| Date |
Text |
| 2006-03-17 00:00:00 | ******* UNSAT 3RD REVIEW ********* |
| | |
| | PLEASE SEE NOTES FROM PREVIOUS REVIEW |
| | AND SOME NEW NOTES DUE TO CHANGES IN |
| | PLANS FROM PREVIOUS PLANS SUBMITTED. |
| | |
| | SEE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PERVIOUS REVIEW. |
| | |
| | ********** UNSAT ************* |
| | |
| | |
| | 1)NOTE:NOTE #1 , OK, HOWEVER PLEASE |
| | SEE SOME CIRCUITS ARE STILL SHOWN ON |
| | PLANS. PLEASE ALSO SEE CIRCUIT B-7 IS |
| | STIL SHOWN FOR GDO , YET THE GDO IS A |
| | DEDICATED CIRCUIT ON PANEL SCHEDULE. |
| | MOSTCIRCUITING WAS REMOVED FROM PLANS. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE CORRELATE CIRCUTING ON PLANS WITH |
| | PANEL SCHEDULES SUBMITTED. |
| | |
| | 2)NOTE: NOTE #2 OK. |
| | |
| | 3)NOTE:NOTE #3 OK, HOWEVER PLEASE SEE |
| | LOAD ON PANEL "A" (41.3KW) DOES NOT |
| | CORRELATE WITH LOAD SHOWN ON |
| | CALCUALTIONS BELOW PANEL. PLEASE SEE |
| | TOTAAL LOAD IS SHOWN AS 11,440 VA. |
| | PLEASE ALSO SEE THE FOLLOWING COMMENT AS |
| | THIS WILL AFFECT LOAD CALCUALTIONS. |
| | |
| | |
| | ** PREVIOUS REVIEW** |
| | PLEASE SUBMIT LOAD CALCUALTIONS. PLEASE |
| | SEE MISSING CIRCUITS IN FORTH COMING |
| | NOTES WHICH WILL AFFECT LOAD CALCS. |
| | PLEASE SEE LOADS ON POOL PANEL DO NOT |
| | CORRELATE WITH THE LOAD ON PANEL "B". |
| | PLEASE BE SURE TO INDICATE IF CONTINUOUS |
| | LOADS ARE ALREADY FIGURED AT 125% (POOL |
| | PUMPS) ANY LOADS FOR 3 OR MORE HRS. |
| | 215.5,220, 215.3,230.42 ETC. |
| | |
| | 4)NOTE:NOTE #4 NO, PLEASE SEE LOADS |
| | FOR AHUS' ON PANEL "A" ARE BEING DERATED |
| | AT 65%. THESE MUST BE SHOWN AT 100%. |
| | PLEASE KNOW, AS GENERATOR IS SHOWN AS |
| | 45KW, THIS SHOULD BE OK, HOWEVE THIS |
| | NEEDS TO BE SHOWN. IF PROVIDING LOAD |
| | SHEDDING, PLEASE PROVIDE DETAIL/ |
| | |
| | ** PREVIOUS REVIEW** |
| | PLEASE SEE THAT SEPARATE LOAD |
| | CALCS ARE NEEDED FOR THE PANEL WHICH |
| | WILL |
| | BE FED FROM THE GENERATOR AS ANY HEAT |
| | AND MOTOR LOADS SHALL BE FIGURED AT |
| | 100%. PLEASE KNOW, AUTOMATIC LOAD |
| | SHEDDING IS PERMITTED, HOWEVER PLEASE |
| | PROVIDE THIS DETAIL SINCE THE GEN IS |
| | UNDER THE HOUSE PERMIT. |
| | 220,702.5,215.5 |
| | |
| | 5)NOTE: NOTE #5 NO, PLEASE SEE THIS IS |
| | STILL NOT INDICATED ON PLANS AND SIZING |
| | CONDUCTORS PER 445.13 CAN NOT VERIFIED. |
| | |
| | ** PREVIOUS REVIEW** |
| | PLEASE INDICATE THE OCP AT THE |
| | GENERATOR ON PLANS/RISER. PLEASE 445.13 |
| | FOR SIZING OF CONDUCTORS. |
| | 215..5 |
| | |
| | 6)NOTE:NOTE #6 NO, PLEASE SEE RISER |
| | APPEARS TO SHOW MAINS GROUPED, HOWEVER |
| | PLANS DO NOT CORRELATE WITH THIS OR |
| | GROUPING OF MEANS OF DISCONNECTS ETC.. |
| | PLEASE SEE PLANS SHOW METER AND ONE MAIN |
| | AT FRONT OF HOUSE AND ATS , DISCONNECT |
| | AND GEN DISCONNECT AT REAR OF HOUSE?? |
| | PLEASE REVISE PLANS. |
| | |
| | |
| | ** PREVIOUS REVIEW** |
| | PLEASE SEE THAT THE MAINS ARE GROUPED AT |
