2006-08-05 00:00:00******* PROVISO/ REVISION ***********
  
  
 1) NOTE: PLEASE SEE PLANS ARE MISSING
 DISCONNETC "B" FOR GROUPED WITH OTHER
 MAINS "A" AND GEN DISCONNECT.
 ALL MAINS ARE GROUPED PER CONTRACTOR,
 SEE RISER DIAGRAM. 230.72, 225.34
  
 2) NOTE: PLEASE REVISE AND SUBMIT ALL
 PANEL SCHEDULES BEFORE FINAL.
 PLEASE SEE THAT ALL CIRCUITING IS
 SPECFIC TO ROOMS AND AREAS IN WHICH THEY
 SERVE. IE; LIVING RM LTS, BEDRM 32,
 RECEPTS/LTS, KITCGEN LTS, ETC ETC.
 408.4.
 FBC 106.1.2
  
  
 **** PLEASE VERIFY NOTE #1, IF MAINIS
 GROUPED, THEN PLEASE SUBMIT THE REVISED
 PANEL SCHEDULES BEFORE FINAL.
 PLEASE KNOW, IF THERE ARE ANY OTHER
 REVISIONS, THESE ARE REQUIRED BEFORE
 ROUGH ELECTRICAL INSPECTION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  