Plan Review Notes
Plan Review Notes For Permit 05120685
Permit Number 05120685
Review Stop E
Sequence Number 4
Notes
Date Text
2006-03-17 00:00:00******* UNSAT 3RD REVIEW *********
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEW
 AND SOME NEW NOTES DUE TO CHANGES IN
 PLANS FROM PREVIOUS PLANS SUBMITTED.
  
 SEE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PERVIOUS REVIEW.
  
 ********** UNSAT *************
  
  
 1)NOTE:NOTE #1 , OK, HOWEVER PLEASE
 SEE SOME CIRCUITS ARE STILL SHOWN ON
 PLANS. PLEASE ALSO SEE CIRCUIT B-7 IS
 STIL SHOWN FOR GDO , YET THE GDO IS A
 DEDICATED CIRCUIT ON PANEL SCHEDULE.
 MOSTCIRCUITING WAS REMOVED FROM PLANS.
  
 ** PREVIOUS NOTE**
 PLEASE CORRELATE CIRCUTING ON PLANS WITH
 PANEL SCHEDULES SUBMITTED.
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE:NOTE #3 OK, HOWEVER PLEASE SEE
 LOAD ON PANEL "A" (41.3KW) DOES NOT
 CORRELATE WITH LOAD SHOWN ON
 CALCUALTIONS BELOW PANEL. PLEASE SEE
 TOTAAL LOAD IS SHOWN AS 11,440 VA.
 PLEASE ALSO SEE THE FOLLOWING COMMENT AS
 THIS WILL AFFECT LOAD CALCUALTIONS.
  
  
 ** PREVIOUS REVIEW**
 PLEASE SUBMIT LOAD CALCUALTIONS. PLEASE
 SEE MISSING CIRCUITS IN FORTH COMING
 NOTES WHICH WILL AFFECT LOAD CALCS.
 PLEASE SEE LOADS ON POOL PANEL DO NOT
 CORRELATE WITH THE LOAD ON PANEL "B".
 PLEASE BE SURE TO INDICATE IF CONTINUOUS
 LOADS ARE ALREADY FIGURED AT 125% (POOL
 PUMPS) ANY LOADS FOR 3 OR MORE HRS.
 215.5,220, 215.3,230.42 ETC.
  
 4)NOTE:NOTE #4 NO, PLEASE SEE LOADS
 FOR AHUS' ON PANEL "A" ARE BEING DERATED
 AT 65%. THESE MUST BE SHOWN AT 100%.
 PLEASE KNOW, AS GENERATOR IS SHOWN AS
 45KW, THIS SHOULD BE OK, HOWEVE THIS
 NEEDS TO BE SHOWN. IF PROVIDING LOAD
 SHEDDING, PLEASE PROVIDE DETAIL/
  
 ** PREVIOUS REVIEW**
 PLEASE SEE THAT SEPARATE LOAD
 CALCS ARE NEEDED FOR THE PANEL WHICH
 WILL
 BE FED FROM THE GENERATOR AS ANY HEAT
 AND MOTOR LOADS SHALL BE FIGURED AT
 100%. PLEASE KNOW, AUTOMATIC LOAD
 SHEDDING IS PERMITTED, HOWEVER PLEASE
 PROVIDE THIS DETAIL SINCE THE GEN IS
 UNDER THE HOUSE PERMIT.
 220,702.5,215.5
  
 5)NOTE: NOTE #5 NO, PLEASE SEE THIS IS
 STILL NOT INDICATED ON PLANS AND SIZING
 CONDUCTORS PER 445.13 CAN NOT VERIFIED.
  
 ** PREVIOUS REVIEW**
 PLEASE INDICATE THE OCP AT THE
 GENERATOR ON PLANS/RISER. PLEASE 445.13
 FOR SIZING OF CONDUCTORS.
 215..5
  
 6)NOTE:NOTE #6 NO, PLEASE SEE RISER
 APPEARS TO SHOW MAINS GROUPED, HOWEVER
 PLANS DO NOT CORRELATE WITH THIS OR
 GROUPING OF MEANS OF DISCONNECTS ETC..
 PLEASE SEE PLANS SHOW METER AND ONE MAIN
 AT FRONT OF HOUSE AND ATS , DISCONNECT
 AND GEN DISCONNECT AT REAR OF HOUSE??
 PLEASE REVISE PLANS.
  