| | MAIN ELECTRICAL SERVICE. |
| | PLEASE SEE THERE IS A GEN DISCONNECT |
| | SHOWN ON PLANS, BUT NOT ON RISER. IN |
| | EITHER CASE THIS DISCONNECT IS REQUIRD |
| | TO BE GROUPED WITH OTHER MAINS FOR |
| | HOUSE. |
| | 230.72,225.34 ETC |
| | 225.31-225.39 |
| | |
| | 7)NOTE:NOTE #7 NO, PLEASE SEE THE SAME |
| | SPEC SHEET WERE SUBMITTED BACK AND NO |
| | MCB AS REQUIRED IS SHOWN, DETAILED OR |
| | NOTED. ATS SPEC ONLYS NOTE THAT THIS |
| | EQUIPMENT IS "SERVICE ENTRANCE RATED" AS |
| | SERVICE EQUIPMENT", WHICH DOES NOT MEAN |
| | IT CONTAINS A MCB/OR MAIN AS SHOWN ON |
| | ON RISER DIAGRAM. |
| | |
| | ** PREVIOUS REVIEW ** |
| | PLEASE SEE RISER SEEMS TO INDICATE THE |
| | ATS CONTAINS A MCB? THIS CAN NOT BE |
| | VERIFIED AS THE SPECS SUBMITTED DO NOT |
| | SEEM TO SHOW THIS. |
| | PLEASE SEE THAT THE MEANS OF DISCONNECT |
| | SHALL BE LOCATED ON THE OUTSIDE,(READILY |
| | ACCESSSIBLE), RATED FOR THE LOAD SERVED, |
| | AND SHALL BE MANUAL. |
| | 230.76,230.79, 230.70 |
| | |
| | 8)NOTE: OK |
| | |
| | 9)NOTE: NOTE #9 NO, PLEASE KNOW, IT IS |
| | STILL THIS AHJ'S INTERPRETATION THAT THE |
| | AMOUNT OF FIXTURES SHOWN GO EBOVE WHAT |
| | WOULD BE NORMAL "GENERAL LIGHTING" AS |
| | MENTIONED IN THE EXCEPTION TO 220.3(A) |
| | AND 220.3B4 AS NOTED IN HANDBOOK. |
| | PLEASE INDICATE THE # OF FIXTURES X |
| | -WATTS PER FIXTURE AND ONLY ADD TO OVER |
| | ALL LOAD. |
| | |
| | ** PREVIOUS REVIEW** |
| | PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | |
| | 10)NOTE:NOTE #10 NO, PLEASE SEE PLANS, |
| | PANEL SCHEDULES AND RISER. PLEASE SEE |
| | PLANS MISSING THE UN-LABELED SUB-PANEL |
| | FED FROM PANEL "A"?? PLEASE LABEL ALL |
| | PANELS. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SEE PLANS SHOWS PANELS |
| | A, B, C, AND D, PLEASE CORRELATE. |
| | 215.5 |
| | |
| | 11)NOTE: NOTE #11 ? NO, THIS IS UNCLEAR |
| | AS IT SEEMS A NOTE WAS ADDED TO |
| | "ELECTRICAL NOTES" #22 WHICH MENTIONS A |
| | STUB OUT FOR "FUTURE" LANDSCAPE |
| | LIGHTING, HOWEVER PLEASE SEE NOTES #9 |
| | AND #10 ARE STILL NOTED?? PLEASE REMOVE |
| | NOTES AS THESE ARE SEPARATE PERMIT |
| | ITEMS. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SEE NOTES PERTAINING TO |
| | LV LANDSCAPE LTS AND LV SPRKR WIRING |
| | THIS WOULD EITHER ALL BE COMPLETE UNDER |
| | MAIN PLANS, OR SHALL BE UNDER SEPARATE |
| | PERMITS AND PLANS. |
| | |
| | 12)NOTE:NOTE #12NO, PLEASE SEE THERE |
| | ARERECEPTS MISSING WHICH WERE REDLINED |
| | ON PREVIOUS PLANS, BUT DIDN'T GET PLACED |
| | ON PLANS. PLEASE SEE REDLINED LOCATIONS. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SEE 210.52 FOR MISSING RECEPTS |
| | FOR 2',6',12' RULE. |
| | |
| | 13)NOTE: NOTE #13 OK. |
| | |
| | 14)NOTE: NOTE #14 OK. |
| | |
| | 15)NOTE: NOTE #15 NO, THESE WERE NOT |
| | ADDED AS REQUIRED. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SEE MISSING DEDICATED |
| | BATH(S) CIRCUIT(S), SHALL BE 20A AND |
| | #12. 210.11C3 |
