2006-02-15 00:00:00********** UNSAT *************
  
  
 1)NOTE: PLEASE CORRELATE CIRCUITING ON
 PLANS WITH PANEL SCHEDULES SUBMITTED.
 PLEASE SEE THERE ARE MANY ITEMS EITHER
 MISSING OE DO NOT MATCH.
 215.5
  
 2)NOTE: PLEASE CORRELATE AHU/HEAT LOADS
 AS ALL THE KW RATINGS ON MECHANICAL
 PLANS DO NOT CORRELATE WITH ELECTRICAL
 PLANS.
 PLEASE ALSO SEE OTHER COMMENTS WITH
 RESPECT TO LOADS.
 215.5
  
 3)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS.
 PLEASE SEE MISSING CIRCUITS IN FORTH
 COMING NOTES WHICH WILL AFFECT LOAD
 CALCS.
 PLEASE SEE LOADS ON POOL PANEL DO NOT
 CORRELATE WITH THE LOAD ON PANEL "B".
 PLEASE BE SURE TO INDICATE IF CONTINUOUS
 LOADS ARE ALREADY FIGURED AT 125% (POOL
 PUMPS) ANY LOADS FOR 3 OR MORE HRS.
 215.5,220, 215.3,230.42 ETC.
  
 4)NOTE: PLEASE SEE THAT SEPARATE LOAD
 CALCS ARE NEED FOR THE PANEL WHICH WILL
 BE FED FROM THE GENERATOR AS ANY HEAT
 AND MOTOR LOADS SHALL BE FIGURED AT
 100%. PLEASE KNOW, AUTOMATIC LOAD
 SHEDDING IS PERMITTED, HOWEVER PLEASE
 PROVIDE THIS DETAIL SINCE THE GEN IS
 UNDER THE HOUSE PERMIT.
 220,702.5,215.5
  
 5)NOTE: PLEASE INDICATE THE OCP AT THE
 GENERATOR ON PLANS/RISER. PLEASE 445.13
 FOR SIZING OF CONDUCTORS.
 215..5
  
 6)NOTE: PLEASE SEE THAT THE MAINS ARE
 GROUPED AT MAIN ELECTRICAL SERVICE.
 PLEASE SEE THERE IS A GEN DISCONNECT
 SHOWN ON PLANS, BUT NOT ON RISER. IN
 EITHER CASE THIS DISCONNECT IS REQUIRD
 TO BE GROUPED WITH OTHER MAINS FOR
 HOUSE.
 230.72,225.34 ETC
 225.31-225.39
  
 7)NOTE: PLEASE SEE RISER SEEMS TO
 INDICAT THE ATS CONTAINS A MCB? THIS CAN
 NOT BE VERIFIED AS THE SPECS SUBMITTED
 DO NOT SEEM TO SHOW THIS.
 PLEASE SEE THAT THE MEANS OF DISCONNECT
 SHALL BE LOCATED ON THE OUTSIDE,(READILY
 ACCESSSIBLE), RATED FOR THE LOAD SERVED,
 AND SHALL BE MANUAL.
 230.76,230.79, 230.70
  
 8)NOTE: PLEASE SEE RISER INDICATES A
 400A SERVICE BEING PROVIDED, THE MIN
 SIZE GROUNDING ELECTRODE CONDUCTOR SHALL
 BE 1/0 AS SIZED PER 310.15B6, 250.66.
  
 9 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 10)NOTE: PLEASE SEE PLANS SHOWS PANELS
 A, B, C, AND D, PLEASE CORRELATE.
 215.5
  
 11)NOTE: PLEASE SEE NOTES PERTAINING TO
 LV LANDSCAPE LTS AND LV SPRKR WIRING
 THIS WOULD EITHER ALL BE COMPLETE UNDER
 MAIN PLANS, OR SHALL BE UNDER SEPARATE
 PERMITS AND PLANS.
  
 12)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPTS FOR 2',6',12' RULE.
  
 13)NOTE: PLEASE SEE 210.52C1 FOR
 POSSIBLE MISSING GFI RECEPTS ALONG
 KITCHEN COUNTERSPACE.
  
 14)NOTE: PLEASE SEE MISSING TWO MIN
 SMALL APPLIANCE CIRCUITS AS REQUIRED PER
 210.52B1,220.16,210.11B1
  
 15)NOTE: PLEASE SEE MISSING DEDICATED
 BATH(S) CIRCUIT(S), SHALL BE 20A AND
 #12. 210.11C3
  
 16)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT CIRCUITS PER 210.12B, 2002 NEC.
  
 17)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR SLAB DETAIL REQUIRED.
  
 18)NOTE: PLEASE INDICATE WHERE AND HOW
 "JANDY PANEL" IS BEING FED ETC.
 A PANEL AND CIRCUTIING IS SHOWN ON
 PLANS, HOWEVER PANEL SCHEDULES DO NOT
 INDICATE ANY FEEDING OF SAID PANEL.
 215.5
 PLEASE ALSO VERIFY GFI RECEPT IN FRONT
 OF HOUSE BEING FED FROM THIS PANEL?
  
 ** PLEASE SUBMIT TWO COMPLETE SETS OF
 PLANS FOR REVIEW. PLEASE BE SURE TO
 INSERT ALL ELECTRICAL MECHANICAL PLANS
 INTO HOUSE SETS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT NEW REVISED
 SHEETS INTO THE TWO COMPLETED SETS FOR
 REVIEW AND STAMPING. PLEASE SEE ONE SET
 OF OLD/VOIDED SHEETS SHOUDL EB SUBMTTED
 FOR REFERENCE ONLY
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THEREARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 *** VALUATION FOR COMPLETE SCOPE
 INCLUDING GENERATOR INOT ELECTRICAL
 SHALL BE INCREASED
2006-02-14 00:00:00REVIEW IN PROGRESS, NOTES TO FOLLOW.
 PLANS WILL GO INTO "F" STATUS.