  
 ** PREVIOUS REVIEW**
 PLEASE SEE THAT THE MAINS ARE GROUPED AT
 MAIN ELECTRICAL SERVICE.
 PLEASE SEE THERE IS A GEN DISCONNECT
 SHOWN ON PLANS, BUT NOT ON RISER. IN
 EITHER CASE THIS DISCONNECT IS REQUIRD
 TO BE GROUPED WITH OTHER MAINS FOR
 HOUSE.
 230.72,225.34 ETC
 225.31-225.39
  
 7)NOTE:NOTE #7 NO, PLEASE SEE THE SAME
 SPEC SHEET WERE SUBMITTED BACK AND NO
 MCB AS REQUIRED IS SHOWN, DETAILED OR
 NOTED. ATS SPEC ONLYS NOTE THAT THIS
 EQUIPMENT IS "SERVICE ENTRANCE RATED" AS
 SERVICE EQUIPMENT", WHICH DOES NOT MEAN
 IT CONTAINS A MCB/OR MAIN AS SHOWN ON
 ON RISER DIAGRAM.
  
 ** PREVIOUS REVIEW **
 PLEASE SEE RISER SEEMS TO INDICATE THE
 ATS CONTAINS A MCB? THIS CAN NOT BE
 VERIFIED AS THE SPECS SUBMITTED DO NOT
 SEEM TO SHOW THIS.
 PLEASE SEE THAT THE MEANS OF DISCONNECT
 SHALL BE LOCATED ON THE OUTSIDE,(READILY
 ACCESSSIBLE), RATED FOR THE LOAD SERVED,
 AND SHALL BE MANUAL.
 230.76,230.79, 230.70
  
 8)NOTE: OK
  
 9)NOTE: NOTE #9 NO, PLEASE KNOW, IT IS
 STILL THIS AHJ'S INTERPRETATION THAT THE
 AMOUNT OF FIXTURES SHOWN GO EBOVE WHAT
 WOULD BE NORMAL "GENERAL LIGHTING" AS
 MENTIONED IN THE EXCEPTION TO 220.3(A)
 AND 220.3B4 AS NOTED IN HANDBOOK.
 PLEASE INDICATE THE # OF FIXTURES X
 -WATTS PER FIXTURE AND ONLY ADD TO OVER
 ALL LOAD.
  
 ** PREVIOUS REVIEW**
 PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
  
 10)NOTE:NOTE #10 NO, PLEASE SEE PLANS,
 PANEL SCHEDULES AND RISER. PLEASE SEE
 PLANS MISSING THE UN-LABELED SUB-PANEL
 FED FROM PANEL "A"?? PLEASE LABEL ALL
 PANELS.
  
 ** PREVIOUS NOTE**
 PLEASE SEE PLANS SHOWS PANELS
 A, B, C, AND D, PLEASE CORRELATE.
 215.5
  
 11)NOTE: NOTE #11 ? NO, THIS IS UNCLEAR
 AS IT SEEMS A NOTE WAS ADDED TO
 "ELECTRICAL NOTES" #22 WHICH MENTIONS A
 STUB OUT FOR "FUTURE" LANDSCAPE
 LIGHTING, HOWEVER PLEASE SEE NOTES #9
 AND #10 ARE STILL NOTED?? PLEASE REMOVE
 NOTES AS THESE ARE SEPARATE PERMIT
 ITEMS.
  
 ** PREVIOUS NOTE**
 PLEASE SEE NOTES PERTAINING TO
 LV LANDSCAPE LTS AND LV SPRKR WIRING
 THIS WOULD EITHER ALL BE COMPLETE UNDER
 MAIN PLANS, OR SHALL BE UNDER SEPARATE
 PERMITS AND PLANS.
  
 12)NOTE:NOTE #12NO, PLEASE SEE THERE
 ARERECEPTS MISSING WHICH WERE REDLINED
 ON PREVIOUS PLANS, BUT DIDN'T GET PLACED
 ON PLANS. PLEASE SEE REDLINED LOCATIONS.
  
 ** PREVIOUS NOTE**
 PLEASE SEE 210.52 FOR MISSING RECEPTS
 FOR 2',6',12' RULE.
  
 13)NOTE: NOTE #13 OK.
  
 14)NOTE: NOTE #14 OK.
  
 15)NOTE: NOTE #15 NO, THESE WERE NOT
 ADDED AS REQUIRED.
  