| | |
| | 16)NOTE: NOTE #16 OK, NOTED ON PLANS. |
| | |
| | 17)NOTE: NOTE #17 ? UNCLEAR AS GEN SLAB |
| | DETAIL WAS NOT LOCATE ON PLANS? SEE ANY |
| | COMMENTS FROM BLDG TRADES. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SEE BLDG REVIEW COMMENTS |
| | FOR SLAB DETAIL REQUIRED. |
| | |
| | 18)NOTE: NOTE #18 NO? THIS IS NOT CLEAR |
| | AS THE POOL PANEL MENTIONS A 2-POLE FEED |
| | TO ANOTHER "POOL PANEL" ?? IS THIS THE |
| | "JANDY PANEL"?PLEASE ALSO SEE NEW |
| | COMMENTS FOR POOL EQUIPMENT ETC. |
| | |
| | ** PREVIOUS NOTE** |
| | |
| | PLEASE INDICATE WHERE AND HOW |
| | "JANDY PANEL" IS BEING FED ETC. |
| | A PANEL AND CIRCUTIING IS SHOWN ON |
| | PLANS, HOWEVER PANEL SCHEDULES DO NOT |
| | INDICATE ANY FEEDING OF SAID PANEL. |
| | 215.5 |
| | PLEASE ALSO VERIFY GFI RECEPT IN FRONT |
| | OF HOUSE BEING FED FROM THIS PANEL? |
| | |
| | *********** NEW NOTES **************** |
| | |
| | 19) NOTE: PLEASE CLARIFY THE POOL PUMP |
| | BEING FED FROM PANEL "B"? |
| | PLEASE SEE POOL PANEL(?) DOES NOT |
| | INDICATE THE "WATER FALL" PUMP? IS THIS |
| | FED FROM THE "JANDY PANEL" ?? |
| | PLEASE ALSO SEE LOAD ON "POOL PANEL" IS |
| | SHOWN @ 42.5 AMPS, HOWEVER THE BREAKER? |
| | OCP FROM PANEL "B" ONLY SHOWS A 40A |
| | BRKR? PLEASE SEE POOL PANEL SHOWS 60A |
| | BRKR PANEL? |
| | PLEASE VERIFY AND INCREASE OCP. PLEASE |
| | SEE NOTE #3 FROM PREVIOUS REVIEW WHICH |
| | REQUESTED THE CONTINUOUS LOADS, 3 OR |
| | MORE HRS TO BE SHOWN AT 125%. 215.3, |
| | 230.42. PLEASE KNOW, THE POOL PUMP WOULD |
| | BE CONSIDERED , AS THIS RUNS FOR MORE |
| | THAN 3 HRS. |
| | |
| | 20) NOTE: PLEASE SEE PANEL "A" DOES NOT |
| | INDICATE THE OCP AND CONDUCTORS FOR |
| | LIGHTING SUB-PANEL. PLEASE LABEL, AS |
| | PLANS INDICATES A PANEL "C" OUTSIDE, |
| | HOWEVER THIS IS UNCLEAR IF THIS IS THE |
| | POOL PANEL ? OR GEN LIGHTING PANEL. |
| | 215.5 |
| | |
| | 21)NOTE: PLEASE SEE GEN LIGHTING PANEL |
| | WHICH SHOWS ALL BRANCH CIRCUITS AS 2POLE |
| | CIRCUITS? THIS MUST BE A MISPRINT? |
| | 215.5 |
| | |
| | 22)NOTE: PLEASE SEE NOTE WHICH WAS ADDED |
| | TO PREVIOUS PLAN REVIEW, WHICH REQUIRED |
| | TOTAL VALUATION OG GEN, ATS ETC TO BE |
| | ADDED TO MAIN HOUSE VALUATION IF BEING |
| | PERMITTED UNDER MAIN HOUSE. |
| | 108.3 FBC ADMINISTRATIVE CODE AS ADOPTED |
| | BY THE CITY OF WEST PALM BEACH. |
| | |
| | ** PLEASE SUBMIT TWO COMPLETE SETS OF |
| | PLANS FOR REVIEW. PLEASE BE SURE TO |
| | INSERT ALL ELECTRICAL/ MECHANICAL PLANS |
| | INTO HOUSE SETS. |
| | PLEASE SEE MECHANCIAL PLANS ARE NOT |
| | ATTACHED TO PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | FROM SETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO THE TWO COMPLETED SETS FOR |
| | REVIEW AND STAMPING. PLEASE SEE ONE SET |
| | OF OLD/VOIDED SHEETS SHOUDL EB SUBMTTED |
| | FOR REFERENCE ONLY |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THEREARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |