| 2006-02-15 00:00:00 | ********** UNSAT ************* |
| | |
| | |
| | 1)NOTE: PLEASE CORRELATE CIRCUITING ON |
| | PLANS WITH PANEL SCHEDULES SUBMITTED. |
| | PLEASE SEE THERE ARE MANY ITEMS EITHER |
| | MISSING OE DO NOT MATCH. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE CORRELATE AHU/HEAT LOADS |
| | AS ALL THE KW RATINGS ON MECHANICAL |
| | PLANS DO NOT CORRELATE WITH ELECTRICAL |
| | PLANS. |
| | PLEASE ALSO SEE OTHER COMMENTS WITH |
| | RESPECT TO LOADS. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS. |
| | PLEASE SEE MISSING CIRCUITS IN FORTH |
| | COMING NOTES WHICH WILL AFFECT LOAD |
| | CALCS. |
| | PLEASE SEE LOADS ON POOL PANEL DO NOT |
| | CORRELATE WITH THE LOAD ON PANEL "B". |
| | PLEASE BE SURE TO INDICATE IF CONTINUOUS |
| | LOADS ARE ALREADY FIGURED AT 125% (POOL |
| | PUMPS) ANY LOADS FOR 3 OR MORE HRS. |
| | 215.5,220, 215.3,230.42 ETC. |
| | |
| | 4)NOTE: PLEASE SEE THAT SEPARATE LOAD |
| | CALCS ARE NEED FOR THE PANEL WHICH WILL |
| | BE FED FROM THE GENERATOR AS ANY HEAT |
| | AND MOTOR LOADS SHALL BE FIGURED AT |
| | 100%. PLEASE KNOW, AUTOMATIC LOAD |
| | SHEDDING IS PERMITTED, HOWEVER PLEASE |
| | PROVIDE THIS DETAIL SINCE THE GEN IS |
| | UNDER THE HOUSE PERMIT. |
| | 220,702.5,215.5 |
| | |
| | 5)NOTE: PLEASE INDICATE THE OCP AT THE |
| | GENERATOR ON PLANS/RISER. PLEASE 445.13 |
| | FOR SIZING OF CONDUCTORS. |
| | 215..5 |
| | |
| | 6)NOTE: PLEASE SEE THAT THE MAINS ARE |
| | GROUPED AT MAIN ELECTRICAL SERVICE. |
| | PLEASE SEE THERE IS A GEN DISCONNECT |
| | SHOWN ON PLANS, BUT NOT ON RISER. IN |
| | EITHER CASE THIS DISCONNECT IS REQUIRD |
| | TO BE GROUPED WITH OTHER MAINS FOR |
| | HOUSE. |
| | 230.72,225.34 ETC |
| | 225.31-225.39 |
| | |
| | 7)NOTE: PLEASE SEE RISER SEEMS TO |
| | INDICAT THE ATS CONTAINS A MCB? THIS CAN |
| | NOT BE VERIFIED AS THE SPECS SUBMITTED |
| | DO NOT SEEM TO SHOW THIS. |
| | PLEASE SEE THAT THE MEANS OF DISCONNECT |
| | SHALL BE LOCATED ON THE OUTSIDE,(READILY |
| | ACCESSSIBLE), RATED FOR THE LOAD SERVED, |
| | AND SHALL BE MANUAL. |
| | 230.76,230.79, 230.70 |
| | |
| | 8)NOTE: PLEASE SEE RISER INDICATES A |
| | 400A SERVICE BEING PROVIDED, THE MIN |
| | SIZE GROUNDING ELECTRODE CONDUCTOR SHALL |
| | BE 1/0 AS SIZED PER 310.15B6, 250.66. |
| | |
| | 9 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 10)NOTE: PLEASE SEE PLANS SHOWS PANELS |
| | A, B, C, AND D, PLEASE CORRELATE. |
| | 215.5 |
| | |
| | 11)NOTE: PLEASE SEE NOTES PERTAINING TO |
| | LV LANDSCAPE LTS AND LV SPRKR WIRING |
| | THIS WOULD EITHER ALL BE COMPLETE UNDER |
| | MAIN PLANS, OR SHALL BE UNDER SEPARATE |
| | PERMITS AND PLANS. |
| | |
| | 12)NOTE: PLEASE SEE 210.52 FOR MISSING |
| | RECEPTS FOR 2',6',12' RULE. |
| | |
| | 13)NOTE: PLEASE SEE 210.52C1 FOR |
| | POSSIBLE MISSING GFI RECEPTS ALONG |
| | KITCHEN COUNTERSPACE. |
| | |
| | 14)NOTE: PLEASE SEE MISSING TWO MIN |
| | SMALL APPLIANCE CIRCUITS AS REQUIRED PER |
| | 210.52B1,220.16,210.11B1 |
| | |
| | 15)NOTE: PLEASE SEE MISSING DEDICATED |
| | BATH(S) CIRCUIT(S), SHALL BE 20A AND |
| | #12. 210.11C3 |
| | |
| | 16)NOTE: PLEASE LIST THE REQUIRED ARC |
| | FAULT CIRCUITS PER 210.12B, 2002 NEC. |
| | |
| | 17)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | FOR SLAB DETAIL REQUIRED. |
| | |
| | 18)NOTE: PLEASE INDICATE WHERE AND HOW |
| | "JANDY PANEL" IS BEING FED ETC. |
| | A PANEL AND CIRCUTIING IS SHOWN ON |
| | PLANS, HOWEVER PANEL SCHEDULES DO NOT |
| | INDICATE ANY FEEDING OF SAID PANEL. |
| | 215.5 |
| | PLEASE ALSO VERIFY GFI RECEPT IN FRONT |
| | OF HOUSE BEING FED FROM THIS PANEL? |
| | |
| | ** PLEASE SUBMIT TWO COMPLETE SETS OF |
| | PLANS FOR REVIEW. PLEASE BE SURE TO |
| | INSERT ALL ELECTRICAL MECHANICAL PLANS |
| | INTO HOUSE SETS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | FROM SETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO THE TWO COMPLETED SETS FOR |
| | REVIEW AND STAMPING. PLEASE SEE ONE SET |
| | OF OLD/VOIDED SHEETS SHOUDL EB SUBMTTED |
| | FOR REFERENCE ONLY |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THEREARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | *** VALUATION FOR COMPLETE SCOPE |
| | INCLUDING GENERATOR INOT ELECTRICAL |
| | SHALL BE INCREASED |
| 2006-02-14 00:00:00 | REVIEW IN PROGRESS, NOTES TO FOLLOW. |
| | PLANS WILL GO INTO "F" STATUS. |