEED OF MINIMUM
 90 MPH, 3-SECOND WIND GUST WITH
 APPLICABLE SHAPE FACTORS AND TO RESIST
 NOT LESS THAN 10 PSF (478 PA) ROOF LIVE
 LOAD.
  
 2) 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH
 A QUICK REMOVAL OR BREAKAWAY MEMBRANE OR
 FABRIC AT WIND VELOCITIES OF 75 MPH,
 SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
 1.MINIMUM WIND VELOCITY OF 3-SECOND
 WIND GUST 90 MPH
 2.IMPORTANCE FACTOR BASED ON LOW
 HAZARD TO HUMAN LIFE OF 0.77.
 3.EXPOSURE CATEGORY B FOR OR C AS
 DEFINED IN CHAPTER 16 .
  
 3) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  