 ** PREVIOUS NOTE**
 PLEASE SEE MISSING DEDICATED
 BATH(S) CIRCUIT(S), SHALL BE 20A AND
 #12. 210.11C3
  
 16)NOTE: NOTE #16 OK, NOTED ON PLANS.
  
 17)NOTE: NOTE #17 ? UNCLEAR AS GEN SLAB
 DETAIL WAS NOT LOCATE ON PLANS? SEE ANY
 COMMENTS FROM BLDG TRADES.
  
 ** PREVIOUS NOTE**
 PLEASE SEE BLDG REVIEW COMMENTS
 FOR SLAB DETAIL REQUIRED.
  
 18)NOTE: NOTE #18 NO? THIS IS NOT CLEAR
 AS THE POOL PANEL MENTIONS A 2-POLE FEED
 TO ANOTHER "POOL PANEL" ?? IS THIS THE
 "JANDY PANEL"?PLEASE ALSO SEE NEW
 COMMENTS FOR POOL EQUIPMENT ETC.
  
 ** PREVIOUS NOTE**
  
 PLEASE INDICATE WHERE AND HOW
 "JANDY PANEL" IS BEING FED ETC.
 A PANEL AND CIRCUTIING IS SHOWN ON
 PLANS, HOWEVER PANEL SCHEDULES DO NOT
 INDICATE ANY FEEDING OF SAID PANEL.
 215.5
 PLEASE ALSO VERIFY GFI RECEPT IN FRONT
 OF HOUSE BEING FED FROM THIS PANEL?
  
 *********** NEW NOTES ****************
  
 19) NOTE: PLEASE CLARIFY THE POOL PUMP
 BEING FED FROM PANEL "B"?
 PLEASE SEE POOL PANEL(?) DOES NOT
 INDICATE THE "WATER FALL" PUMP? IS THIS
 FED FROM THE "JANDY PANEL" ??
 PLEASE ALSO SEE LOAD ON "POOL PANEL" IS
 SHOWN @ 42.5 AMPS, HOWEVER THE BREAKER?
 OCP FROM PANEL "B" ONLY SHOWS A 40A
 BRKR? PLEASE SEE POOL PANEL SHOWS 60A
 BRKR PANEL?
 PLEASE VERIFY AND INCREASE OCP. PLEASE
 SEE NOTE #3 FROM PREVIOUS REVIEW WHICH
 REQUESTED THE CONTINUOUS LOADS, 3 OR
 MORE HRS TO BE SHOWN AT 125%. 215.3,
 230.42. PLEASE KNOW, THE POOL PUMP WOULD
 BE CONSIDERED , AS THIS RUNS FOR MORE
 THAN 3 HRS.
  
 20) NOTE: PLEASE SEE PANEL "A" DOES NOT
 INDICATE THE OCP AND CONDUCTORS FOR
 LIGHTING SUB-PANEL. PLEASE LABEL, AS
 PLANS INDICATES A PANEL "C" OUTSIDE,
 HOWEVER THIS IS UNCLEAR IF THIS IS THE
 POOL PANEL ? OR GEN LIGHTING PANEL.
 215.5
  
 21)NOTE: PLEASE SEE GEN LIGHTING PANEL
 WHICH SHOWS ALL BRANCH CIRCUITS AS 2POLE
 CIRCUITS? THIS MUST BE A MISPRINT?
 215.5
  
 22)NOTE: PLEASE SEE NOTE WHICH WAS ADDED
 TO PREVIOUS PLAN REVIEW, WHICH REQUIRED
 TOTAL VALUATION OG GEN, ATS ETC TO BE
 ADDED TO MAIN HOUSE VALUATION IF BEING
 PERMITTED UNDER MAIN HOUSE.
 108.3 FBC ADMINISTRATIVE CODE AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 ** PLEASE SUBMIT TWO COMPLETE SETS OF
 PLANS FOR REVIEW. PLEASE BE SURE TO
 INSERT ALL ELECTRICAL/ MECHANICAL PLANS
 INTO HOUSE SETS.
 PLEASE SEE MECHANCIAL PLANS ARE NOT
 ATTACHED TO PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT NEW REVISED
 SHEETS INTO THE TWO COMPLETED SETS FOR
 REVIEW AND STAMPING. PLEASE SEE ONE SET
 OF OLD/VOIDED SHEETS SHOUDL EB SUBMTTED
 FOR REFERENCE ONLY
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THEREARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW