| Plan Review Notes For Permit 05120685 |
| Permit Number |
05120685 |
|
| Review Stop |
E |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2006-08-05 00:00:00 | ******* PROVISO/ REVISION *********** | | | | | | | | | 1) NOTE: PLEASE SEE PLANS ARE MISSING | | | DISCONNETC "B" FOR GROUPED WITH OTHER | | | MAINS "A" AND GEN DISCONNECT. | | | ALL MAINS ARE GROUPED PER CONTRACTOR, | | | SEE RISER DIAGRAM. 230.72, 225.34 | | | | | | 2) NOTE: PLEASE REVISE AND SUBMIT ALL | | | PANEL SCHEDULES BEFORE FINAL. | | | PLEASE SEE THAT ALL CIRCUITING IS | | | SPECFIC TO ROOMS AND AREAS IN WHICH THEY | | | SERVE. IE; LIVING RM LTS, BEDRM 32, | | | RECEPTS/LTS, KITCGEN LTS, ETC ETC. | | | 408.4. | | | FBC 106.1.2 | | | | | | | | | **** PLEASE VERIFY NOTE #1, IF MAINIS | | | GROUPED, THEN PLEASE SUBMIT THE REVISED | | | PANEL SCHEDULES BEFORE FINAL. | | | PLEASE KNOW, IF THERE ARE ANY OTHER | | | REVISIONS, THESE ARE REQUIRED BEFORE | | | ROUGH ELECTRICAL INSPECTION. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|