2006-02-10 00:00:00******* UNSAT 2ND REVIEW *********
  
  
 1)NOTE: PLEASE SEE PLANS ARE NOW STAMPED
 WITH A TITLE BLOCK CONTAINING A
 EB/CERTIFICATE OF AUTHORIZATION NUMBER
 WHICH IS NULL & VOID ON DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION'S
 WEBSITE.
 PLEASE SEE ATTACHED COPY WHICH INDICATES
 THIS.
 PLEASE SEE ONE COPY OF PLANS SHALL BE
 RETAINED FOR FILE AND MAY BE FORWARDED
 TO THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS FOR REVIEW AND LEGAL CONSEL TO
 THE BOARD FOR USE OF A CA # NOT CURRENT.
  
 2)NOTE: PLEASE SEE TWO DIFFERENT RISERS
 FOR SIGNS ELECTRICAL DETAIL SUBMITTED.
 ONE SHOWS 48A'S+ AND THE OTHER 16.8A'S??
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE VALUATION HAS NOT
 BEEN INCREASED TO REFLECT THE SCOPE OF
 WORK INCLUDING ALL LABOR AND MATERIALS.
 PLEASE SEE A COPY OF A PERMIT TO REPLACE
 THIS SIGN ONE YEAR AGO WAS ATTACHED
 WHICH SHOWS A VALUE OF $8900.00 AND
 PERMIT APPLICATION STILL SHOWS $1800.00
 PLEASE SEE CONSTRUCTION COST IN THE
 LLAST YEAR HAS INCREASED AND NO
 REFLECTION TO THESE CHANGES WERE MADE.
  
  
 4)NOTE: PLEASE SEE ATTACHED COPY OF
 FLORIDA STATUES 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT COMMENTS.
 PLEASE KNOW, IF PLANS COME BACK WITH
 "ANY" OF THE SAME CODE COMPLIANT
 COMMENTS NOT BEING ADDRESSED, A 4X FEE
 FOR THE PLAN REVIEW PORTION OF THE
 PERMIT FEE SHALL BE ACCESSED AS REQUIRED
 BY STATUES.
  
  
  
 PLEASE SUBMIT AS REQUESTED AND ADJUST AS
 NEEDED.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL
 THIS OFFICE.
  