| Plan Review Notes For Permit 05120693 |
| Permit Number |
05120693 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-13 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- PERMIT APPLICATIONS SUBMITTED AFTER | | | OCTOBER 1ST 2005 NEED TO COMPLY WITH FBC | | | 2004.PRODUCT APPROVALS NEED TO BE | | | UPDATED TO THE 2004 CODE VERSION. | | | PRODUCT APPROVAL FOR METAL ROOFING | | | SUBMITTED IS FOR 2001 CODE. GO TO | | | WEBSITE WWW.FLORIDABUILDING.ORG TO | | | VERIFY IF METAL ROOFING MANUFACTURER | | | HAVE APPLIED FOR THE 2004 CODE EDITION. | | | | | | 2- ACCORDING TO THE LIMITS OF USE OF THE | | | FLORIDA PRODUCT APPROVAL NEED RATIONAL | | | ANALYSIS COMPUTATIONS PREPARED BY A | | | QUALIFIED DESIGN PROFESSIONAL. PROVIDE | | | ALL INFORMATION AS REQUIRED. | | | | | | 3- DADE COUNTY NOA SUBMITTED IS NOT PART | | | OF THE INFORMATION THAT WAS SUBMITTED | | | FOR FLORIDA PRODUCT APPROVAL. PROVIDE | | | ONLY THE INFORMATION THAT WAS REVIEWED | | | AND APPROVED BY THE FLORIDA BUILDING | | | COMMISSION. | | | | | | 4- OWES $56.36 VALUE DECLARED ON THE | | | PERMIT APPLICATION WAS UPDATED. SEC. | | | 108.3 CITY AMENDMENTS TO FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|